APPLICATION

The  75F®  Pressure  Sensor  Package

  is  designed  to  monitor  the 

differential pressure inside your building. Pressure in a building can be 
created in several ways. Buildings are generally designed to  exhaust 
as much air as is being taken in, but circumstances often arise that 

create a positive or negative pressure in a space. Typically, a building 
should  maintain  a  slightly  positive  pressure,  +0.01 

inches’

  water 

column. 75F solutions can regulate the pressure differential when the 

Pressure Sensor Package Solution is used in conjunction with a 75F® 
Outside Air Optimization

 Package. 

|

 

PRECAUTIONS

Failure to wire devices with the correct polarity when using a
shared  transformer  may  result  in  damage  to  any  device
powered by the shared transformer.

Do NOT mount the tubing so that the inside or outside tube

ends are in direct line of a breeze or draft.

Remove  power  before  wiring.  Never  connect  or  disconnect
wiring  with  the  power  applied.  Do  not  allow  live  wires  to
touch the circuit boards.

Fig. 1

INSTALLATION & OPERATION INSTRUCTIONS 

75F® Pressure Sensor Package™

 

Содержание A/DP2 Series

Страница 1: ...olumn 75F solutions can regulate the pressure differential when the Pressure Sensor Package Solution is used in conjunction with a 75F Outside Air Optimization Package PRECAUTIONS Failure to wire devi...

Страница 2: ...ackage pressure control is possible SPECIFICATIONS 75F Pressure Controller Supply Voltage 24VAC Input 0 10VDC Operating Environment 41 F 122 F Enclosure Rainproof type 3R non metallic enclosure A DP2...

Страница 3: ...on the label pointing upward If the unit must be installed flat there may be a zero shift The shift can be corrected with the zero adjustment located inside the enclosure To adjust the zero both press...

Страница 4: ...below Wiring the A DP2 Use 18 3AWG to run power from the 75F controller to the pressure sensor as shown in Fig 3 The power for the A DP2 is internally connected so that the controller will power the A...

Страница 5: ...e Smart Node should read default room 1 Press the Right button on the Smart Node until Advertising is displayed 2 2 With the CCU Tablet within 20 of the Smart Node press Pair Pressure Sensor from Setu...

Страница 6: ...w tab will appear titled Summary In the Summary tab look at the Pressure Sensor section and check that there are rational values being displayed for the differential pressure Typical differential pres...

Страница 7: ...ied foam is missing No pressure value If there is no differential pressure value displayed in the system summary first use your voltmeter to check that there is a DC signal of 5VDC being sent to the c...