supply specification to avoid over-voltage damaging the
device.
The device surface temperature is high after running;
please don't directly contact to avoid scalding.
【
DIN-Rail Mounting
】
The product adopts 35mm standard DIN-Rail mounting which
is suitable for most industrial scenes, mounting steps as
follows:
Step 1
Check if the DIN-Rail mounting kit is installed firmly.
Step 2
Insert the bottom of DIN-Rail mounting kit (one side
with spring support) into DIN-Rail, and then insert
the top into DIN-Rail.
Tips:
Insert a little to the bottom, lift upward and then insert
to the top.
Step 3
Check and confirm the products is firmly installed
on DIN-Rail, then mounting ends.
【
Disassembling DIN-Rail
】
Step 1
Device power off.
Step 2
After lift the device upward slightly, first shift out the
top of DIN-Rail mounting kit, and then shift out the
bottom of DIN-Rail, disassembling ends.
Note before powering on:
Power ON operation: First insert the power supply
terminal block into the device power supply interface,
and then plug the power supply plug contact and power
on.
Power OFF operation: First, remove the power plug,
and then remove the wiring section of terminal block.
Please pay attention to the above operation sequence.
【
Power Supply Connection
】
DC power supply
Model I and Model III provide 3-pin 7.62mm
pitch terminal block for 1 DC power input.
This power supply supports anti-reverse
connection Power supply range: 9
~
48VDC. The pin definitions of power supply are shown as
follows:
Pin No.
1
2
3
Definition
V+
FG
V-
AC power supply
Model II and Model IV provide 3 7.62mm
pitch terminal block for 1 power input.
Power supply range: 100~240VAC/DC.
The pin definitions of power supply are
shown as follows:
Pin No.
1
2
3
Definition
N/-
GND
L/+
【
DIP Switch Settings
】
Provide 4-bits DIP switch for function setting,
where "ON" is enable valid terminal. DIP switches
definition as follows:
DIP Definition
Operation
1
Jumbo frame Set the DIP to ON to enable jumbo
frame function
2
Broadcast
storm
suppression
Set the DIP to ON to enable
broadcast storm suppression
function
3
LFP
Set the DIP to ON to enable LFP
function, when one end of the
DIP Definition
Operation
copper port or fiber port
disconnects, close another port;
when the port is reconnected, open
another port.
4
Flow control
Set the DIP to ON to enable flow
control function
【
Checking LED Indicator
】
The device provides LED indicators to monitor the device
working
status
with
a
comprehensive
simplified
troubleshooting; the function of each LED is described in the
table as below:
LED
Indicate Description
PWR
ON
PWR is connected normally
OFF
PWR is disconnected or running
abnormally
Link/Act
(1-2)
ON
Ethernet port is connected
Blinking
The Ethernet interface is in a
network activity state.
OFF
Ethernet port is is connected
abnormally or disconnected
【
Specification
】
Panel
100M Copper Port
10/100Base-T(X),
RJ45,
Automatic Flow Control, Full/half
Duplex
Mode,
MDI/MDI-X
Autotunning
100M fiber port
100Base-FX, optional SC/ST/FC
100M SFP
100Base-FX SFP slot
Indicator
Power supply indicator, interface
indicator
Switch Property
Backplane bandwidth
1G
MAC Address Table
2K
Power supply