Cold Shrink QT-lll Silicone Rubber Three Core Inverted Skirted Termination
with High-K Stress Relief
3.16 Install cold shrink jacket extension assembly. Align the jacket seal tube (not the plastic support core) to
overlap ground wire seal area by approximately 1/4" (6 mm). To install, pull loose core end, while unwinding
counterclockwise around the cable. (Figure 12).
3.17 Bind cable ground wire and ground braid tail to cable jacket using Scotch
®
Vinyl Electrical Tape Super 88
(wide vinyl tape) (Figure 12). Apply at least eight tape layers and wrap only to width of tape roll.
1/4" (6 mm)
Pull Tab
Scotch
®
Vinyl Electrical Tape Super 88
(Wide Vinyl Tape)
Figure 12