41
Servicing should only be performed by a Qualified Service Technician
BLOWER SPEED CONTROL BTH 199 AND 250
The input of the BTH 199 and BTH 250 is determined by blower. The input of the water heater may be
determined by clocking the meter as shown on Page 5 or by making sure the blower is receiving the proper
signal. The blower rpm is controlled by the Central Control Board (CCB). The rpm of the blower may be
measured by attaching a MULTIMETER that has a Hertz (Hz) setting as shown in the illustration below. If
the Hz signal is /-5% of the numbers in the chart below the reading is normal.
Model
High Speed Hz
Low Speed Hz
199 N
182
172
250 N
227
178
199 Propane (LP)
200
194
250 Propane (LP)
254
191
Note:
Removing the plug shown in the illustration will cause the blower to accelerate and the input of the
water heater to increase to a much higher rate. This may cause damage to the water heater.
Meter black lead is connected to ground (not shown) and the red lead is connected to an open terminal on
blower speed control connection.
Meter red probe
connected to open
terminal on plug
Содержание BTH 120 Series
Страница 2: ......
Страница 31: ...29 Servicing should only be performed by a Qualified Service Technician CONTROL SEQUENCE FLOW CHART ...
Страница 33: ...31 Servicing should only be performed by a Qualified Service Technician This is the back of the UIM ...
Страница 46: ...44 Servicing should only be performed by a Qualified Service Technician WIRING DIAGRAM BTH 120 300 ...
Страница 47: ...45 Servicing should only be performed by a Qualified Service Technician WIRING DIAGRAM BTH 400 500 ...
Страница 48: ...46 Servicing should only be performed by a Qualified Service Technician NOTES ...
Страница 49: ...47 Servicing should only be performed by a Qualified Service Technician NOTES ...