1. Brief introduction
KD-122LA Wireless Interconnected Fire Detecting Alarm is a portable, photoelectric smoke alarm with low
power consumption. Internal precise analog circuit, digital circuit and wireless transmission circuit make the
detection work more stable and reliable. It has wireless interconnection function, which means when one unit
makes alarm, other interconnected units within the interlink range will alarm at the same time. This product
has small volume and the built-in large-capacity battery can provide service life of 10 years.(If used under WiFi
system, it is around 5years)
2. Product characteristics
• Photoelectric smoke detection
• Reliable performance and less nuisance alarms
• Precise analog circuit and digital circuit
• Low power consumption
• Small size
• Portable
• Interlink range>100m (open field)
• Radio frequency:868.3MHz.
3. Technical specification
4. Appearance and dimensions (Figure. 1)
Tech
n
ic
al
p
ar
am
et
ers
Smoke detection
Voltage
DC3V (built-in CP605050)
Low-voltage
inspection
2.2V
Current
Alarm current
Quiescent current
≤
120mA
≤
2uA
Status display
Normal smoke
detection
LED (red) flashes once about every 344 seconds,
no alarm sound
Smoke detection or
key test
LED (red) flashes and continuous alarm is given
Low sensitivity
detection (silent
mode)
LED (red) flashes every 9 seconds, no alarm sound,
automatically cancel low sensitivity detection about
9 minutes later
Alarm memory
LED (green) flashes 3 times about every 43 seconds,
and stops 24 hours later. The first time you press test/
mute button after alarm is made, the detector will hint
by special alarm mode
End of life
After power-up and work for 10 years, end-of-life
warning will be made. The buzzer beeps 3 times every
43 seconds.
Low-voltage inspection
LED (red) flashes about every 344 seconds,
beeps about every 43 seconds.
Alarm
loudness
≥
85dB/3m
Wireless
interconnection
Radio frequency
868.3MHz
Interlink range
≥
100m (open field)
Interconnection /
learn indication
Red LED being steady on means the product needs to
learn. Red LED flashing means signal transmitting.
Green LED being steady on means the product is ready
to send identification code. Green LED flashing means
the unit has received wireless signal.
transmission rate
Working
temperature
-10°C~+40°C
Ambient
humidity
≤
95%RH (no condensation)