TABLE 3

BTUH Input

Minimum 

Square

Feet with

8’ Ceiling

Typical Room

with 8’ Ceiling

30,000

188

9 x 21

45,000

281

14 x 20

60,000

375

15 x 25

75,000

469

15 x 31

90,000

563

20 x 28

105,000

657

20 x 33

120,000

750

25 x 30

135,000

844

28 x 30

IMPORTANT:
• 

The area must be open and be able to provide the 

proper air requirements to the water heater. Areas that 

are being used for storage or contain large objects 

may not be suitable for water heater installation. 

• 

Water heaters installed in open spaces in buildings 

with unusually tight construction may still require out-

door air to function properly. In this situation, outside 

air openings should be sized the same as for a con-

fined space. 

• 

Modern home construction usually requires supplying 

outside air into the water heater area. 

Confined Space                                                    

 

For the correct and proper operation of this water heater, 

ample air must be supplied for the combustion, ventilation, 

and dilution of flue gases. Small enclosures and confined 

areas must have two permanent openings so that sufficient 

fresh air can be drawn from outside of the enclosure. One 

opening shall be within 12 inches of the top and one within 

12 inches of the bottom of the enclosure as shown in 

Figure 4.
The size of each opening (free area) is determined by the 

total BTUH input of all gas utilization equipment (i.e., water 

heaters, furnaces, clothes dryers, etc.) and the method by 

which the air is provided. The BTUH input can be found 

on the water heater rating plate. Additional air can be 

provided by two methods:

1.   All air from inside the building.
2.   All air from outdoors.

COMBUSTION AIR & VENTILATION

WARNING

Carbon Monoxide Warning

Water heater must be vented to outdoors.
Vent must be installed by a qualified technician using 
the installation instructions.
Examples of a qualified technican include: gas 
technicians, authorized gas company personel, and 
authorized service persons.
Failure to so do can result in death or carbon monoxide 
poisoning.

IMPORTANT:  Air for combustion and ventilation must not 

come from a corrosive atmosphere. Any failure due to 

corrosive elements in the atmosphere is excluded from 

warranty coverage.
The following types of installation (not limited to the 

following) will require outdoor air for combustion due to 

chemical exposure and may reduce but not eliminate the 

presence of corrosive chemicals in the air:
• beauty 

shops

• 

photo processing labs

• 

buildings with indoor pools 

• 

water heaters installed in laundry, hobby, or craft 

rooms

• 

water heaters installed near chemical storage areas

Combustion air must be free of acid-forming chemicals such 

as sulfur, fluorine, and chlorine. These elements are found 

in aerosol sprays, detergents, bleaches, cleaning solvents, 

air fresheners, paint, and varnish removers, refrigerants, 

and many other commercial and household products. When 

burned, vapors from these products form highly corrosive acid 

compounds. These products should not be stored or used 

near the water heater or air inlet.
Combustion and ventilation air requirements are determined 

by the location of the water heater. The water heater may 

be located in either an open (unconfined) area or in a 

confined area or small enclosure such as a closet or small 

room. Confined spaces are areas with less than 50 cubic 

feet for each 1,000 BTUH of the total input for all gas-using 

appliances.

Unconfined Space                                                   

A water heater in an unconfined space uses indoor air for 

combustion and requires at least 50 cubic feet for each 

1,000 BTUH of the total input for all gas appliances. The 

table below shows a few examples of the minimum square 

footage (area) required for various BTUH inputs.

Содержание 315456-002

Страница 1: ...pplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier WARNING If t...

Страница 2: ...lief Valve 16 17 T P Relief Valve and Pipe Installation 17 Combination Space Heating Potable Water System 17 18 Solar Installation 18 Electrical Connections and Wiring Diagram 18 Important Information...

Страница 3: ...ty equivalent to a licensed tradesman in the fields of plumbing air supply venting and gas supply including a thorough understanding of the requirements of the National Fuel Gas Code as it relates to...

Страница 4: ...oid all ignition sources if you smell Natural or LP gas Do not expose water heater control to excessive gas pressure Use only gas shown on rating plate Maintain required clearances to combustibles Kee...

Страница 5: ...CODES IMPORTANT WHEN BRUSHING ON AN APPROVED NONCORROSIVE LEAK DETECTION SOLUTION DO NOT SPLASH SOLUTION ONTO ELECTRICAL CON NECTIONS SEE PAGE 27 M N A L B P D E Q F G DISCHARGE PIPE DO NOT CAP OR PLU...

Страница 6: ...future users of this water heater will need it for future reference Service to the FVIR System should only be performed by a qualified technician Examples of a qualified technician include licensed pl...

Страница 7: ...ignition sources have been extinguished Fire or Explosion Hazard WARNING Read instruction manual before installing using or servicing water heater Improper use may result in fire or explosion Maintain...

Страница 8: ...ply wholesalers and retailers and detect and react to leakage in various ways Sensors mounted in the metal drain pan that trigger an alarm or turn off the incoming water to the water heater when water...

Страница 9: ...PPLY WARNING Use a new CSA approved gas supply line Install a shut off valve Do not connect a natural gas water heater to an L P gas supply Do not connect an L P gas water heater to a natural gas supp...

Страница 10: ...these instructions can result in death explosion or carbon monoxide poisoning Explosion Hazard Gas Pipe Capacity Table WARNING Explosion Hazard Gas leaks can not always be detected by smell Gas suppl...

Страница 11: ...y a qualified technician using the installation instructions Examples of a qualified technican include gas technicians authorized gas company personel and authorized service persons Failure to so do c...

Страница 12: ...for ventilation and combustion air supply openings consideration must be given to the blocking effect of protection louvers grilles and screens These devices can reduce airflow which in turn may requi...

Страница 13: ...or use on this water heater U L recognized fuel gas and carbon monoxide CO detectors are recommended in all applications and should be installed using the manufacturer s instructions and local codes r...

Страница 14: ...assageway is clear and free of obstructions The chimney must be cleaned if previously used for venting solid fuel appliances or fireplaces Also consult local and state codes for proper chimney sizing...

Страница 15: ...nder Closed System Thermal Expansion 5 Install a shut off valve in the cold water inlet line It should be located close to the water heater and be easily accessible Know the location of this valve and...

Страница 16: ...or other chemicals must not be used Chemicals that may contaminate the potable water supply must not be added to the piping system Closed System Thermal Expansion As water is heated it expands thermal...

Страница 17: ...ed into the T P valve discharge opening per the instructions manual 4 Locate the hot water outlet cold water inlet pipes to the water heater 5 Locate the slit running the length of a section of pipe i...

Страница 18: ...tions for leaks Open the nearest hot water faucet and let it run for three 3 minutes to purge the water lines of air and sediment and to ensure complete filling of the tank The Electrical power may th...

Страница 19: ...se review the following checklist and make any required installation upgrades or changes Questions Contact Residential Technical Assistance by referencing the phone number on the front of the Installa...

Страница 20: ...performed 3 Set the ON OFF switch on the gas control to the OFF postition 2 6 This appliance is equipped with a device which automatically lights the burner DO NOT TRY TO LIGHT THE BURNER BY HAND This...

Страница 21: ...operation when a call for heat is initiated The ignition control module will attempt to light the burner three times If the ignition control does not detect ignition it will enter lockout mode indica...

Страница 22: ...hermostat see Figures 20 and 21 Using the lowest hot water temperature that meets your needs will also provide the most energy efficient operation of the water heater Never allow small children to use...

Страница 23: ...the water heater cannot be used until the gas control valve thermostat is replaced by a qualified technician Contact your local dealer for service information losses and may satisfy your normal hot wa...

Страница 24: ...s To drain the tank perform the following steps 1 Turn off the gas to the water heater at the manual gas shut off valve and turn off the electrical power to the gas control thermostat valve 2 Open a n...

Страница 25: ...Manifold Burner Assembly 1 Turn off the gas supply to the water heater at the manual gas shut off valve This valve is typically located beside the water heater Note the position of the shut off valve...

Страница 26: ...dirt it may be necessary to check the air intake chamber screen more frequently 2 Use a vacuum cleaner with a hose attachment to remove any dust or debris that may have accumulated on the screen FIGU...

Страница 27: ...eater Refer to the section of Draining and Flushing section and follow the procedure 5 Disconnect the the flame sense hot surface igniter wire power supply transformer pressure switch fan and display...

Страница 28: ...ABOVE 170 F 1 Defective air flow restrictor 2 Not enough dilution air to mix with flue gases in inlet elbow 3 Dilution air too hot for mixing with flue gases 4 Wrong burner orifice 1 Take unit out of...

Страница 29: ...secondary air 2 Low gas pressure 3 Water heater flue or vent system blocked 4 Thermostat not functioning prop erly 5 Heater installed in a confined area 6 Burner flame yellow lazy 1 Provide ventilati...

Страница 30: ...are within requirements in the installation manual Manifold gas pressure is non adjustable if pressure is off by more than 0 3 W C 75 Pa replace the lower control 2 Low supply voltage should be 115 12...

Страница 31: ...oth terminals on pressure switch 4 Check pressure switch contacts with an ohmmeter for continuity A If pressure switch contacts show continuity closed circuit replace the pressure switch B If pressure...

Страница 32: ...ing The self diagnostic test has detected the temperature sensor thermistor inside the immersion probe is shorted 1 Turn power off for 10 to 20 seconds then on again to clear this error code 2 This pa...

Страница 33: ...DURING TRIAL FOR IGNITION IGNITOR TURNS OFF YES NO IS FLAME SENSE LOST IS REQUEST FOR HEAT SATISFIED GAS VALVE OFF COMBUSTION FAN OFF AFTER POST PURGE DELAY GAS VALVE CLOSES LESS THAN 3 TRIES FOR IGN...

Страница 34: ...w Retainer Clip 16 Manifold Door Gasket 17 Viewport Assembly 18 FV Sensor 19 Outer Door 20 Electrical Transformer 21 Pressure Switch REPAIR PARTS ILLUSTRATION LEGEND Special anode rod see Anode Rod Wa...

Страница 35: ...assembly which contains the manifold tube gasket manifold door manifold component block with retainer clip and flame sense hot surface igniter assembly Natural Gas Item 15 Contains manifold component...

Страница 36: ...36 NOTES...

Страница 37: ...37 NOTES...

Страница 38: ...38 NOTES...

Страница 39: ...niques for residential water heaters bearing a rating plate which has not been altered defaced or removed except as required by the warrantor used in an open system or in a closed system with a proper...

Страница 40: ...M DOES NOT CONSTITUTE PROOF OF PURCHASE OR PROOF OF INSTALLATION DISCLAIMERS NO EXPRESSED WARRANTY HAS BEEN OR WILL BE MADE ON BEHALF OF THE WARRANTOR WITH RESPECT TO THE MERCHANTABILITY OF THE HEATER...

Отзывы: