BLOCKED OUTLET PROVER SWITCH

(SEE FIGURE 13)

The Blocked Outlet Prover Switch is set up to shut the unit off when a build-
up of positive pressure in the exhaust vent pipe occurs. This switch is a
positive pressure switch that requires an increase in pressure to change
the electrical contacts from normally closed to open. When this switch
prevents the unit from igniting, most likely the exhaust is blocked by some
means Check to see if the condensate is allowed to flow freely from the
exhaust elbow and for obstructions in the exhaust venting and exhaust
vent terminal. Also verify that there is no more than fifty equivalent feet
(15.2 m)  of three inch PVC vent pipe on the exhaust.

BLOCKED INLET PROVER SWITCH

(SEE FIGURE 13)

The Blocked Inlet Prover Switch is set up to shut the unit off when a build-
up of negative pressure in the intake vent pipe occurs. This switch is a
negative pressure switch that requires an increase in negative pressure
to change the electrical contacts from normally closed to open. The switch
is connected to the pressure tap on the PVC flange connected to the inlet
of the blower. When this switch prevents the unit from igniting, most likely
the intake is blocked by some means. Check to see if there is no more than
fifty equivalent feet (15.2 m) of three inch PVC vent pipe on the intake. Also
verify that the intake and intake vent terminal is free of obstructions that
may prevent air from entering the unit.

LOW GAS PRESSURE SWITCH

(SEE FIGURE 13)

The Low Gas Switch (LGS) is a single-pole, normally open pressure switch
that will close its contacts when a rising pressure of 5.0 in. (1.25Kpa)  W.C.
is encountered. The contacts will open when the pressure falls below the
fixed set point of 5.0 in. (1.25Kpa) W.C. The LGS monitors the gas supply
pressure to the  heater. If the gas supply falls below 5.0 in. (1.25Kpa) W.C.,
the main burner is extinguished (if heater is running) or the heater will not
start up.

ON/OFF SWITCH

The ON/OFF Switch is a single-pole, single-throw rocker switch. This
switch provides 120V from the line source to the heater.

 

CAUTION

THE WATER HEATER IS POLARITY SENSITIVE. BEFORE APPLYING
ELECTRICITY TO THIS HEATER BE CERTAIN THAT SUPPLY NEUTRAL
WIRE TO GROUND CHECK INDICATES ZERO VOLTAGE.

HOT SURFACE IGNITER

The Hot Surface Igniter is a device that ignites the main burner by high
temperature (>1800°F or >982°C). When 120VAC is applied to the igniter,
sufficient heat is generated to ignite the main burner. Although improvements
have been made to strengthen the igniter, it is still fragile and care must be
taken when handling the igniter to prevent breakage.

GAS PIPING

Contact your local gas service company to ensure that adequate gas
service is available and to review applicable installation codes for your
area.

Size the main gas line in accordance with Table 3. The figures shown are
for straight lengths of pipe at 0.5 in. (125Pa) W.C. pressure drop, which is
considered normal for low pressure systems Note that fittings such as
elbows and tees will add to the pipe pressure drop.

 

CAUTION

DO NOT USE FLEXIBLE GAS PIPING.

TABLE 3

MAXIMUM CAPACITY OF PIPE IN CUBIC FEET OF GAS PER HOUR

(Based upon a Pressure Drop of 0.5 inch Water Column

and 0.6 Specific Gravity Gas and max. gas pressure of 0.5 psig)

 

WARNING

THE HEATER IS NOT INTENDED FOR OPERATION AT HIGHER THAN 14.0"
WATER COLUMN (1/2 POUND or 3.45Kpa PER SQUARE INCH) SUPPLY
GAS PRESSURE. HIGHER  GAS SUPPLY PRESSURES REQUIRE
SUPPLEMENTAL REDUCING SERVICE REGULATION. EXPOSURE TO
HIGHER GAS SUPPLY PRESSURE MAY CAUSE DAMAGE TO THE GAS
CONTROLS WHICH COULD RESULT IN FIRE OR EXPLOSION. IF
OVERPRESSURE HAS OCCURRED SUCH AS THROUGH IMPROPER
TESTING OF GAS LINES OR EMERGENCY MALFUNCTION OF THE
SUPPLY SYSTEM THE GAS VALVE MUST BE CHECKED FOR SAFE
OPERATION. MAKE SURE THAT THE OUTSIDE VENTS ON THE SUPPLY
REGULATORS AND THE SAFETY VENT VALVES ARE PROTECTED
AGAINST BLOCKAGE. THESE ARE PARTS OF THE GAS SUPPLY
SYSTEM, NOT THE HEATER. VENT BLOCKAGE MAY OCCUR DURING
ICE STORMS.

IT IS IMPORTANT TO GUARD AGAINST GAS VALVE FOULING FROM
CONTAMINANTS IN THE GAS WAYS. SUCH FOULING MAY CAUSE
IMPROPER OPERATION, FIRE OR EXPLOSION.

IF COPPER SUPPLY LINES ARE USED THEY MUST BE INTERNALLY
TINNED AND CERTIFIED FOR GAS SERVICE.

BEFORE ATTACHING THE GAS LINE BE SURE THAT ALL GAS PIPE IS
CLEAN ON THE INSIDE.

TO TRAP ANY DIRT OR FOREIGN MATERIAL IN THE GAS SUPPLY LINE,
A DIRT LEG (SOMETIMES CALLED A SEDIMENT TRAP OR DRIP LEG)
MUST BE INCORPORATED IN THE PIPING (SEE FIG. 14). THE DIRT LEG
MUST BE READILY ACCESSIBLE AND NOT SUBJECT TO FREEZING
CONDITIONS. INSTALL IN ACCORDANCE WITH RECOMMENDATIONS
OF SERVING GAS SUPPLIERS. REFER TO THE NATIONAL FUEL GAS
CODE.

FIGURE 14

  LENGTH

NORMAL IRON PIPE SIZES (INCHES)

IN

    INPUT IN THOUSANDS BTU/HR

 FEET

1/2"

3/4"

1"

1 1/4" 1 1/2"

2"

2 1/2"

3"

4"

10

175

360

680

1400

2100

3960

6300

11000 23000

20

120

250

485

950

1460

2750

4360

7700

15800

30

97

200

375

770

1180

2200

3520

6250

12800

40

82

170

320

660

990

1900

3000

5300

10900

50

73

151

285

580

900

1680

2650

4750

9700

60

66

138

260

530

810

1520

2400

4300

8800

70

61

125

240

490

750

1400

2250

3900

8100

80

57

118

220

460

690

1300

2050

3700

7500

90

53

110

205

430

650

1220

1950

3450

7200

100

50

103

195

400

620

1150

1850

3250

6700

125

44

93

175

360

550

1020

1650

2950

6000

150

40

84

160

325

500

950

1500

2650

5500

175

37

77

145

300

460

850

1370

2450

5000

200

35

72

135

280

430

800

1280

2280

4600

  LENGTH

NORMAL IRON PIPE SIZES (INCHES)

 IN

                  INPUT IN KW

  METERS 1/2"

3/4"

1"

1 1/4" 1 1/2"

2"

2 1/2"

3"

4"

3.0

51

105

199

410

615

1160

1845

3221

6735

6.1

35

73

142

278

428

805

1277

2255

4626

9.1

28

59

110

225

346

644

1031

1830

3748

12.2

24

50

94

193

290

556

878

1552

3192

15.2

21

44

83

170

264

492

776

1391

2840

18.3

19

40

76

155

237

445

703

1259

2577

21.3

18

37

70

143

220

410

659

1142

2372

24.4

17

35

64

135

202

381

600

1083

2196

27.4

16

32

60

126

190

357

571

1010

2108

30.5

15

30

57

117

182

337

542

952

1962

38.1

13

27

51

105

161

299

483

864

1757

45.7

12

25

47

95

146

278

439

776

1610

53.3

11

23

42

88

135

249

401

717

1464

61.0

10

21

40

82

126

234

375

688

1347

Содержание BTH 120-250(A)

Страница 1: ...FORE INSTALLING AND USING THIS APPLIANCE INSTALLATION OPERATION SERVICE MAINTENANCE LIMITED WARRANTY WARNING If the information in these instructions is not followed exactly a fire or explosion may result causing property damage personal injury or death Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do n...

Страница 2: ... ProtectionAssociation 1 Batterymarch Park Quincy MA02269 FOREWORD CYCLONE XHE BTH 120 250 ROUGH IN DIMENSIONS TEMPERATURE RISE DEGREES C LITERS PER HOUR Approx Input Liter Model kW Capacity 17 C 22 C 28 C 33 C 39 C 44 C 50 C 56 C 61 C 67 C 72 C 78 C BTH 120 37 Nat 227 1798 1348 1079 898 768 674 598 538 488 450 416 386 BTH 120 35 L P 227 1726 1295 1037 863 738 647 575 519 469 432 397 371 BTH 150 4...

Страница 3: ...tion WATER TEMPERATURE CONTROL TABLE OF CONTENTS ROUGH INDIMENSIONS 2 FOREWORD 2 FEATURES 3 4 Water Temperature Control 3 High Limit Switch E C O 4 Dishwashing Machine Requirement 4 Circulating Pump 4 INSTALLATIONINSTRUCTIONS 4 13 Required Ability 4 Insulation Blankets 4 5 Locating The Heater 5 Clearances 5 Hard Water 6 Air Requirements 6 Mechanical Exhausting of Room Air 6 Unconfined Space 6 Conf...

Страница 4: ...n Foundation requirements are designed to operate with water flow pressures between 15 and 25 pounds per square inch 103 Kpa and 173 Kpa Flow pressures above 25 pounds per square inch 173 Kpa or below 15 pounds per square inch 103 Kpa will result in improperly sanitized dishes Where pressures are high a water pressure reducing or flow regulating control valve should be used in the 180 F 82 C line ...

Страница 5: ...quality water pressure and the environment in which the water heater is installed Water heaters are sometimes installed in locations where leakage may result in property damage even with the use of a drain pan piped to a drain However unanticipated damage can be reduced or prevented by a leak detector or water shut off device used in conjunction with a piped drain pan These devices are available f...

Страница 6: ...UNLESS RUBBER ISOLATION PIPE HANGERSARE USED THIS PREVENTSANY VIBRATIONS FROM BEING ALCOVE HARDWATER Where hard water conditions exist water softening or the threshold type of water treatment is recommended This will protect the dishwashers coffee urns water heaters water piping and other equipment See MAINTENANCE section for details of tank cleanout procedure AIR REQUIREMENTS KEEP APPLIANCE AREA ...

Страница 7: ...RMINATE EXHAUST OVER PUBLIC AREA WHERE CONDENSATE OR VAPOR CAN CAUSE NUISANCE OR HAZARD ON DIRECT VENT INSTALLATIONS EXHAUST VENT HOOD MUST BE LOCATED 1 30 5cm MINIMUM FROM ANY OPENING IN BUILDING ON DIRECT VENT INSTALLATIONS EXHAUST VENT HOOD MUST BE LOCATED 4 122cm MINIMUM FROM ANY OPENING IN BUILDING ...

Страница 8: ... the vent system layout so that proper clearances are maintained from plumbing and wiring Vent pipes serving power vented appliances are classified by building codes as vent connectors Required clearances from combustible materials must be provided in accordance with information in this manual under LOCATION OF HEATER and CLEARANCES and with National Fuel Gas Code and local Codes IMPORTANT Plan th...

Страница 9: ... wall Align the holes by drilling a hole through the center of the template from the inside through to the outside The template can now be positioned on the outside wall using the drilled holes as a centering point for the template 3 A MASONRY SIDE WALLS Chisel an opening approximately 1 2 1 3 cm larger than the marked circle B WOODEN SIDE WALLS Drill a pilot hole approximately one quarter inch ou...

Страница 10: ...tions should be sealed with a plumbing roof boot or equivalent flashing 3 The intake vent termination and the exhaust vent termination must penetrate the same side of roof 4 The center line of the intake vent termination and the center line of the exhaust vent termination must be no closer than 24 61cm 5 The intake vent terminal and the exhaust vent terminal must be oriented facing downward and th...

Страница 11: ...90 elbows with the 4 inch venting is six 6 on the intake and six 6 on the exhaust A 90 elbow is equal to five 5 equivalent feet 1 5m of pipe One 1 90 elbow is equal to two 2 45 elbows Any venting configuration using less than 50 equivalent feet should use 3 inch venting See Table 2 The 3 inch venting terminals provided must be used with the 4 inch venting by adding 4x3 reducing couplings at the ve...

Страница 12: ...h is considered normal for low pressure systems Note that fittings such as elbows and tees will add to the pipe pressure drop CAUTION DO NOT USE FLEXIBLE GAS PIPING TABLE 3 MAXIMUM CAPACITY OF PIPE IN CUBIC FEET OF GAS PER HOUR Based upon a Pressure Drop of 0 5 inch Water Column and 0 6 Specific Gravity Gas and max gas pressure of 0 5 psig WARNING THE HEATER IS NOT INTENDED FOR OPERATIONAT HIGHER ...

Страница 13: ...ter is too small ask the gas company to install a larger meter having adequate capacity GAS PRESSURE REGULATION Main line gas pressure to the water heater should be between a maximum 14 0 3 45Kpa W C and a minimum as shown in Table 4 that is for Natural Gas 5 0 1 25Kpa W C for BTH 120 250 or 4 5 1 12Kpa W C for BTH 150 199 or for L P Gas 11 0 2 74Kpa W C The inlet gas pressure must not exceed the ...

Страница 14: ...TER TANK IS FILLED WITH WATER NOTE This controller is Polarity Sensitive If the Hot and Neutral Supply Voltage is reversed the controller will not sense flame Verify polarity before connecting the unit WATER LINE CONNECTIONS This manual provides detailed installation diagrams see back section of this manual for typical methods of application for the water heaters The water heater may be installed ...

Страница 15: ...y return to Step 2 and repeat the entire operating cycle SELF DIAGNOSTIC CONTROLLER A green LED is mounted on the Main Control Board to indicate line voltage polarity is properly connected The green LED is mounted next to connector CN1 Line input connection When 120 VAC input power is properly connected to the Main Control Board the green LED will illuminate If an error is made when connecting 120...

Страница 16: ... Clogged gas valve 6 Replace gas valve 7 Faulty gas valve 7 Replace gas valve 8 Defective control 8 Replace control 9 Burner improperly adjusted 9 Adjust burner 10 Dirty burner 10 Clean burner GAS VALVE LED FLASHING This condition results from a failure to establish burner ignition after three successive trials In such cases 1 Investigate the possible cause and remedy any observations 2 Momentaril...

Страница 17: ...ntrol problem 2 Water in tank above freezing 2 Temperature probe out of tolerance replace temp probe PossibleCause Remedy 1 Water in tank is low probe 1 Fill tank immersed in steam 2 Probe wiring shorted 2 Repair wiring 3 Defective probe 3 Replace probe PossibleCause Remedy 1 Temp Probe unplugged 1 Check connectors 2 Temp probe wiring damaged 2 Repair wiring 3 Water in tank too hot 3 Normal condit...

Страница 18: ...ect orifice PRIOR TO START UP REQUIRED ABILITY INSTALLATION OR SERVICE OFTHIS WATER HEATER REQUIRESABILITY EQUIVALENT TO THAT OF A LICENSED TRADESMAN IN THE FIELD INVOLVED PLUMBING AIR SUPPLY VENTING GAS SUPPLY AND ELECTRICALWORKAREREQUIRED Before attempting start up thoroughly study and familiarize yourself with the exact sequence of operation and all other details on the specific heater being us...

Страница 19: ...19 FORYOUR SAFETYREAD BEFORE OPERATING WARNING If you do not follow these instructions exactly a fire or explosion may result causing property damage personal injury or loss of life ...

Страница 20: ...LATIONS WARNING BTH HEATERSARE CERTIFIED FOR USE WITHOUT MODIFICATION FOR ALTITUDES UP TO 6500 FEET INSTALLATIONSABOVE 6500 FEET MAY REQUIRE REPLACEMENT OF THE BURNER ORIFICE CALL THE TECHNICAL CENTER 800 527 1953 FOR REQUIREMENTS Some gas utility companies derate their gas for altitude making it unneccessary to install high altitude orifices Call the local gas or utlity company to verify BTU cont...

Страница 21: ...alve when finished flushing 4 Turn on the heater electrical disconnect switch DRAINING The heater must be drained if it is to be shut down and exposed to freezing temperatures Maintenance and service procedures may also require draining the heater 1 Turn off the heater electrical disconnect switch 2 Close the cold water inlet valve to heater 3 Open a nearby hot water faucet to vent the system 4 Op...

Страница 22: ...and a tank explosion In areas with poor water conditions it may be necessary to inspect the T P valve more often than every three years CAUTION BEFORE MANUALLY OPERATING THE VALVE MAKE SURE THAT A DRAIN LINE HAS BEEN ATTACHED TO THE VALVE TO DIRECT THE DISCHARGE TOAN OPEN DRAIN FAILURE TO TAKE THIS PRECAUTION COULD MEAN CONTACT WITH EXTREMELY HOT WATER PASSING OUT THE VALVE DURING THIS CHECKING OP...

Страница 23: ...OT WATER SUPPLIED TO FIXTURES PIPE TO OPEN DRAIN INSTALLINACCORDANCE WITH LOCAL CODES CAUTION IF BUILDING COLD WATER SUPPLY HAS A BACK FLOW PREVENTER CHECK VALVEORWATERMETERWITH CHECK VALVE PROVISIONS FOR THERMALEXPANSION OF WATER IN THE HOT WATER SYSTEM MUST BE PROVIDED NOTE CONNECT RETURN LINE FROM HOT WATER CIRCULATING LOOP IF USED TO COLD WATER INLET LINE PIPE TO OPEN DRAIN INSTALLINACCORDANCE...

Страница 24: ...DANGER TEMPERATURE SETTING SHOULD NOT EXCEED SAFE TEMPERATUREATFIXTURES SEEWATERTEMPERATURE CONTROL WARNING ON PAGE 4 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD AN ANTI SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES CAUTION IF BUILDING COLD WATER SUPPLY HAS A BACK FLOW PREVENTER CHECK VALVE OR WATER METERWITHCHECKVALVEPROVISIONSFORTHERMAL EXPANSION OF WATER ...

Страница 25: ...IT SPECIFICATIONS PAGE28 CAUTION IF BUILDING COLD WATER SUPPLY HAS A BACK FLOW PREVENTER CHECK VALVE OR WATER METER WITH CHECK VALVE PROVISIONS FOR THERMALEXPANSION OF WATER IN THE HOT WATER SYSTEM MUST BE PROVIDED DANGER TEMPERATURE SETTING SHOULD NOT EXCEED SAFE TEMPERATURE ATFIXTURES SEEWATERTEMPERATURECONTROLWARNINGONPAGE 4 IF HIGHER PREHEAT TEMPERATURESARE NECESSARY TO OBTAIN ADEQUATE BOOSTER...

Страница 26: ...ECTCIRCULATINGLINEOF180 F 82 C ORBOOSTEDWATER IF USED TO INLETWATER LINETO BOOSTER INSTALLINACCORDANCE WITH LOCALCODES TWO TEMPERATURE TWO HEATERS ONE PRE HEATER ONE BOOSTER HEATER WITH OR WITHOUT BUILDING RECIRCULATION DANGER TEMPERATURE SETTING SHOULD NOT EXCEED SAFE TEMPERATURE ATFIXTURES SEEWATERTEMPERATURECONTROLWARNINGONPAGE 4 IF HIGHER PREHEAT TEMPERATURESARE NECESSARY TO OBTAIN ADEQUATE BO...

Страница 27: ...TANK NOTE4 IFTEMPEREDWATERISRECIRCULATED RETURNLINESHOULD BE CONNECTEDATPOINTA DANGER TEMPERATURE SETTING SHOULD NOT EXCEED SAFE TEMPERATURE ATFIXTURES SEEWATERTEMPERATURECONTROLWARNINGONPAGE 5 IF HIGHER PREHEAT TEMPERATURESARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD ANANTI SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES CAUTION IF BUILDING COLD WATER SUPPLY HAS A BACK FLOW PREVENTER CHECK ...

Страница 28: ...ter heating and storage potential of the system cannot be achieved Plus the units with the higher water flow may have a shortened life Unions shown in piping diagrams are not included in the manifold kits Dimensions shown are for minimum space occupied by the water heaters assemblies Space for the venting system and unit servicing must be added ...

Страница 29: ...o see if the water heater drain valve is tightly closed Also check the cleanout opening for leakage 2 The apparent leakage may be condensation which forms on cool surfaces of the heater and piping 3 If the outlet of the relief valve is leaking it may represent Excessive water pressure Excessive water temperature Faulty relief valve Excessive water pressure is the most common cause of relief valve ...

Страница 30: ...a W C or lower than the minimal gas supply pressure as shown in Table 4 that is for Natural Gas 5 0 1 25 kPa W C for BTH 120 250 or 4 5 1 1 kPa W C for BTH 150 199 or for L P Gas 11 0 2 74 kPa W C pressure Also the manifold pressure should rise during the three 3 second trial for ignition to the manifold pressure value for the individual unit listed in Table 4 that is for Natural Gas 4 0 1 kPa W C...

Страница 31: ... to unless an effective method of controlling thermal expansion is also installed at the heater s and operational at all times The relief valve installed on the heater is not an acceptable method 4 SERVICEAND REPAIR EXPENSES Under the limited warranty the warrantor will provide only a replacement water heater or part thereof The owner is responsible for all other costs Such costs may include but a...

Страница 32: ...32 A O SMITH WATER PRODUCTS COMPANY 5621 W 115TH STREET ALSIP ILLINOIS 60803 PHONE 1 800 433 2545 FAX 1 800 433 2515 www hotwater com E MAIL parts hotwater com ...

Отзывы: