INSTALLATION AND OPERATION INSTRUCTIONS

The following instructions are intended to serve as a guideline for the use of the 3M™ Macurco™ Carbon Monoxide Detector 

CM-16A. It is not to be considered all-inclusive, nor is it intended to replace the policy and procedures for each facility. 

This detector helps monitor for the presence and concentration level of carbon monoxide gases. Misuse may produce 

an inaccurate reading, which means that higher levels of the gas being monitored may be present and could result in 

overexposure and 

cause sickness or death.

 For proper use, see supervisor,

 User Instructions

, or call 3M in U.S.A.,  

1-800-243-4630. In Canada, call Technical Service at 1-800-267-4414.

LOCATION

There are two usual sources of CO in homes -- defective heat sources (furnaces or wood burning stoves) and automobiles 

running in adjoining garages. The CM-16A can detect CO from these sources, as well as any other sources of CO. 
For best operation, mount a CM-16A in the hallway near each bedroom area. In addition, another CM-16A may be mounted just 

inside the door from the adjoining garage. Consider placing another detector in a bedroom that is adjacent to a furnace room.

Use For

The CM-16A is a low voltage (12-24V AC or DC) detector of Carbon Monoxide (CO). The CM-16A is designed for connection to 
Fire Alarm/Burglary Control Panels or as a stand alone unit. This carbon monoxide detector is designed to detect CO gas from 
ANY source of combustion. It is NOT designed to detect smoke, fire or any other gas.

Use only for monitoring the gas which the sensor and detector are designed to monitor. Failure to do so may result in 
exposures to gases not detectable and 

cause sickness or death. 

For proper use, see supervisor, 

User Instructions

, or call 

3M in U.S.A., 1-800-243-4630. In Canada, call Technical Service at 1-800-267-4414.

Do Not Use For

The CM-16A is NOT intended for use in industrial applications such as refineries, chemical plants, etc. The CM-16A is NOT 
intended for use in parking garages as the controller of exhaust systems. Do NOT use the CM-16A for monitoring for gases 
other than Carbon Monoxide (CO). The CM-16A is NOT designed to detect smoke, fire or any other gas. Do NOT mount the unit 
in the garage. Do NOT mount the CM-16A where the normal ambient temperature is below 40°F (4.4°C) or exceeds 100°F 
(37.8°C), or within 5 feet (1.5 meters) of a cooking or heating appliance. The Alarm Control Panel must be dedicated to CO 
detection or have alarm devices that provide a distinctive alarm for carbon monoxide detection. Do not connect the CM-16A to 
Fire Alarm Circuits.

CM-16A may not function effectively below 40°F (4.4°C) or above 100°F (37.8°C). Using the detector outside of this 
temperature range may adversely affect product performance and 

result in sickness or death.

General Description 

The CM-16A is for use with Fire Alarm/Burglary Control Panels that have 12 to 24V AC or DC power and alarm initiating 

circuits. The CM-16A is intended for installation in buildings in non-hazardous locations such as residences, retail stores, office 

buildings, and institutional buildings.

W

 WARNING

Features

• 

Surface mounts to a wall using the supplied enclosure 

rear housing.

• 

Flush mounts in a 4 x 4 or 2-gang, handy electrical box.

• 

Low profile, attractive unit in a white plastic case.

• 

Inexpensive, easy to install. Microcomputer control 

allows mostly automatic operation.

• 

Test & Reset switch conducts internal tests and actuates 

alarm relay.

• 

Visual display: GREEN - Normal operation.

• 

FLASHING AMBER - Trouble Contact your installer or 3M 

Macurco Tech Support

• 

RED - Danger! Move to fresh air (hazardous condition is 

present).

• 

Long Life solid state sensor

• 

N.O. and N.C. SPDT Alarm Relay and N.C. SPST Trouble 

relay to connect to Alarm Control Panels

SPECIFICATIONS

•  SPDT Alarm Relay SPDT Alarm Relay

•  SPST Trouble Relay SPST Trouble Relay

•  Visual Status Indicator

•  Loud Buzzer

•  Voltage 12-24 VDC or VAC Input (50-60 Hz)

•  Current (standby) 67 mA @ 12V, 47 mA @ 24V

•  Current (alarm) 115 mA @ 12V, 81 mA @ 24V

•  Size 4-1/2" x 5" x 1-5/8"

•  Alarm Relay 1 Amp, 125V, 30VA

•  Trouble Relay 0.5 Amp, 200V, 10VA

•  Buzzer Rating 85 dBA at 10 Feet

•  Shipping Weight (each) One pound

•  Color: White

•  Operating Temperature Range 32ºF to 120ºF

•  Alarm Setting: 70 ppm of CO after 60 to 240 minutes, 

150 ppm of CO after 10 to 50 minutes, and 400 ppm 

of CO after 4 to 15 minutes, in accordance with the 

provisions of UL Standard 2034.

•  This product is not UL listed.

W

 WARNING

W

 WARNING

Содержание Macurco CM-16A

Страница 1: ...ser Instructions may adversely affect product performance and result in sickness or death For proper use see User Instructions or call 3M in U S A 1 800 243 4630 In Canada call Technical Service at 1 800 267 4414 Important Keep these User Instructions for reference FOR MORE INFORMATION In United States contact Website www 3M com OccSafety Technical Assistance 1 800 243 4630 For other 3M products 1...

Страница 2: ...ot Use For 4 General Description 4 Features 5 Specifications 5 INSTALLATION AND OPERATION INSTRUCTIONS 5 Location 5 Installation 6 Power Up 8 Operation 8 Alarms 8 Reset Silence Switch 9 Trouble Indicator 10 Errors 10 MAINTENANCE 10 Testing 10 Cleaning 11 Sensor Poisons 11 3M GAS DETECTION PRODUCTS WARRANTY 11 TABLE OF CONTENTS ...

Страница 3: ...l Safety and Health Administration OSHA commercial or industrial standards To help avoid false alarms the CM 16A is not intended for low level detection below 30 ppm of carbon monoxide per UL 2034 Individuals with certain medical problems may consider using warning devices that provide audible and visual signals for carbon monoxide concentrations below 30 ppm The following symptoms are related to ...

Страница 4: ...Monoxide CO The CM 16A is NOT designed to detect smoke fire or any other gas Do NOT mount the unit in the garage Do NOT mount the CM 16A where the normal ambient temperature is below 40 F 4 4 C or exceeds 100 F 37 8 C or within 5 feet 1 5 meters of a cooking or heating appliance The Alarm Control Panel must be dedicated to CO detection or have alarm devices that provide a distinctive alarm for car...

Страница 5: ...two screws inside the CM 16A s mount on a two gang old work box or a 4 X 4 electrical box provided by the installer 2 The detector may be installed on either a ceiling or a wall If installed on a peaked gabled or sloped ceiling it should be located about 3 feet from the highest point The unit can be placed vertically or horizontally on a wall so the information on the front of the CM 16A can be re...

Страница 6: ...are aware they are not well they become so disoriented they are unable to save themselves by either exiting the building or calling for assistance Young children and household pets may be the first affected Transient CO situations can occur 1 Excessive spillage or reverse venting of fuel burning appliances caused by outdoor ambient conditions such as a Wind direction and or velocity including high...

Страница 7: ... CM 16A status indicator light is illuminated GREEN continuously If not do not proceed with the tests Though there is no field calibration procedure for this unit there is an optional field test procedure CLEANING The CM 16A should be cleaned using the soft brush attachment of your vacuum cleaner The CM 16A should be tested after cleaning to ensure the unit is operating normally SENSOR POISONS The...

Отзывы: