HR111 ~ 118  

DO1 ~  8 PWM duty cycle 

R/W 

0 (No) 

 

3.6 Predictive  maintenance  functions (changeover  &  time  on counters) 

Power  on cycles  and run hours may  reduce  life-time  of the  equipment  under  monitor. 

Now  it is possible to count them  using  Synapse  onboard counters  and totalizers: 

Address

 

Description

 

Data 

R/W 

Default

 

HR0 ~ 14 

DI 1 ~  8 changeover  counters 

DW 

R/W 

HR60 ~ 74 

DI 1 ~  8 time  on totalizers

 

DW 

R/W 

HR76 ~ 90 

DO 1 ~  8 changeover  ounters

 

DW 

R/W 

HR92 ~ 106 

DO 1 ~  8 time  on totalizers

 

DW 

R/W 

 
3.7  1-Wire  connection 

The  Synapse  provides  connection  for  up  to  32  digital  

temperature  sensors DS18B20 via 1-Wire bus with a maximum  length  200 m, as shown 
at  figure  below. 

Bus topology. Up to 200 meters. 

 
Auto  enumeration  for  1-Wire  sensors.

  Each  DS18B20 has  their  own  unique  serial  

number.  Using  a  special  search  algorithm,  the  Synapse  finds  and  saves  the 
enumeration  scheme  for the  sensors found in the static memory.  New  sensors still can 
be  added  to the  existing  enumeration  by: 

 

powering  on or resetting  the  module 

 

writing  non-zero value  into  HR33 register   

 

Address

 

Description

 

Data 

R/W 

Default

 

IR0 ~  IR31 

Temperatures  1 ~ 32 

-1000* 

HR33 

Total  sensors quantity  /  Init**

 

R/W 

*  -1000 is displayed if a sensor  is not present  or damaged 
**  writing  0 to HR33 clears  the  enumeration. 
 

4. Configuration  

The  factory  network  default  settings  for  the  Ethernet  interfaces  is  a  DHCP client.  So, 
after  power  on and plugging  it into your  router  network  it automatically  will  be added  
to your  network.  You  may  setup a  static  DHCP lease  for the  module,  or  use manual  IP 

network  setup.   

 
         4.1  Configuration  mode  for  IP  settings 

When  you  have  a  device  with  unknown  

address  and want  to make  quick IP  setup,  switch the  module  to  the  CONFIGURATOIN  
MODE.  Hold  the  reset  button  during  reboot  for  a  few  seconds  (status  LED  will  be 
blinking  frequently).  The  module  will  start  with 

192.168.4.1

 address.  In this mode  you 

can  change  setting  either  with 

Configuration

 

Web  server 

or  with

  Modbus  setting 

registers.   

To  switch back  to normal  mode,  reboot  the module. 

       4.2  Configuration  Web  server 

In  the  configuration  mode,  there  is  Configuration  

web-page  available  on the 

192.168.4.1

.  Instead  of Modbus register,  you  can use  this 

page  for module  setup.   The  page  can be  switched  off during setup. To enable  it again , 
use the  following  register: 
 

Address

 

Description

 

Data 

R/W 

Default

 

HR39 

Configuration  Web  server  enable 

R/W 

1 (yes) 

 

 
IP  configuration 

It can  be done  either  with  the  web  page  or  the  Modbus  registers: 

Address

 

Description

 

Data 

R/W 

Default

 

HR40 

Static  IP  enable 

R/W 

0(no) 

HR41 ~  HR44 

IP address  octets (x.x.x.x) 

R/W 

192.168.1.2 

HR45 ~ HR48 

Mask octets  (x.x.x.x) 

R/W 

255.255.255.0 

HR49 ~ HR52 

Gateway  IP address 
octets 

R/W 

192.168.1.1 

 

MQTT  configuration    

 

 
Visit level2.webhmi.com.u a  to learn   
about  IoT  applications  with  Synapse 

MQTT  capability.   

Use  ready  “New  device”  

tool  to  quickly  create  your  register  set  in 
Level2  /  WebHMI  projects. 

 
5. Diagnostics 

 

The  normal  LED  state  upon power  on is as follows: 

 

red  POWER  - always  on. 

 

green  SYSTEM 

  is blinking  once a  second (two  times  faster  in configuration  

mode) 

 

yellow  1WIRE 

  blinks when  the  sensors are  polled   

The  DI/DO  LEDs  reflects  the  actual  signal  states  on  terminals.  During  normal  boot 
process, DI/DO  ticks in  series.   

Use 

“ping”  command  to 

check  network  connection  and  Modbus/MQTT  testing  tools 

to test  the  protocol connection. 
In  case  of troubles  with  adding  temperature  sensors, the  most  probable  cause  is the 
length  of 1-Wire bus or its topology (signal or power  attenuation,  caused  too long line, 

interference  due  to  side  branches  etc.).  First  of all,  try  to  connect sensors  with  short 
wires.  If ok,  then check  wiring  (refer  to  general  Maxim  1-Wire  recommendations). 

Synapse  has  internal  watchdog,  which  may  reboot  the  device  in  case  of  accidental  
malfunction.  Refer  to the  following  diagnostic  registers  to  check if failures  might  have  
occurred. 
 In a  case  the  device  doesn't  working  properly,  please  contact to your  supplier. 

 
6.  For more information 

If  you  have  any  questions  or  problems  related  to  the  operation  of  the  7Bit™ 

products,  please  contact  to  the  unified  support  service  +38  (056)  796-96-90,

 

[email protected]

 

 

7. Warranty  

The  company  of “Distributed  Data  Systems  LLC”, the  manufacturer  of 7Bit Synapse  IO  

module  (hereinafter  referred  to as the Manufacturer),  expresses  its great  gratitude  for 
your  choice.  We  did our best  to ensure  that  this product  met  your  requirements,  and 
the  quality  corresponded  to  the best  standards.  The  manufacturer  sets the  life  of the 

Synapse  IO module  to 10 years  in case of its proper usage.  The  service  life  is calculated  
from  the  date  of  manufacture  of  the  requirements  for  warranty  obligations  and  for 
free  repair  (replacement  of  the  product)  in  the  case  of  failure  to  comply  with  the 
conditions set forth below.  All the  terms of the warranty  and  free  repair  (replacemen t )  
are  in  force under  the  law  on consumer  protection. 
The  manufacturer  sets  a  warranty  period,  counted  from  the  date  of  sale,  and  the 
period  of free  repair  (replacement),  subject  to compliance  with  the rules  of operation, 
12 months. Replacement  of defective  parts (assemblies,  assembly  units) in the product 
during  the warranty  period  does not lead  to  the 
establishment  of a  new  warranty  period  for  the entire  product, or  for replaced  parts. 

The  manufacturer  declines all  responsibility for the possible harm,  directly  or indirectly  
caused  by  the  Synapse  device  to people,  animals,  property  in  case  event  that  this is 
the  result  of  non-compliance  with  the  rules  and  conditions  of  use  of  the  product; 
Intentional  or reckless  actions  of the buyer 
(consumer)  or  third parties.  Also,  the  Manufacturer  declines  all  responsibility  for the 
possible  damage,  directly  or  indirectly  caused  by  the  Synapse  device  as  a  result  of 
alteration,  damage,  loss of data  and information 
 
Date  of the  manufacturer's  QA  _____________________________ 

 
 
Date  of sell  _____________________________________________ 
 
 
Sellers  marks  ___________________________________________ 
 
 
Buyer's  signature

 

________________________________________ 

 

 

Synapse Quick  guide fw ver.: 1.05  

07.21 

Address

 

Description

 

Data 

R/W 

Default

 

HR30 

Reboot  counter 

-1000* 

HR31, HR32 

Uptime,  sec. (low,  high)

 

 

HR34 

Free  memory

 

 

  

  

   

      