A.O. Smith BTH 120-250(A) Скачать руководство пользователя страница 30

30

MOTOR WILL NOT RUN

1. Confirm 120V AC to the controller. Also, to verify correct polarity, check

for 120 V AC between hot supply and ground.

If there is no voltage, check for a loose connection where it connects to
the controller.

2. If there is 120 volts to the controller, check for loose connections or a

locked rotor. If the rotor cannot be freed the motor and blower assembly
must be replaced.

MOTOR RUNS, PREPURGE TIME ELAPSES BUT MAIN

FLAME NOT ESTABLISHED.

1. Check to see if main manual gas valve is open.

2. Check for a loose connection at the transformer, or a defective

transformer.

3. Check for a loose connection at the gas valve.

4. Check for open pressure switches or open reset button. Check for

blockage in the intake and exhaust venting or at the vent hoods. If no
blockage is found, check vinyl tubing for cuts or crimps. If this tubing is
damaged it must be replaced. If these steps do not eliminate the problem,
replace the pressure switches.

5. Check to see if there is resistance across the igniter terminal with an

OHM meter. If there is no continuity, the igniter is broken and should be
replaced.

If the igniter appears to function properly, then verify that the inlet
pressure is 12" Natural Gas (3 kPa) and 14.0" L.P. Gas (3.45 kPa) W.C.
maximum. The gas valve supplied on this appliance is not designed to
open against a higher pressure. At this time also check that the inlet
pressure is not lower than the minimal gas supply pressure, as shown
in Table 4: that is, for Natural Gas, 5.0" (1.25 kPa) W.C. for BTH 120 &
250 or 4.5"  (1.1 kPa) W.C. for BTH 150 & 199 or; for L.P. Gas, 11.0"
(2.74 kPa) W.C. if the inlet pressure is not within these limits then adjust
the supply pressure accordingly.

If the inlet pressure falls within the allowable limits, then verify that the
manifold pressure, when the gas is fully open, with the heater running,
is as called out in Table 4:  that is, for Natural Gas, 4.0" (1 kPa)  W.C. for
BTH 120 & 250 or 3.5" (.9 kPa)  W.C. for BTH 150 & 199 or; for L.P. Gas,
10.0"  (2.5 kPa) W.C. If the manifold pressure is not correct then adjust
accordingly.  See ADJUSTMENT PROCEDURE in OPERATING
INSTRUCTIONS selection, page 18, for the manifold pressure adjustment
procedure.

6. If the inlet and manifold pressures are within the limits specified in step

5, then reset the appliance. Verify 24V AC at the gas valve during the
three (3) second ignition trial, after the igniter reaches operating
temperature. If 24V AC at the gas valve is not seen during this period,
the controller must be replaced.

If there is 24V AC at the gas valve during the four second ignition trial
and the manifold pressure does not increase above 0" W.C. then verify
that the manual gas control valve is in the “ON” position (see page 20).
If the valve is in the “ON” position and the previous voltage and gas
pressure conditions are met, then the gas valve is defective and must
be replaced.

Note that a positive manifold pressure reading of approximately
1.5" (.38 kPa) W.C. is normal during the prepurge portion of the ignition
cycle due to the location of the gas orifice.

MOTOR RUNS, BURNER LIGHTS MOMENTARILY,

THEN LOCKS OUT

1. Reset the appliance two more times to ensure that all of the air has been

purged from the gas line.

2. If the burner lights momentarily but does not sustain ignition, verify that

the inlet pressure is not greater than 14.0" (3.5 kPa) W.C. or lower than

the minimal gas supply pressure, as shown in Table 4: that is, for
Natural Gas, 5.0" (1.25 kPa) W.C. for BTH 120 & 250 or 4.5" (1.1 kPa)
W.C. for BTH 150 & 199 or; for L.P. Gas, 11.0" (2.74 kPa) W.C. pressure.
Also, the manifold pressure should rise during the three (3) second trial
for ignition to the manifold pressure value for the individual unit listed in
Table 4: that is, for Natural Gas, 4.0" (1 kPa) W.C. for BTH 120 & 250 or
3.5" (.9 kPa) W.C. for BTH 150 & 199 or; for L.P. Gas, 10.0" (2.5 kPa)
W.C. If the manifold pressure is not correct then adjust accordingly. See
ADJUSTMENT PROCEDURE in OPERATING INSTRUCTIONS section, page
18, for the manifold pressure adjustment procedure.

3. Check for the reversed polarity in the supply wiring. This controller is

polarity sensitive. If the hot and neutral supply wires are reversed, the
controller will not sense flame. Reverse the supply wires and try to fire
the unit.

NOTE:  

Always turn off and disconnect main supply wiring before servicing

the unit.

4. Check connecting wire to the flame sensor. Verify that the flame sensor

has not been damaged in any way.

5. Verify that the air supply is adequate. The air inlet screen or blower

wheel may be restricted. Also, check the installation for proper ventilation.
See AIR REQUIREMENTS.

6. Check the venting system for the correct sizing, excess or insufficient.

See VENTING.

7. Check for a maximum inlet pressure of 12" Natural Gas (3 kPa), 14.0"

L.P. Gas (3.45 kPa) W.C. and the manifold pressure as listed in Table 4:
that is, for Natural Gas, 4.0" (1 kPa) W.C. for BTH 120 & 250 or 3.5" (.9
kPa) W.C. for BTH 150 & 199 or; for L.P. Gas, 10.0" (2.5 kPa) W.C.
Please note that the manifold pressure listed is the maximum value for
the manifold pressure. Do not set the manifold pressure higher than the
value shown for your heater in Table 4. Overfiring the heater will result
in rough ignition and/or noisy operation.

8. Confirm that the air inlet screen (see Figures 7 & 8) is free of obstructions.

 

 

CAUTION

Do not reach into the burner housing or combustion chamber if
the heater is still hot. Allow the heater to cool and always use
gloves as the combustion chamber and the burner sleeve and
housing can become very hot after operation. Overfiring is a
dangerous condition that must be corrected immediately.

NOISY BURNER OPERATION

The exhaust of this unit produces some noise. This noise may be
objectionable if the exhaust terminal is located too close to the opening of
an occupied space. The noise may also be objectionable if the exhaust is
located in the confined space between two buildings such as an alley or
walkway. Since everyone's perception and tolerance for background noise
varies, there is no standard recommendation. The best option when the
noise is a concern is to locate the exhaust as far away from any occupied
spaces as practical.

If noise becomes more than one can tolerate, a dampening muffler is available
through our Product Service Division. See “REPLACEMENT PARTS” segment
below.

GAS FAILS TO SHUT OFF

Check for defective gas valve or thermostat. If operation is incorrect,
replace.

REPLACEMENT PARTS

Replacement parts may be ordered through A.O. Smith dealers, authorized
servicers or distributors. Refer to the Yellow Pages for where to call or
contact the A.O. Smith Water Products Company, 5621 W. 115th Street,
Alsip, IL  60803, 1-800-433-2545. When ordering parts be sure to state the
quantity, part number and description of the items including the complete
model and serial number as it appears on the product. Refer to the parts list
for more information.

Содержание BTH 120-250(A)

Страница 1: ...FORE INSTALLING AND USING THIS APPLIANCE INSTALLATION OPERATION SERVICE MAINTENANCE LIMITED WARRANTY WARNING If the information in these instructions is not followed exactly a fire or explosion may result causing property damage personal injury or death Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do n...

Страница 2: ... ProtectionAssociation 1 Batterymarch Park Quincy MA02269 FOREWORD CYCLONE XHE BTH 120 250 ROUGH IN DIMENSIONS TEMPERATURE RISE DEGREES C LITERS PER HOUR Approx Input Liter Model kW Capacity 17 C 22 C 28 C 33 C 39 C 44 C 50 C 56 C 61 C 67 C 72 C 78 C BTH 120 37 Nat 227 1798 1348 1079 898 768 674 598 538 488 450 416 386 BTH 120 35 L P 227 1726 1295 1037 863 738 647 575 519 469 432 397 371 BTH 150 4...

Страница 3: ...tion WATER TEMPERATURE CONTROL TABLE OF CONTENTS ROUGH INDIMENSIONS 2 FOREWORD 2 FEATURES 3 4 Water Temperature Control 3 High Limit Switch E C O 4 Dishwashing Machine Requirement 4 Circulating Pump 4 INSTALLATIONINSTRUCTIONS 4 13 Required Ability 4 Insulation Blankets 4 5 Locating The Heater 5 Clearances 5 Hard Water 6 Air Requirements 6 Mechanical Exhausting of Room Air 6 Unconfined Space 6 Conf...

Страница 4: ...n Foundation requirements are designed to operate with water flow pressures between 15 and 25 pounds per square inch 103 Kpa and 173 Kpa Flow pressures above 25 pounds per square inch 173 Kpa or below 15 pounds per square inch 103 Kpa will result in improperly sanitized dishes Where pressures are high a water pressure reducing or flow regulating control valve should be used in the 180 F 82 C line ...

Страница 5: ...quality water pressure and the environment in which the water heater is installed Water heaters are sometimes installed in locations where leakage may result in property damage even with the use of a drain pan piped to a drain However unanticipated damage can be reduced or prevented by a leak detector or water shut off device used in conjunction with a piped drain pan These devices are available f...

Страница 6: ...UNLESS RUBBER ISOLATION PIPE HANGERSARE USED THIS PREVENTSANY VIBRATIONS FROM BEING ALCOVE HARDWATER Where hard water conditions exist water softening or the threshold type of water treatment is recommended This will protect the dishwashers coffee urns water heaters water piping and other equipment See MAINTENANCE section for details of tank cleanout procedure AIR REQUIREMENTS KEEP APPLIANCE AREA ...

Страница 7: ...RMINATE EXHAUST OVER PUBLIC AREA WHERE CONDENSATE OR VAPOR CAN CAUSE NUISANCE OR HAZARD ON DIRECT VENT INSTALLATIONS EXHAUST VENT HOOD MUST BE LOCATED 1 30 5cm MINIMUM FROM ANY OPENING IN BUILDING ON DIRECT VENT INSTALLATIONS EXHAUST VENT HOOD MUST BE LOCATED 4 122cm MINIMUM FROM ANY OPENING IN BUILDING ...

Страница 8: ... the vent system layout so that proper clearances are maintained from plumbing and wiring Vent pipes serving power vented appliances are classified by building codes as vent connectors Required clearances from combustible materials must be provided in accordance with information in this manual under LOCATION OF HEATER and CLEARANCES and with National Fuel Gas Code and local Codes IMPORTANT Plan th...

Страница 9: ... wall Align the holes by drilling a hole through the center of the template from the inside through to the outside The template can now be positioned on the outside wall using the drilled holes as a centering point for the template 3 A MASONRY SIDE WALLS Chisel an opening approximately 1 2 1 3 cm larger than the marked circle B WOODEN SIDE WALLS Drill a pilot hole approximately one quarter inch ou...

Страница 10: ...tions should be sealed with a plumbing roof boot or equivalent flashing 3 The intake vent termination and the exhaust vent termination must penetrate the same side of roof 4 The center line of the intake vent termination and the center line of the exhaust vent termination must be no closer than 24 61cm 5 The intake vent terminal and the exhaust vent terminal must be oriented facing downward and th...

Страница 11: ...90 elbows with the 4 inch venting is six 6 on the intake and six 6 on the exhaust A 90 elbow is equal to five 5 equivalent feet 1 5m of pipe One 1 90 elbow is equal to two 2 45 elbows Any venting configuration using less than 50 equivalent feet should use 3 inch venting See Table 2 The 3 inch venting terminals provided must be used with the 4 inch venting by adding 4x3 reducing couplings at the ve...

Страница 12: ...h is considered normal for low pressure systems Note that fittings such as elbows and tees will add to the pipe pressure drop CAUTION DO NOT USE FLEXIBLE GAS PIPING TABLE 3 MAXIMUM CAPACITY OF PIPE IN CUBIC FEET OF GAS PER HOUR Based upon a Pressure Drop of 0 5 inch Water Column and 0 6 Specific Gravity Gas and max gas pressure of 0 5 psig WARNING THE HEATER IS NOT INTENDED FOR OPERATIONAT HIGHER ...

Страница 13: ...ter is too small ask the gas company to install a larger meter having adequate capacity GAS PRESSURE REGULATION Main line gas pressure to the water heater should be between a maximum 14 0 3 45Kpa W C and a minimum as shown in Table 4 that is for Natural Gas 5 0 1 25Kpa W C for BTH 120 250 or 4 5 1 12Kpa W C for BTH 150 199 or for L P Gas 11 0 2 74Kpa W C The inlet gas pressure must not exceed the ...

Страница 14: ...TER TANK IS FILLED WITH WATER NOTE This controller is Polarity Sensitive If the Hot and Neutral Supply Voltage is reversed the controller will not sense flame Verify polarity before connecting the unit WATER LINE CONNECTIONS This manual provides detailed installation diagrams see back section of this manual for typical methods of application for the water heaters The water heater may be installed ...

Страница 15: ...y return to Step 2 and repeat the entire operating cycle SELF DIAGNOSTIC CONTROLLER A green LED is mounted on the Main Control Board to indicate line voltage polarity is properly connected The green LED is mounted next to connector CN1 Line input connection When 120 VAC input power is properly connected to the Main Control Board the green LED will illuminate If an error is made when connecting 120...

Страница 16: ... Clogged gas valve 6 Replace gas valve 7 Faulty gas valve 7 Replace gas valve 8 Defective control 8 Replace control 9 Burner improperly adjusted 9 Adjust burner 10 Dirty burner 10 Clean burner GAS VALVE LED FLASHING This condition results from a failure to establish burner ignition after three successive trials In such cases 1 Investigate the possible cause and remedy any observations 2 Momentaril...

Страница 17: ...ntrol problem 2 Water in tank above freezing 2 Temperature probe out of tolerance replace temp probe PossibleCause Remedy 1 Water in tank is low probe 1 Fill tank immersed in steam 2 Probe wiring shorted 2 Repair wiring 3 Defective probe 3 Replace probe PossibleCause Remedy 1 Temp Probe unplugged 1 Check connectors 2 Temp probe wiring damaged 2 Repair wiring 3 Water in tank too hot 3 Normal condit...

Страница 18: ...ect orifice PRIOR TO START UP REQUIRED ABILITY INSTALLATION OR SERVICE OFTHIS WATER HEATER REQUIRESABILITY EQUIVALENT TO THAT OF A LICENSED TRADESMAN IN THE FIELD INVOLVED PLUMBING AIR SUPPLY VENTING GAS SUPPLY AND ELECTRICALWORKAREREQUIRED Before attempting start up thoroughly study and familiarize yourself with the exact sequence of operation and all other details on the specific heater being us...

Страница 19: ...19 FORYOUR SAFETYREAD BEFORE OPERATING WARNING If you do not follow these instructions exactly a fire or explosion may result causing property damage personal injury or loss of life ...

Страница 20: ...LATIONS WARNING BTH HEATERSARE CERTIFIED FOR USE WITHOUT MODIFICATION FOR ALTITUDES UP TO 6500 FEET INSTALLATIONSABOVE 6500 FEET MAY REQUIRE REPLACEMENT OF THE BURNER ORIFICE CALL THE TECHNICAL CENTER 800 527 1953 FOR REQUIREMENTS Some gas utility companies derate their gas for altitude making it unneccessary to install high altitude orifices Call the local gas or utlity company to verify BTU cont...

Страница 21: ...alve when finished flushing 4 Turn on the heater electrical disconnect switch DRAINING The heater must be drained if it is to be shut down and exposed to freezing temperatures Maintenance and service procedures may also require draining the heater 1 Turn off the heater electrical disconnect switch 2 Close the cold water inlet valve to heater 3 Open a nearby hot water faucet to vent the system 4 Op...

Страница 22: ...and a tank explosion In areas with poor water conditions it may be necessary to inspect the T P valve more often than every three years CAUTION BEFORE MANUALLY OPERATING THE VALVE MAKE SURE THAT A DRAIN LINE HAS BEEN ATTACHED TO THE VALVE TO DIRECT THE DISCHARGE TOAN OPEN DRAIN FAILURE TO TAKE THIS PRECAUTION COULD MEAN CONTACT WITH EXTREMELY HOT WATER PASSING OUT THE VALVE DURING THIS CHECKING OP...

Страница 23: ...OT WATER SUPPLIED TO FIXTURES PIPE TO OPEN DRAIN INSTALLINACCORDANCE WITH LOCAL CODES CAUTION IF BUILDING COLD WATER SUPPLY HAS A BACK FLOW PREVENTER CHECK VALVEORWATERMETERWITH CHECK VALVE PROVISIONS FOR THERMALEXPANSION OF WATER IN THE HOT WATER SYSTEM MUST BE PROVIDED NOTE CONNECT RETURN LINE FROM HOT WATER CIRCULATING LOOP IF USED TO COLD WATER INLET LINE PIPE TO OPEN DRAIN INSTALLINACCORDANCE...

Страница 24: ...DANGER TEMPERATURE SETTING SHOULD NOT EXCEED SAFE TEMPERATUREATFIXTURES SEEWATERTEMPERATURE CONTROL WARNING ON PAGE 4 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD AN ANTI SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES CAUTION IF BUILDING COLD WATER SUPPLY HAS A BACK FLOW PREVENTER CHECK VALVE OR WATER METERWITHCHECKVALVEPROVISIONSFORTHERMAL EXPANSION OF WATER ...

Страница 25: ...IT SPECIFICATIONS PAGE28 CAUTION IF BUILDING COLD WATER SUPPLY HAS A BACK FLOW PREVENTER CHECK VALVE OR WATER METER WITH CHECK VALVE PROVISIONS FOR THERMALEXPANSION OF WATER IN THE HOT WATER SYSTEM MUST BE PROVIDED DANGER TEMPERATURE SETTING SHOULD NOT EXCEED SAFE TEMPERATURE ATFIXTURES SEEWATERTEMPERATURECONTROLWARNINGONPAGE 4 IF HIGHER PREHEAT TEMPERATURESARE NECESSARY TO OBTAIN ADEQUATE BOOSTER...

Страница 26: ...ECTCIRCULATINGLINEOF180 F 82 C ORBOOSTEDWATER IF USED TO INLETWATER LINETO BOOSTER INSTALLINACCORDANCE WITH LOCALCODES TWO TEMPERATURE TWO HEATERS ONE PRE HEATER ONE BOOSTER HEATER WITH OR WITHOUT BUILDING RECIRCULATION DANGER TEMPERATURE SETTING SHOULD NOT EXCEED SAFE TEMPERATURE ATFIXTURES SEEWATERTEMPERATURECONTROLWARNINGONPAGE 4 IF HIGHER PREHEAT TEMPERATURESARE NECESSARY TO OBTAIN ADEQUATE BO...

Страница 27: ...TANK NOTE4 IFTEMPEREDWATERISRECIRCULATED RETURNLINESHOULD BE CONNECTEDATPOINTA DANGER TEMPERATURE SETTING SHOULD NOT EXCEED SAFE TEMPERATURE ATFIXTURES SEEWATERTEMPERATURECONTROLWARNINGONPAGE 5 IF HIGHER PREHEAT TEMPERATURESARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD ANANTI SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES CAUTION IF BUILDING COLD WATER SUPPLY HAS A BACK FLOW PREVENTER CHECK ...

Страница 28: ...ter heating and storage potential of the system cannot be achieved Plus the units with the higher water flow may have a shortened life Unions shown in piping diagrams are not included in the manifold kits Dimensions shown are for minimum space occupied by the water heaters assemblies Space for the venting system and unit servicing must be added ...

Страница 29: ...o see if the water heater drain valve is tightly closed Also check the cleanout opening for leakage 2 The apparent leakage may be condensation which forms on cool surfaces of the heater and piping 3 If the outlet of the relief valve is leaking it may represent Excessive water pressure Excessive water temperature Faulty relief valve Excessive water pressure is the most common cause of relief valve ...

Страница 30: ...a W C or lower than the minimal gas supply pressure as shown in Table 4 that is for Natural Gas 5 0 1 25 kPa W C for BTH 120 250 or 4 5 1 1 kPa W C for BTH 150 199 or for L P Gas 11 0 2 74 kPa W C pressure Also the manifold pressure should rise during the three 3 second trial for ignition to the manifold pressure value for the individual unit listed in Table 4 that is for Natural Gas 4 0 1 kPa W C...

Страница 31: ... to unless an effective method of controlling thermal expansion is also installed at the heater s and operational at all times The relief valve installed on the heater is not an acceptable method 4 SERVICEAND REPAIR EXPENSES Under the limited warranty the warrantor will provide only a replacement water heater or part thereof The owner is responsible for all other costs Such costs may include but a...

Страница 32: ...32 A O SMITH WATER PRODUCTS COMPANY 5621 W 115TH STREET ALSIP ILLINOIS 60803 PHONE 1 800 433 2545 FAX 1 800 433 2515 www hotwater com E MAIL parts hotwater com ...

Отзывы: