STANDARD TANK THERMOSTAT WIRING
3
8
Figure 1
6
REMOTE AIR
TEMPERATURE
SENSOR
FIELD SUPPLIED
STANDARD TANK
THERMOSTAT
NOTE:
TANK TEMPERATURE
SETTING MUST NOT
EXCEED 140°F (60°C)
(24 VAC COM)
(24 VAC HOT)
HPWH
TERMINAL
STRIP
AMBIENT AIR
LIMIT THERMOSTAT
AMBIENT AIR LIMIT THERMOSTAT
CONFIGURATION NOTES:
1) Configure stage 1 for cooling.
2) Configure stage 2 for heating.
3) Set cooling set point at 50°F
4) *Set heating set point 95°F
5) Set cooling differential to 10°F
6) Set heating differential to 5°F
7) Locate remote air temperature
sensor near return (entering) air
connection or inside return air
ducting near unit.
* When High Ambient Air Kit is installed
adjust heating set point to 120°F
RANCO DIGITAL THERMOSTAT
PART # ETC 212000-000
24V COM
NC NO C
NC C NO
OUTPUT 1
OUTPUT 2