- Electrical parameters are stated on the model identification plate located on the heater unit shell.
•
- Heater unit must be connected by TN-S system, which means that the neutral wire must always be connected.
•
- Main switch disconnecting all mains poles must always be included in the mains supply.
•
- Electrical shielding of the heater unit is IP54.
•
El. power supply phases to the heater unit must be connected through a protective power circuit breaker
of corresponding current and type. Distances between disconnected contacts must be higher than 3 mm.
•
The heater unit must be connected so that it is possible to disconnect it from the el. power supply by single
component.
•
Minimum dimensioning of supply cables:
L
L
N
N
1~230V
PE
6. INSTALLATION
L
L
N
N
1~230V
PE
PE
L
L
N
N
1~230V
PE
Type
Cable
[conductor x mm
2
]
SAV-2
3 x 1,5
SAV-4
3 x 1,5
SAV-6
3 x 1,5