13
How to Configure Loop Test?
Loop Test
is generally done to verify the working status of the alarm panel connection. Here, a relay
output is selected, frequency (number of occurrences of a repeating event per unit time) of the loop test
and a predefined alarm panel connection test event code is set, and configuration is written to the
module, followed by module reboot.
In Pégasus Nx debugger, a 16 digit message composition as per the contact id protocol is shown along
with the predefined alarm panel test event code. Match and verify the alarm panel test event code with
the event code received in the message composition. This event will not be transmitted to the
monitoring station as it is a test event used to check the alarm panel connection.
In case the device fails to receive any test event from the alarm panel, it will try the alarm panel loop test
two more times, if again failed to receive any test event, then an occurrence related to the alarm panel
connection failure is sent to the Zeus Server.
To configure “loop test”
1.
In the
Output
drop-down box, select a relay output for the loop test. Four relay outputs are available.
2.
In the
Frequency
text
box, enter the number of occurrences of the loop test
in seconds. The minimum acceptable
duration is 300 seconds and the maximum acceptable duration is 86400 seconds. The default duration is 0.
3.
In the
Event
text box, enter the predefined test event codes per the contact id protocol.
Содержание Pegasus NX
Страница 14: ...6 A message box is displayed saying Do you want to reboot the module 2 Click the Yes button ...
Страница 19: ...6 A message box is displayed saying Do you want to reboot the module 2 Click the Yes button ...
Страница 32: ...19 A message box is displayed saying Do you want to reboot the module 2 Click the Yes button ...
Страница 39: ...26 A message box is displayed saying Do you want to reboot the module 2 Click the Yes button ...
Страница 62: ...49 2 Enable the required Buzzer Activation Trigger s ...
Страница 84: ...71 Manage Debugger How to Connect Disconnect Debugger To connect debugger 1 Select your preferred language ...
Страница 85: ...72 2 Select the communication port to which device is connected 3 Click the Connect icon ...
Страница 86: ...73 Pégasus Nx debugger is connected and debug messages are displayed in the screen ...
Страница 87: ...74 To disconnect the debugger 1 Click the Disconnect icon ...
Страница 90: ...77 2 The Configuration Commands via SMS screen is displayed ...