5.
Maintenance
5-1
Maintenance of Flame-Proof version.
1.When performing maintenance on Flame-proof version, never remove the terminal box
cover or main cover while the power is connected.
2.
Always turn off the power before performing any maintenance or repair work.
5-2
Periodic Inspection
Performing periodic inspection and maintenance of the I/P Converter will help reduce the
incidence of faults and extend the working life of the unit.
<Supply pressure filter>
・
A metal mesh is fitted inside the SUPPLY coupling. Use a pair of tweezers or similar to
remove any sealing tape or dirt particles caught in the mesh.
<Fixed orifice assembly>
・
The fixed orifice plays an important role in supplying the air to the nozzle. If no nozzle back
pressure is present, this may indicate a blocked orifice.
・
Take off the exhaust cover, then remove the fixed orifice assembly from the pilot relay unit
and replace with a spare assembly. (See Figure 5-1)
・
If you do not have a spare fixed orifice assembly, use [phi]0.3 piano wire or similar to clean
the blocked orifice. Then use clean air to blow off any remaining dirt.
・
When finished cleaning, screw the assembly back into its original position. Take care to
ensure that the O-ring is positioned correctly in the body of the pilot relay unit.
Figure 5-1
5-1