<How to set the Freeze protection pump >
To set the Freeze protection pump mode in 520 Indoor or 520 Outdoor, please follow the procedures
below:
1.
Change the dipswitch No.4 of the right bank on the computer board to the “OFF” position (Individual
operation mode should be
OFF
position) .
2.
If the 9007603005 installed, turn off the 9007603005.
3. While in Stand by mode (cannot be in combustion, forced-combustion, or FM adjustment modes),
press and hold the “Increase” button for at least 5 seconds or longer to enter “Diagnostic Mode”.
4. Scroll through the needed information (mode# P1)by pressing the "Increase" or "Decrease" buttons
to scroll up or down on the “3-digit 7-Seg LED”.
5. While the “P1” is displayed, press the “Number display” button.
6. The “3-digit 7-seg LED” will display “on”.
7. When the “Increase” button is pressed for at least 3 seconds or 30 minutes have elapsed without
pressing any buttons, the display will return to normal.
520 Indoor / 520 Outdoor Computer board
Right bank of dipswitches