Maintenance

 

5-1

 Maintenance of Flame-Proof version. 

 

1.When performing maintenance on Flame-proof version, never remove the terminal box 

cover or main cover while the power is connected. 

2.

 Always turn off the power before performing any maintenance or repair work. 

 

5-2

 Periodic Inspection

 

Performing  periodic  inspection  and  maintenance  of  the  I/P  Converter  will  help  reduce  the 

incidence of faults and extend the working life of the unit.

 

 

<Supply pressure filter> 

A  metal  mesh  is  fitted  inside  the  SUPPLY  coupling.  Use  a  pair  of  tweezers  or  similar  to 

remove any sealing tape or dirt particles caught in the mesh.

 

 

<Fixed orifice assembly>

 

The fixed orifice plays an important role in supplying the air to the nozzle. If no nozzle back 

pressure is present, this may indicate a blocked orifice. 

Take off the exhaust cover, then remove the fixed orifice assembly from the pilot relay unit 

and replace with a spare assembly. (See Figure 5-1) 

If you do not have a spare fixed orifice assembly, use [phi]0.3 piano wire or similar to clean 

the blocked orifice. Then use clean air to blow off any remaining dirt. 

When  finished  cleaning,  screw  the  assembly  back  into  its  original  position.  Take  care  to 

ensure that the O-ring is positioned correctly in the body of the pilot relay unit. 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 5-1 

 

5-1 

Содержание TE100

Страница 1: ...TE100 200 I P CONVERTER INSTRUCTION MANUAL 3S Co Ltd E IM TE100 00 R6...

Страница 2: ...after making the environment non hazardous Always turn off the power before removing the terminal box cover or main cover If intending to remove or disassemble the pressure gauge for maintenance or ot...

Страница 3: ...rsion 3 1 3 2 Installation 3 2 3 2 1 Pipe Mounting 3 2 3 2 2 Wall Mounting 3 2 3 3 Pneumatic and Electrical Installation 3 2 3 3 1 Pneumatic Installation 3 2 3 3 2 Electrical Installation 3 3 1 Flame...

Страница 4: ...utions Store the I P converter in a location that satisfies the following criteria Not subject to rain or moisture Not subject to shock or other impact Normal room temperature and humidity 1 4 Install...

Страница 5: ...es them easy to use High accuracy The I P Converters use a high accuracy sensor and the latest technology to achieve a high level of conversion accuracy Built in reducing valve A model is available th...

Страница 6: ...ver the nozzle 3 and raise the pressure in the pilot relay pneumatic valve nozzle back pressure chamber 4 The increased nozzle back pressure causes a displacement in the diaphragm assembly 5 in the pi...

Страница 7: ...kg 1 8kg with a Mini set integrated approx 1 3kg 1 5kg with a Mini set integrated Material Primary Aluminum Die casting 2 4 Model Codes 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 Basic code Series Housing Pneum...

Страница 8: ...2 5 Dimensions 2 4...

Страница 9: ...2 6 Name of Each Part TE100 TE200 2 5...

Страница 10: ...lame proof Do not use the I P Converter in hazardous environments containing gases other than those applicable to the explosion proofing grade of the transducer Use the I P Converter with the ambient...

Страница 11: ...ing using the appropriate procedure depending upon whether a reducing valve Mini Set XR100 is fitted or not If a reducing valve is not fitted connect to the SUPPLY inlet on the I P Converter If a redu...

Страница 12: ...e Flame proof version Ex d IIB T6 Cable pipe with threaded pressure coupling method Use a G1 2 thick steel cable pipe PF1 2 equivalent with a lock nut to provide a full threaded coupling Alternatively...

Страница 13: ...Locking After partially attaching the terminal box cover lock the cover in place using the locking screw Other details All other aspects of the installation should be carried out in compliance with th...

Страница 14: ...h terminal box To connect the cables remove the terminal box cover and use the insulated crimping terminals on the terminal block Connect by crimping the input terminal to the terminal red and the inp...

Страница 15: ...late so that the M becomes visible Partially retighten the screw in this position 2 Next use a screwdriver to rotate the AM switch shaft as far as it will go in the direction of the arrow on the plate...

Страница 16: ...0 output 20kPa 0 2kgf cm2 Rotating clockwise increases the output and rotating counter clockwise reduces the output See Figure 4 2 b Next apply a 100 20mA input signal Rotate the span adjustment trimm...

Страница 17: ...dure as for the standard range version Range 0 100 4 12mA 4mA 12mA 12 20mA 12mA 20mA 4 3 Width of Range Adjustment The table below shows the width of the zero and span adjustment bands You can set the...

Страница 18: ...similar to remove any sealing tape or dirt particles caught in the mesh Fixed orifice assembly The fixed orifice plays an important role in supplying the air to the nozzle If no nozzle back pressure i...

Страница 19: ...exhaust cover from the bottom of the I P Converter and undo the two screws See Figure 5 2 Figure 5 2 5 4 Replacement Parts Name Part No Quantity Circuit board TE100 TE100 500 11A 1 TE200 TE100 500 11B...

Страница 20: ...ty of input signal wiring is reversed Check wiring and connections No air supply Supply 140kPa 1 4kgf cm 2 Pilot relay is faulty Inspect and or replace pilot relay Output is unstable Large fluctuation...