EXTERNAL ACCESSORIES

SUPERIOR MASTER

1

Room sensor (accessories)

2

LPHW out sensor (included in delivery)

3

Outside air sensor (included in delivery)

4

Signal to SLAVE unit

5

Control panel

6

Antifreeze thermostat (NC)

7

RUN contact (relay contact, NO/NC)

8

ERROR contact (relay contact, NO/NC)

9

Water pump (relay contact)

10

DOOR contact (input, NO/NC)

11

Room thermosat (input, NO/NC)

12

External control 

(input, NO/NC)

13

Water valve control (0-10V)

1

2

3

EN

RU

PL

IT

CS

1

SMU - power supply

Смесительный узел – источник питания

Układ mieszający  zasilanie

Punto di miscelazione - alimentazione

SMU - napájení

2

Control signal (adjustable: SMU, heater/

cooler)

Управляющий сигнал (регулируемый: SMU, 

обогреватель/кулер)

Sygnał sterujący ( do nastawienia  : SMU,heater/

cooler)

Segnale di controllo (impostabile: SMU, heater/

cooler)

Řídící signál (nastavitelné: SMU, heater/

cooler)

3

Spatial sensor

Внутренний датчик

Czujnik przestrzenny

Sensore ambientale

Prostorové čidlo teploty

4

Flap - inlet (fresh air)

Клапан свежего воздуха

Klapa świeżego powietrza

Aletta – Aria fresca

Klapka pro čerstvý vzduch

5

Flap - outlet

Клапан отработанного воздуха

Klapa wydechu

Aletta - Scarico

Klapka pro odvodní vzduch

6

Water pump

Водяной насос (конденсат)

Pompa wodna

Pompa dell‘acqua

Vodní čerpadlo

7

RUN function (adjustable in units with direct 

evaporator: 0-10V/ON-OFF)

Функция RUN (у модулей с прямым 

выпаривателем можно настроить: 0-10V/ON-OFF)

Funkcja RUN (u jednostek z parownikiem bez-

pośrednim  do nastawienia : 0-10V/ON-OFF)

Funzione RUN (impostabile per le unità dotate 

dell’evaporatore diretto: 0-10V/ON-OFF)

Funkce RUN (nastavitelné s jednotkou s 

přímím výparníkem 0-10V / ON/OFF)

8

C/O - cooling/heating 

C/O - охлаждение/ обогрев

C/O - chłodzenie / ogrzewanie

C/O – raffreddamento/riscaldamento

C/O - chlazení/topení

9

Direct evaporator - ERROR

Прямой выпариватель - ERROR

Prosty parownik – ERROR (błąd)

Evaporatore diretto – ERROR

Přímý výparník - ERROR

10

Direct evaporator - defrost

Прямой выпариватель - РАЗМОРОЗКА

Prosty parownik - odmrażanie

Evaporatore diretto - SCONGELAMENTO

Přímý výparník - ODMRAŽOVÁNÍ

11

External control -ON/OFF

Внешнее управление

Sterowanie zewnętrzne  Wł./Wył.

Accensione/spegnimento esterno

Externí ovládání ON/OFF

12

Alarm - FIRE

Пожарный извещатель

Wejście stycznika pożarowego

Fiamma

Poplach - FIRE

13

BOOST regime

Функция Boost

Funkcja BOOST

Boost

Režim BOOST

14

Recuperator - ERROR

Ошибка рекуператора

Usterka rekuperatora

Errore – recuperatore

Chyba rekuperátoru

15

The air quality sensor - power supply

CO2/RH/VOC - источник питания

CO2/RH/VOC - zasilanie

CO2/RH/VOC - alimentazione

Čidlo kvality vzduchu - napájení

16

The air quality sensor - control signal

CO2/RH/VOC - данные

CO2/RH/VOC - data

CO2/RH/VOC - dati

Čidlo kvality vzduchu - ovládání

17

Presence sensor

Датчик движения

Czujnik ruchu

Sensore di presenza

Čidlo přítomnosti

N - Neutral

Entrée

24VAC

24V

GND

GND

GND

CAPTEUR 

PRÉSENCE

DX GENERAL ERROR

(settable)

DX DEFROST 

(settable)

230VAC

GND

2

1

V+

0-10 VDC

CO

2

 /RH/VOC/EXT

CO

2

 / RH/VOC

EXTERNAL

CAPTEUR 0-10V

15VAC

Capteur CO /HR

VDC

0-10

24VAC

Alimentation 

vanne

0-10V 

Vanne/ Groupe Exterieur DX

Capteur Externe.

Câble deux fils blindé

alimentation générale

Registre 

max.1A 

max. 50 m 

Air Neuf

79 80

70 69

68 67

66 65

81 82 55 56

Registre 

Air Rejeté

77 78

23 24

230VAC

POMPE

DE CIRCULATION

76 75

25 26

49 50

59 60

OUTPUT

     DX = ON/OFF 

(Sortie pour unité 

exterieure)

72 71

CONTACT 

ERREUR

Commande 

á distance

63 64

CONTACT 

EXTERNE

ON/OFF

53 54

51 52

CONTACT

INCENDIE

CMSI

62 61

BOOST

BOOST

57 58

boitier de commande

J1/J2

GND GND

15

13 14

9
8
7

10

5
4
3
2

1

6

12

11

16 17 18 19 20 21 22 23 24

82

83

81 80 79 78 77 76 75 74 73

25 26 27 28 29

68 67 66 65 64 63 62 61 60 59 58 57 56 55 54 53 52 51

31

33

35 36 37 38 39 40 41 42 43

9

44 45 46 47 48 49 50

30

32

34

72 71

70 69

GND

N

L

LO

L

LO

L

LO

N

GND

GND

0-10V

+SSR -SSR

GND

0-10V

VENT-INT

230VAC

PIR

230VAC

FLAP-INT

230VAC

FLAP-EXT

230VAC

W. PUMP

ALARM

HEATER

RUN

OUTPUT

COOL/HEAT

HEAT PUMP

HEAT PUMP

ERROR DEFROST EXTERNAL

ON/OFF

FIRE

BOOST

PRESENCE

SENSOR

PIR

REC ERR

TRANSF- 24VAC

TRANSF- 15VAC

TRANSF- 12VAC

L-VENT INT-EXT

L
N

N

L-TR

N-TR

~

VENT-EXT

HEATER/

COOL/PUMP

PREHEATER

0-10V GND

POSTHEATER

REC/BYP

GND

PWM

GND

PWM

RPM

(TC)

RPM

24VAC

24VAC

T-EXT-1 T-EXT-2 T-EXT-3 T-INT-1

T-INT-2

FILTER

INT

T-WATER T-WATER T-ROOM

JP1

LED1

DATA

SWO

TX

RX

-OUT

-IN

(TC)

1

~

2

~

1

~

2

15VAC

IN  GND

CO2/RH/EXT

2

1

1

2

10

ModBUS RTU via 

Rs485

GTC

ou

FUSE

(VENT-EXT)

FUSE

(VENT-INT)

FUSE

(PCB)

FUSE

(PERIPHERY)

!

!

defrost

24VAC

POWER SUPPLY

 MIX POINT

MIX. POINT / OUTDOOR 

UNIT DX

INPUT

MAIN ELECTRIC SUPPLY

EXT. SENSOR

(two-wire shielded cable)

or

INLET -Fresh air

OUTLET

 DX = ON/OFF 

(Output for outdoor unit)

Control panel

EXTERNAL 

CONTROL

FIRE

WATER

PUMP CONTROL

ERROR

CONTACT

PRESENCE

SENSOR

SENSOR

SENSOR

1

5

6

11

17

15

16

2

3

4

7

12

13

14

8

9

10

E-SCH-RGJ-HR85

3-050-D06378    

              

EN

RU

PL

IT

CS

1

SMU - power supply

Смесительный узел – источник питания

Układ mieszający  zasilanie

Punto di miscelazione - alimentazione

SMU - napájení

2

Control signal (adjustable: SMU, heater/

cooler)

Управляющий сигнал (регулируемый: SMU, 

обогреватель/кулер)

Sygnał sterujący ( do nastawienia  : SMU,heater/

cooler)

Segnale di controllo (impostabile: SMU, heater/

cooler)

Řídící signál (nastavitelné: SMU, heater/

cooler)

3

Spatial sensor

Внутренний датчик

Czujnik przestrzenny

Sensore ambientale

Prostorové čidlo teploty

4

Flap - inlet (fresh air)

Клапан свежего воздуха

Klapa świeżego powietrza

Aletta – Aria fresca

Klapka pro čerstvý vzduch

5

Flap - outlet

Клапан отработанного воздуха

Klapa wydechu

Aletta - Scarico

Klapka pro odvodní vzduch

6

Water pump

Водяной насос (конденсат)

Pompa wodna

Pompa dell‘acqua

Vodní čerpadlo

7

RUN function (adjustable in units with direct 

evaporator: 0-10V/ON-OFF)

Функция RUN (у модулей с прямым 

выпаривателем можно настроить: 0-10V/ON-OFF)

Funkcja RUN (u jednostek z parownikiem bez-

pośrednim  do nastawienia : 0-10V/ON-OFF)

Funzione RUN (impostabile per le unità dotate 

dell’evaporatore diretto: 0-10V/ON-OFF)

Funkce RUN (nastavitelné s jednotkou s 

přímím výparníkem 0-10V / ON/OFF)

8

C/O - cooling/heating 

C/O - охлаждение/ обогрев

C/O - chłodzenie / ogrzewanie

C/O – raffreddamento/riscaldamento

C/O - chlazení/topení

9

Direct evaporator - ERROR

Прямой выпариватель - ERROR

Prosty parownik – ERROR (błąd)

Evaporatore diretto – ERROR

Přímý výparník - ERROR

10

Direct evaporator - defrost

Прямой выпариватель - РАЗМОРОЗКА

Prosty parownik - odmrażanie

Evaporatore diretto - SCONGELAMENTO

Přímý výparník - ODMRAŽOVÁNÍ

11

External control -ON/OFF

Внешнее управление

Sterowanie zewnętrzne  Wł./Wył.

Accensione/spegnimento esterno

Externí ovládání ON/OFF

12

Alarm - FIRE

Пожарный извещатель

Wejście stycznika pożarowego

Fiamma

Poplach - FIRE

13

BOOST regime

Функция Boost

Funkcja BOOST

Boost

Režim BOOST

14

Recuperator - ERROR

Ошибка рекуператора

Usterka rekuperatora

Errore – recuperatore

Chyba rekuperátoru

15

The air quality sensor - power supply

CO2/RH/VOC - источник питания

CO2/RH/VOC - zasilanie

CO2/RH/VOC - alimentazione

Čidlo kvality vzduchu - napájení

16

The air quality sensor - control signal

CO2/RH/VOC - данные

CO2/RH/VOC - data

CO2/RH/VOC - dati

Čidlo kvality vzduchu - ovládání

17

Presence sensor

Датчик движения

Czujnik ruchu

Sensore di presenza

Čidlo přítomnosti

N - Neutral

Entrée

24VAC

24V

GND

GND

GND

CAPTEUR 

PRÉSENCE

DX GENERAL ERROR

(settable)

DX DEFROST 

(settable)

230VAC

GND

2

1

V+

0-10 VDC

CO

2

 /RH/VOC/EXT

CO

2

 / RH/VOC

EXTERNAL

CAPTEUR 0-10V

15VAC

Capteur CO /HR

VDC

0-10

24VAC

Alimentation 

vanne

0-10V 

Vanne/ Groupe Exterieur DX

Capteur Externe.

Câble deux fils blindé

alimentation générale

Registre 

max.1A 

max. 50 m 

Air Neuf

79 80

70 69

68 67

66 65

81 82 55 56

Registre 

Air Rejeté

77 78

23 24

230VAC

POMPE

DE CIRCULATION

76 75

25 26

49 50

59 60

OUTPUT

     DX = ON/OFF 

(Sortie pour unité 

exterieure)

72 71

CONTACT 

ERREUR

Commande 

á distance

63 64

CONTACT 

EXTERNE

ON/OFF

53 54

51 52

CONTACT

INCENDIE

CMSI

62 61

BOOST

BOOST

57 58

boitier de commande

J1/J2

GND GND

15

13 14

9
8
7

10

5
4
3
2

1

6

12

11

16 17 18 19 20 21 22 23 24

82

83

81 80 79 78 77 76 75 74 73

25 26 27 28 29

68 67 66 65 64 63 62 61 60 59 58 57 56 55 54 53 52 51

31

33

35 36 37 38 39 40 41 42 43

9

44 45 46 47 48 49 50

30

32

34

72 71

70 69

GND

N

L

LO

L

LO

L

LO

N

GND

GND

0-10V

+SSR -SSR

GND

0-10V

VENT-INT

230VAC

PIR

230VAC

FLAP-INT

230VAC

FLAP-EXT

230VAC

W. PUMP

ALARM

HEATER

RUN

OUTPUT

COOL/HEAT

HEAT PUMP

HEAT PUMP

ERROR DEFROST EXTERNAL

ON/OFF

FIRE

BOOST

PRESENCE

SENSOR

PIR

REC ERR

TRANSF- 24VAC

TRANSF- 15VAC

TRANSF- 12VAC

L-VENT INT-EXT

L
N

N

L-TR

N-TR

~

VENT-EXT

HEATER/

COOL/PUMP

PREHEATER

0-10V GND

POSTHEATER

REC/BYP

GND

PWM

GND

PWM

RPM

(TC)

RPM

24VAC

24VAC

T-EXT-1 T-EXT-2 T-EXT-3 T-INT-1

T-INT-2

FILTER

INT

T-WATER T-WATER T-ROOM

JP1

LED1

DATA

SWO

TX

RX

-OUT

-IN

(TC)

1

~

2

~

1

~

2

15VAC

IN  GND

CO2/RH/EXT

2

1

1

2

10

ModBUS RTU via 

Rs485

GTC

ou

FUSE

(VENT-EXT)

FUSE

(VENT-INT)

FUSE

(PCB)

FUSE

(PERIPHERY)

!

!

defrost

24VAC

POWER SUPPLY

 MIX POINT

MIX. POINT / OUTDOOR 

UNIT DX

INPUT

MAIN ELECTRIC SUPPLY

EXT. SENSOR

(two-wire shielded cable)

or

INLET -Fresh air

OUTLET

 DX = ON/OFF 

(Output for outdoor unit)

Control panel

EXTERNAL 

CONTROL

FIRE

WATER

PUMP CONTROL

ERROR

CONTACT

PRESENCE

SENSOR

SENSOR

SENSOR

1

5

6

11

17

15

16

2

3

4

7

12

13

14

8

9

10

E-SCH-RGJ-HR85

3-050-D06378    

              

13 14

5

7

8

6

10

11

12

9

EN

RU

PL

IT

CS

1

SMU - power supply

Смесительный узел – источник питания

Układ mieszający  zasilanie

Punto di miscelazione - alimentazione

SMU - napájení

2

Control signal (adjustable: SMU, heater/

cooler)

Управляющий сигнал (регулируемый: SMU, 

обогреватель/кулер)

Sygnał sterujący ( do nastawienia  : SMU,heater/

cooler)

Segnale di controllo (impostabile: SMU, heater/

cooler)

Řídící signál (nastavitelné: SMU, heater/

cooler)

3

Spatial sensor

Внутренний датчик

Czujnik przestrzenny

Sensore ambientale

Prostorové čidlo teploty

4

Flap - inlet (fresh air)

Клапан свежего воздуха

Klapa świeżego powietrza

Aletta – Aria fresca

Klapka pro čerstvý vzduch

5

Flap - outlet

Клапан отработанного воздуха

Klapa wydechu

Aletta - Scarico

Klapka pro odvodní vzduch

6

Water pump

Водяной насос (конденсат)

Pompa wodna

Pompa dell‘acqua

Vodní čerpadlo

7

RUN function (adjustable in units with direct 

evaporator: 0-10V/ON-OFF)

Функция RUN (у модулей с прямым 

выпаривателем можно настроить: 0-10V/ON-OFF)

Funkcja RUN (u jednostek z parownikiem bez-

pośrednim  do nastawienia : 0-10V/ON-OFF)

Funzione RUN (impostabile per le unità dotate 

dell’evaporatore diretto: 0-10V/ON-OFF)

Funkce RUN (nastavitelné s jednotkou s 

přímím výparníkem 0-10V / ON/OFF)

8

C/O - cooling/heating 

C/O - охлаждение/ обогрев

C/O - chłodzenie / ogrzewanie

C/O – raffreddamento/riscaldamento

C/O - chlazení/topení

9

Direct evaporator - ERROR

Прямой выпариватель - ERROR

Prosty parownik – ERROR (błąd)

Evaporatore diretto – ERROR

Přímý výparník - ERROR

10

Direct evaporator - defrost

Прямой выпариватель - РАЗМОРОЗКА

Prosty parownik - odmrażanie

Evaporatore diretto - SCONGELAMENTO

Přímý výparník - ODMRAŽOVÁNÍ

11

External control -ON/OFF

Внешнее управление

Sterowanie zewnętrzne  Wł./Wył.

Accensione/spegnimento esterno

Externí ovládání ON/OFF

12

Alarm - FIRE

Пожарный извещатель

Wejście stycznika pożarowego

Fiamma

Poplach - FIRE

13

BOOST regime

Функция Boost

Funkcja BOOST

Boost

Režim BOOST

14

Recuperator - ERROR

Ошибка рекуператора

Usterka rekuperatora

Errore – recuperatore

Chyba rekuperátoru

15

The air quality sensor - power supply

CO2/RH/VOC - источник питания

CO2/RH/VOC - zasilanie

CO2/RH/VOC - alimentazione

Čidlo kvality vzduchu - napájení

16

The air quality sensor - control signal

CO2/RH/VOC - данные

CO2/RH/VOC - data

CO2/RH/VOC - dati

Čidlo kvality vzduchu - ovládání

17

Presence sensor

Датчик движения

Czujnik ruchu

Sensore di presenza

Čidlo přítomnosti

N - Neutral

Entrée

24VAC

24V

GND

GND

GND

CAPTEUR 

PRÉSENCE

DX GENERAL ERROR

(settable)

DX DEFROST 

(settable)

230VAC

GND

2

1

V+

0-10 VDC

CO

2

 /RH/VOC/EXT

CO

2

 / RH/VOC

EXTERNAL

CAPTEUR 0-10V

15VAC

Capteur CO /HR

VDC

0-10

24VAC

Alimentation 

vanne

0-10V 

Vanne/ Groupe Exterieur DX

Capteur Externe.

Câble deux fils blindé

alimentation générale

Registre 

max.1A 

max. 50 m 

Air Neuf

79 80

70 69

68 67

66 65

81 82 55 56

Registre 

Air Rejeté

77 78

23 24

230VAC

POMPE

DE CIRCULATION

76 75

25 26

49 50

59 60

OUTPUT

     DX = ON/OFF 

(Sortie pour unité 

exterieure)

72 71

CONTACT 

ERREUR

Commande 

á distance

63 64

CONTACT 

EXTERNE

ON/OFF

53 54

51 52

CONTACT

INCENDIE

CMSI

62 61

BOOST

BOOST

57 58

boitier de commande

J1/J2

GND GND

15

13 14

9
8
7

10

5
4
3
2

1

6

12

11

16 17 18 19 20 21 22 23 24

82

83

81 80 79 78 77 76 75 74 73

25 26 27 28 29

68 67 66 65 64 63 62 61 60 59 58 57 56 55 54 53 52 51

31

33

35 36 37 38 39 40 41 42 43

9

44 45 46 47 48 49 50

30

32

34

72 71

70 69

GND

N

L

LO

L

LO

L

LO

N

GND

GND

0-10V

+SSR -SSR

GND

0-10V

VENT-INT

230VAC

PIR

230VAC

FLAP-INT

230VAC

FLAP-EXT

230VAC

W. PUMP

ALARM

HEATER

RUN

OUTPUT

COOL/HEAT

HEAT PUMP

HEAT PUMP

ERROR DEFROST EXTERNAL

ON/OFF

FIRE

BOOST

PRESENCE

SENSOR

PIR

REC ERR

TRANSF- 24VAC

TRANSF- 15VAC

TRANSF- 12VAC

L-VENT INT-EXT

L
N

N

L-TR

N-TR

~

VENT-EXT

HEATER/

COOL/PUMP

PREHEATER

0-10V GND

POSTHEATER

REC/BYP

GND

PWM

GND

PWM

RPM

(TC)

RPM

24VAC

24VAC

T-EXT-1 T-EXT-2 T-EXT-3 T-INT-1

T-INT-2

FILTER

INT

T-WATER T-WATER T-ROOM

JP1

LED1

DATA

SWO

TX

RX

-OUT

-IN

(TC)

1

~

2

~

1

~

2

15VAC

IN  GND

CO2/RH/EXT

2

1

1

2

10

ModBUS RTU via 

Rs485

GTC

ou

FUSE

(VENT-EXT)

FUSE

(VENT-INT)

FUSE

(PCB)

FUSE

(PERIPHERY)

!

!

defrost

24VAC

POWER SUPPLY

 MIX POINT

MIX. POINT / OUTDOOR 

UNIT DX

INPUT

MAIN ELECTRIC SUPPLY

EXT. SENSOR

(two-wire shielded cable)

or

INLET -Fresh air

OUTLET

 DX = ON/OFF 

(Output for outdoor unit)

Control panel

EXTERNAL 

CONTROL

FIRE

WATER

PUMP CONTROL

ERROR

CONTACT

PRESENCE

SENSOR

SENSOR

SENSOR

1

5

6

11

17

15

16

2

3

4

7

12

13

14

8

9

10

E-SCH-RGJ-HR85

3-050-D06378    

              

EN

RU

PL

IT

CS

1

SMU - power supply

Смесительный узел – источник питания

Układ mieszający  zasilanie

Punto di miscelazione - alimentazione

SMU - napájení

2

Control signal (adjustable: SMU, heater/

cooler)

Управляющий сигнал (регулируемый: SMU, 

обогреватель/кулер)

Sygnał sterujący ( do nastawienia  : SMU,heater/

cooler)

Segnale di controllo (impostabile: SMU, heater/

cooler)

Řídící signál (nastavitelné: SMU, heater/

cooler)

3

Spatial sensor

Внутренний датчик

Czujnik przestrzenny

Sensore ambientale

Prostorové čidlo teploty

4

Flap - inlet (fresh air)

Клапан свежего воздуха

Klapa świeżego powietrza

Aletta – Aria fresca

Klapka pro čerstvý vzduch

5

Flap - outlet

Клапан отработанного воздуха

Klapa wydechu

Aletta - Scarico

Klapka pro odvodní vzduch

6

Water pump

Водяной насос (конденсат)

Pompa wodna

Pompa dell‘acqua

Vodní čerpadlo

7

RUN function (adjustable in units with direct 

evaporator: 0-10V/ON-OFF)

Функция RUN (у модулей с прямым 

выпаривателем можно настроить: 0-10V/ON-OFF)

Funkcja RUN (u jednostek z parownikiem bez-

pośrednim  do nastawienia : 0-10V/ON-OFF)

Funzione RUN (impostabile per le unità dotate 

dell’evaporatore diretto: 0-10V/ON-OFF)

Funkce RUN (nastavitelné s jednotkou s 

přímím výparníkem 0-10V / ON/OFF)

8

C/O - cooling/heating 

C/O - охлаждение/ обогрев

C/O - chłodzenie / ogrzewanie

C/O – raffreddamento/riscaldamento

C/O - chlazení/topení

9

Direct evaporator - ERROR

Прямой выпариватель - ERROR

Prosty parownik – ERROR (błąd)

Evaporatore diretto – ERROR

Přímý výparník - ERROR

10

Direct evaporator - defrost

Прямой выпариватель - РАЗМОРОЗКА

Prosty parownik - odmrażanie

Evaporatore diretto - SCONGELAMENTO

Přímý výparník - ODMRAŽOVÁNÍ

11

External control -ON/OFF

Внешнее управление

Sterowanie zewnętrzne  Wł./Wył.

Accensione/spegnimento esterno

Externí ovládání ON/OFF

12

Alarm - FIRE

Пожарный извещатель

Wejście stycznika pożarowego

Fiamma

Poplach - FIRE

13

BOOST regime

Функция Boost

Funkcja BOOST

Boost

Režim BOOST

14

Recuperator - ERROR

Ошибка рекуператора

Usterka rekuperatora

Errore – recuperatore

Chyba rekuperátoru

15

The air quality sensor - power supply

CO2/RH/VOC - источник питания

CO2/RH/VOC - zasilanie

CO2/RH/VOC - alimentazione

Čidlo kvality vzduchu - napájení

16

The air quality sensor - control signal

CO2/RH/VOC - данные

CO2/RH/VOC - data

CO2/RH/VOC - dati

Čidlo kvality vzduchu - ovládání

17

Presence sensor

Датчик движения

Czujnik ruchu

Sensore di presenza

Čidlo přítomnosti

N - Neutral

Entrée

24VAC

24V

GND

GND

GND

CAPTEUR 

PRÉSENCE

DX GENERAL ERROR

(settable)

DX DEFROST 

(settable)

230VAC

GND

2

1

V+

0-10 VDC

CO

2

 /RH/VOC/EXT

CO

2

 / RH/VOC

EXTERNAL

CAPTEUR 0-10V

15VAC

Capteur CO /HR

VDC

0-10

24VAC

Alimentation 

vanne

0-10V 

Vanne/ Groupe Exterieur DX

Capteur Externe.

Câble deux fils blindé

alimentation générale

Registre 

max.1A 

max. 50 m 

Air Neuf

79 80

70 69

68 67

66 65

81 82 55 56

Registre 

Air Rejeté

77 78

23 24

230VAC

POMPE

DE CIRCULATION

76 75

25 26

49 50

59 60

OUTPUT

     DX = ON/OFF 

(Sortie pour unité 

exterieure)

72 71

CONTACT 

ERREUR

Commande 

á distance

63 64

CONTACT 

EXTERNE

ON/OFF

53 54

51 52

CONTACT

INCENDIE

CMSI

62 61

BOOST

BOOST

57 58

boitier de commande

J1/J2

GND GND

15

13 14

9
8
7

10

5
4
3
2

1

6

12

11

16 17 18 19 20 21 22 23 24

82

83

81 80 79 78 77 76 75 74 73

25 26 27 28 29

68 67 66 65 64 63 62 61 60 59 58 57 56 55 54 53 52 51

31

33

35 36 37 38 39 40 41 42 43

9

44 45 46 47 48 49 50

30

32

34

72 71

70 69

GND

N

L

LO

L

LO

L

LO

N

GND

GND

0-10V

+SSR -SSR

GND

0-10V

VENT-INT

230VAC

PIR

230VAC

FLAP-INT

230VAC

FLAP-EXT

230VAC

W. PUMP

ALARM

HEATER

RUN

OUTPUT

COOL/HEAT

HEAT PUMP

HEAT PUMP

ERROR DEFROST EXTERNAL

ON/OFF

FIRE

BOOST

PRESENCE

SENSOR

PIR

REC ERR

TRANSF- 24VAC

TRANSF- 15VAC

TRANSF- 12VAC

L-VENT INT-EXT

L
N

N

L-TR

N-TR

~

VENT-EXT

HEATER/

COOL/PUMP

PREHEATER

0-10V GND

POSTHEATER

REC/BYP

GND

PWM

GND

PWM

RPM

(TC)

RPM

24VAC

24VAC

T-EXT-1 T-EXT-2 T-EXT-3 T-INT-1

T-INT-2

FILTER

INT

T-WATER T-WATER T-ROOM

JP1

LED1

DATA

SWO

TX

RX

-OUT

-IN

(TC)

1

~

2

~

1

~

2

15VAC

IN  GND

CO2/RH/EXT

2

1

1

2

10

ModBUS RTU via 

Rs485

GTC

ou

FUSE

(VENT-EXT)

FUSE

(VENT-INT)

FUSE

(PCB)

FUSE

(PERIPHERY)

!

!

defrost

24VAC

POWER SUPPLY

 MIX POINT

MIX. POINT / OUTDOOR 

UNIT DX

INPUT

MAIN ELECTRIC SUPPLY

EXT. SENSOR

(two-wire shielded cable)

or

INLET -Fresh air

OUTLET

 DX = ON/OFF 

(Output for outdoor unit)

Control panel

EXTERNAL 

CONTROL

FIRE

WATER

PUMP CONTROL

ERROR

CONTACT

PRESENCE

SENSOR

SENSOR

SENSOR

1

5

6

11

17

15

16

2

3

4

7

12

13

14

8

9

10

E-SCH-RGJ-HR85

3-050-D06378    

              

17

1

15

18

4

16

EN

RU

PL

IT

CS

1

SMU - power supply

Смесительный узел – источник питания

Układ mieszający  zasilanie

Punto di miscelazione - alimentazione

SMU - napájení

2

Control signal (adjustable: SMU, heater/

cooler)

Управляющий сигнал (регулируемый: SMU, 

обогреватель/кулер)

Sygnał sterujący ( do nastawienia  : SMU,heater/

cooler)

Segnale di controllo (impostabile: SMU, heater/

cooler)

Řídící signál (nastavitelné: SMU, heater/

cooler)

3

Spatial sensor

Внутренний датчик

Czujnik przestrzenny

Sensore ambientale

Prostorové čidlo teploty

4

Flap - inlet (fresh air)

Клапан свежего воздуха

Klapa świeżego powietrza

Aletta – Aria fresca

Klapka pro čerstvý vzduch

5

Flap - outlet

Клапан отработанного воздуха

Klapa wydechu

Aletta - Scarico

Klapka pro odvodní vzduch

6

Water pump

Водяной насос (конденсат)

Pompa wodna

Pompa dell‘acqua

Vodní čerpadlo

7

RUN function (adjustable in units with direct 

evaporator: 0-10V/ON-OFF)

Функция RUN (у модулей с прямым 

выпаривателем можно настроить: 0-10V/ON-OFF)

Funkcja RUN (u jednostek z parownikiem bez-

pośrednim  do nastawienia : 0-10V/ON-OFF)

Funzione RUN (impostabile per le unità dotate 

dell’evaporatore diretto: 0-10V/ON-OFF)

Funkce RUN (nastavitelné s jednotkou s 

přímím výparníkem 0-10V / ON/OFF)

8

C/O - cooling/heating 

C/O - охлаждение/ обогрев

C/O - chłodzenie / ogrzewanie

C/O – raffreddamento/riscaldamento

C/O - chlazení/topení

9

Direct evaporator - ERROR

Прямой выпариватель - ERROR

Prosty parownik – ERROR (błąd)

Evaporatore diretto – ERROR

Přímý výparník - ERROR

10

Direct evaporator - defrost

Прямой выпариватель - РАЗМОРОЗКА

Prosty parownik - odmrażanie

Evaporatore diretto - SCONGELAMENTO

Přímý výparník - ODMRAŽOVÁNÍ

11

External control -ON/OFF

Внешнее управление

Sterowanie zewnętrzne  Wł./Wył.

Accensione/spegnimento esterno

Externí ovládání ON/OFF

12

Alarm - FIRE

Пожарный извещатель

Wejście stycznika pożarowego

Fiamma

Poplach - FIRE

13

BOOST regime

Функция Boost

Funkcja BOOST

Boost

Režim BOOST

14

Recuperator - ERROR

Ошибка рекуператора

Usterka rekuperatora

Errore – recuperatore

Chyba rekuperátoru

15

The air quality sensor - power supply

CO2/RH/VOC - источник питания

CO2/RH/VOC - zasilanie

CO2/RH/VOC - alimentazione

Čidlo kvality vzduchu - napájení

16

The air quality sensor - control signal

CO2/RH/VOC - данные

CO2/RH/VOC - data

CO2/RH/VOC - dati

Čidlo kvality vzduchu - ovládání

17

Presence sensor

Датчик движения

Czujnik ruchu

Sensore di presenza

Čidlo přítomnosti

N - Neutral

Entrée

24VAC

24V

GND

GND

GND

CAPTEUR 

PRÉSENCE

DX GENERAL ERROR

(settable)

DX DEFROST 

(settable)

230VAC

GND

2

1

V+

0-10 VDC

CO

2

 /RH/VOC/EXT

CO

2

 / RH/VOC

EXTERNAL

CAPTEUR 0-10V

15VAC

Capteur CO /HR

VDC

0-10

24VAC

Alimentation 

vanne

0-10V 

Vanne/ Groupe Exterieur DX

Capteur Externe.

Câble deux fils blindé

alimentation générale

Registre 

max.1A 

max. 50 m 

Air Neuf

79 80

70 69

68 67

66 65

81 82 55 56

Registre 

Air Rejeté

77 78

23 24

230VAC

POMPE

DE CIRCULATION

76 75

25 26

49 50

59 60

OUTPUT

     DX = ON/OFF 

(Sortie pour unité 

exterieure)

72 71

CONTACT 

ERREUR

Commande 

á distance

63 64

CONTACT 

EXTERNE

ON/OFF

53 54

51 52

CONTACT

INCENDIE

CMSI

62 61

BOOST

BOOST

57 58

boitier de commande

J1/J2

GND GND

15

13 14

9
8
7

10

5
4
3
2

1

6

12

11

16 17 18 19 20 21 22 23 24

82

83

81 80 79 78 77 76 75 74 73

25 26 27 28 29

68 67 66 65 64 63 62 61 60 59 58 57 56 55 54 53 52 51

31

33

35 36 37 38 39 40 41 42 43

9

44 45 46 47 48 49 50

30

32

34

72 71

70 69

GND

N

L

LO

L

LO

L

LO

N

GND

GND

0-10V

+SSR -SSR

GND

0-10V

VENT-INT

230VAC

PIR

230VAC

FLAP-INT

230VAC

FLAP-EXT

230VAC

W. PUMP

ALARM

HEATER

RUN

OUTPUT

COOL/HEAT

HEAT PUMP

HEAT PUMP

ERROR DEFROST EXTERNAL

ON/OFF

FIRE

BOOST

PRESENCE

SENSOR

PIR

REC ERR

TRANSF- 24VAC

TRANSF- 15VAC

TRANSF- 12VAC

L-VENT INT-EXT

L
N

N

L-TR

N-TR

~

VENT-EXT

HEATER/

COOL/PUMP

PREHEATER

0-10V GND

POSTHEATER

REC/BYP

GND

PWM

GND

PWM

RPM

(TC)

RPM

24VAC

24VAC

T-EXT-1 T-EXT-2 T-EXT-3 T-INT-1

T-INT-2

FILTER

INT

T-WATER T-WATER T-ROOM

JP1

LED1

DATA

SWO

TX

RX

-OUT

-IN

(TC)

1

~

2

~

1

~

2

15VAC

IN  GND

CO2/RH/EXT

2

1

1

2

10

ModBUS RTU via 

Rs485

GTC

ou

FUSE

(VENT-EXT)

FUSE

(VENT-INT)

FUSE

(PCB)

FUSE

(PERIPHERY)

!

!

defrost

24VAC

POWER SUPPLY

 MIX POINT

MIX. POINT / OUTDOOR 

UNIT DX

INPUT

MAIN ELECTRIC SUPPLY

EXT. SENSOR

(two-wire shielded cable)

or

INLET -Fresh air

OUTLET

 DX = ON/OFF 

(Output for outdoor unit)

Control panel

EXTERNAL 

CONTROL

FIRE

WATER

PUMP CONTROL

ERROR

CONTACT

PRESENCE

SENSOR

SENSOR

SENSOR

1

5

6

11

17

15

16

2

3

4

7

12

13

14

8

9

10

E-SCH-RGJ-HR85

3-050-D06378    

              

EN

RU

PL

IT

CS

1

SMU - power supply

Смесительный узел – источник питания

Układ mieszający  zasilanie

Punto di miscelazione - alimentazione

SMU - napájení

2

Control signal (adjustable: SMU, heater/

cooler)

Управляющий сигнал (регулируемый: SMU, 

обогреватель/кулер)

Sygnał sterujący ( do nastawienia  : SMU,heater/

cooler)

Segnale di controllo (impostabile: SMU, heater/

cooler)

Řídící signál (nastavitelné: SMU, heater/

cooler)

3

Spatial sensor

Внутренний датчик

Czujnik przestrzenny

Sensore ambientale

Prostorové čidlo teploty

4

Flap - inlet (fresh air)

Клапан свежего воздуха

Klapa świeżego powietrza

Aletta – Aria fresca

Klapka pro čerstvý vzduch

5

Flap - outlet

Клапан отработанного воздуха

Klapa wydechu

Aletta - Scarico

Klapka pro odvodní vzduch

6

Water pump

Водяной насос (конденсат)

Pompa wodna

Pompa dell‘acqua

Vodní čerpadlo

7

RUN function (adjustable in units with direct 

evaporator: 0-10V/ON-OFF)

Функция RUN (у модулей с прямым 

выпаривателем можно настроить: 0-10V/ON-OFF)

Funkcja RUN (u jednostek z parownikiem bez-

pośrednim  do nastawienia : 0-10V/ON-OFF)

Funzione RUN (impostabile per le unità dotate 

dell’evaporatore diretto: 0-10V/ON-OFF)

Funkce RUN (nastavitelné s jednotkou s 

přímím výparníkem 0-10V / ON/OFF)

8

C/O - cooling/heating 

C/O - охлаждение/ обогрев

C/O - chłodzenie / ogrzewanie

C/O – raffreddamento/riscaldamento

C/O - chlazení/topení

9

Direct evaporator - ERROR

Прямой выпариватель - ERROR

Prosty parownik – ERROR (błąd)

Evaporatore diretto – ERROR

Přímý výparník - ERROR

10

Direct evaporator - defrost

Прямой выпариватель - РАЗМОРОЗКА

Prosty parownik - odmrażanie

Evaporatore diretto - SCONGELAMENTO

Přímý výparník - ODMRAŽOVÁNÍ

11

External control -ON/OFF

Внешнее управление

Sterowanie zewnętrzne  Wł./Wył.

Accensione/spegnimento esterno

Externí ovládání ON/OFF

12

Alarm - FIRE

Пожарный извещатель

Wejście stycznika pożarowego

Fiamma

Poplach - FIRE

13

BOOST regime

Функция Boost

Funkcja BOOST

Boost

Režim BOOST

14

Recuperator - ERROR

Ошибка рекуператора

Usterka rekuperatora

Errore – recuperatore

Chyba rekuperátoru

15

The air quality sensor - power supply

CO2/RH/VOC - источник питания

CO2/RH/VOC - zasilanie

CO2/RH/VOC - alimentazione

Čidlo kvality vzduchu - napájení

16

The air quality sensor - control signal

CO2/RH/VOC - данные

CO2/RH/VOC - data

CO2/RH/VOC - dati

Čidlo kvality vzduchu - ovládání

17

Presence sensor

Датчик движения

Czujnik ruchu

Sensore di presenza

Čidlo přítomnosti

N - Neutral

Entrée

24VAC

24V

GND

GND

GND

CAPTEUR 

PRÉSENCE

DX GENERAL ERROR

(settable)

DX DEFROST 

(settable)

230VAC

GND

2

1

V+

0-10 VDC

CO

2

 /RH/VOC/EXT

CO

2

 / RH/VOC

EXTERNAL

CAPTEUR 0-10V

15VAC

Capteur CO /HR

VDC

0-10

24VAC

Alimentation 

vanne

0-10V 

Vanne/ Groupe Exterieur DX

Capteur Externe.

Câble deux fils blindé

alimentation générale

Registre 

max.1A 

max. 50 m 

Air Neuf

79 80

70 69

68 67

66 65

81 82 55 56

Registre 

Air Rejeté

77 78

23 24

230VAC

POMPE

DE CIRCULATION

76 75

25 26

49 50

59 60

OUTPUT

     DX = ON/OFF 

(Sortie pour unité 

exterieure)

72 71

CONTACT 

ERREUR

Commande 

á distance

63 64

CONTACT 

EXTERNE

ON/OFF

53 54

51 52

CONTACT

INCENDIE

CMSI

62 61

BOOST

BOOST

57 58

boitier de commande

J1/J2

GND GND

15

13 14

9
8
7

10

5
4
3
2

1

6

12

11

16 17 18 19 20 21 22 23 24

82

83

81 80 79 78 77 76 75 74 73

25 26 27 28 29

68 67 66 65 64 63 62 61 60 59 58 57 56 55 54 53 52 51

31

33

35 36 37 38 39 40 41 42 43

9

44 45 46 47 48 49 50

30

32

34

72 71

70 69

GND

N

L

LO

L

LO

L

LO

N

GND

GND

0-10V

+SSR -SSR

GND

0-10V

VENT-INT

230VAC

PIR

230VAC

FLAP-INT

230VAC

FLAP-EXT

230VAC

W. PUMP

ALARM

HEATER

RUN

OUTPUT

COOL/HEAT

HEAT PUMP

HEAT PUMP

ERROR DEFROST EXTERNAL

ON/OFF

FIRE

BOOST

PRESENCE

SENSOR

PIR

REC ERR

TRANSF- 24VAC

TRANSF- 15VAC

TRANSF- 12VAC

L-VENT INT-EXT

L
N

N

L-TR

N-TR

~

VENT-EXT

HEATER/

COOL/PUMP

PREHEATER

0-10V GND

POSTHEATER

REC/BYP

GND

PWM

GND

PWM

RPM

(TC)

RPM

24VAC

24VAC

T-EXT-1 T-EXT-2 T-EXT-3 T-INT-1

T-INT-2

FILTER

INT

T-WATER T-WATER T-ROOM

JP1

LED1

DATA

SWO

TX

RX

-OUT

-IN

(TC)

1

~

2

~

1

~

2

15VAC

IN  GND

CO2/RH/EXT

2

1

1

2

10

ModBUS RTU via 

Rs485

GTC

ou

FUSE

(VENT-EXT)

FUSE

(VENT-INT)

FUSE

(PCB)

FUSE

(PERIPHERY)

!

!

defrost

24VAC

POWER SUPPLY

 MIX POINT

MIX. POINT / OUTDOOR 

UNIT DX

INPUT

MAIN ELECTRIC SUPPLY

EXT. SENSOR

(two-wire shielded cable)

or

INLET -Fresh air

OUTLET

 DX = ON/OFF 

(Output for outdoor unit)

Control panel

EXTERNAL 

CONTROL

FIRE

WATER

PUMP CONTROL

ERROR

CONTACT

PRESENCE

SENSOR

SENSOR

SENSOR

1

5

6

11

17

15

16

2

3

4

7

12

13

14

8

9

10

E-SCH-RGJ-HR85

3-050-D06378    

              

7

9

8

EN

RU

PL

IT

CS

1

SMU - power supply

Смесительный узел – источник питания

Układ mieszający  zasilanie

Punto di miscelazione - alimentazione

SMU - napájení

2

Control signal (adjustable: SMU, heater/

cooler)

Управляющий сигнал (регулируемый: SMU, 

обогреватель/кулер)

Sygnał sterujący ( do nastawienia  : SMU,heater/

cooler)

Segnale di controllo (impostabile: SMU, heater/

cooler)

Řídící signál (nastavitelné: SMU, heater/

cooler)

3

Spatial sensor

Внутренний датчик

Czujnik przestrzenny

Sensore ambientale

Prostorové čidlo teploty

4

Flap - inlet (fresh air)

Клапан свежего воздуха

Klapa świeżego powietrza

Aletta – Aria fresca

Klapka pro čerstvý vzduch

5

Flap - outlet

Клапан отработанного воздуха

Klapa wydechu

Aletta - Scarico

Klapka pro odvodní vzduch

6

Water pump

Водяной насос (конденсат)

Pompa wodna

Pompa dell‘acqua

Vodní čerpadlo

7

RUN function (adjustable in units with direct 

evaporator: 0-10V/ON-OFF)

Функция RUN (у модулей с прямым 

выпаривателем можно настроить: 0-10V/ON-OFF)

Funkcja RUN (u jednostek z parownikiem bez-

pośrednim  do nastawienia : 0-10V/ON-OFF)

Funzione RUN (impostabile per le unità dotate 

dell’evaporatore diretto: 0-10V/ON-OFF)

Funkce RUN (nastavitelné s jednotkou s 

přímím výparníkem 0-10V / ON/OFF)

8

C/O - cooling/heating 

C/O - охлаждение/ обогрев

C/O - chłodzenie / ogrzewanie

C/O – raffreddamento/riscaldamento

C/O - chlazení/topení

9

Direct evaporator - ERROR

Прямой выпариватель - ERROR

Prosty parownik – ERROR (błąd)

Evaporatore diretto – ERROR

Přímý výparník - ERROR

10

Direct evaporator - defrost

Прямой выпариватель - РАЗМОРОЗКА

Prosty parownik - odmrażanie

Evaporatore diretto - SCONGELAMENTO

Přímý výparník - ODMRAŽOVÁNÍ

11

External control -ON/OFF

Внешнее управление

Sterowanie zewnętrzne  Wł./Wył.

Accensione/spegnimento esterno

Externí ovládání ON/OFF

12

Alarm - FIRE

Пожарный извещатель

Wejście stycznika pożarowego

Fiamma

Poplach - FIRE

13

BOOST regime

Функция Boost

Funkcja BOOST

Boost

Režim BOOST

14

Recuperator - ERROR

Ошибка рекуператора

Usterka rekuperatora

Errore – recuperatore

Chyba rekuperátoru

15

The air quality sensor - power supply

CO2/RH/VOC - источник питания

CO2/RH/VOC - zasilanie

CO2/RH/VOC - alimentazione

Čidlo kvality vzduchu - napájení

16

The air quality sensor - control signal

CO2/RH/VOC - данные

CO2/RH/VOC - data

CO2/RH/VOC - dati

Čidlo kvality vzduchu - ovládání

17

Presence sensor

Датчик движения

Czujnik ruchu

Sensore di presenza

Čidlo přítomnosti

N - Neutral

Entrée

24VAC

24V

GND

GND

GND

CAPTEUR 

PRÉSENCE

DX GENERAL ERROR

(settable)

DX DEFROST 

(settable)

230VAC

GND

2

1

V+

0-10 VDC

CO

2

 /RH/VOC/EXT

CO

2

 / RH/VOC

EXTERNAL

CAPTEUR 0-10V

15VAC

Capteur CO /HR

VDC

0-10

24VAC

Alimentation 

vanne

0-10V 

Vanne/ Groupe Exterieur DX

Capteur Externe.

Câble deux fils blindé

alimentation générale

Registre 

max.1A 

max. 50 m 

Air Neuf

79 80

70 69

68 67

66 65

81 82 55 56

Registre 

Air Rejeté

77 78

23 24

230VAC

POMPE

DE CIRCULATION

76 75

25 26

49 50

59 60

OUTPUT

     DX = ON/OFF 

(Sortie pour unité 

exterieure)

72 71

CONTACT 

ERREUR

Commande 

á distance

63 64

CONTACT 

EXTERNE

ON/OFF

53 54

51 52

CONTACT

INCENDIE

CMSI

62 61

BOOST

BOOST

57 58

boitier de commande

J1/J2

GND GND

15

13 14

9
8
7

10

5
4
3
2

1

6

12

11

16 17 18 19 20 21 22 23 24

82

83

81 80 79 78 77 76 75 74 73

25 26 27 28 29

68 67 66 65 64 63 62 61 60 59 58 57 56 55 54 53 52 51

31

33

35 36 37 38 39 40 41 42 43

9

44 45 46 47 48 49 50

30

32

34

72 71

70 69

GND

N

L

LO

L

LO

L

LO

N

GND

GND

0-10V

+SSR -SSR

GND

0-10V

VENT-INT

230VAC

PIR

230VAC

FLAP-INT

230VAC

FLAP-EXT

230VAC

W. PUMP

ALARM

HEATER

RUN

OUTPUT

COOL/HEAT

HEAT PUMP

HEAT PUMP

ERROR DEFROST EXTERNAL

ON/OFF

FIRE

BOOST

PRESENCE

SENSOR

PIR

REC ERR

TRANSF- 24VAC

TRANSF- 15VAC

TRANSF- 12VAC

L-VENT INT-EXT

L
N

N

L-TR

N-TR

~

VENT-EXT

HEATER/

COOL/PUMP

PREHEATER

0-10V GND

POSTHEATER

REC/BYP

GND

PWM

GND

PWM

RPM

(TC)

RPM

24VAC

24VAC

T-EXT-1 T-EXT-2 T-EXT-3 T-INT-1

T-INT-2

FILTER

INT

T-WATER T-WATER T-ROOM

JP1

LED1

DATA

SWO

TX

RX

-OUT

-IN

(TC)

1

~

2

~

1

~

2

15VAC

IN  GND

CO2/RH/EXT

2

1

1

2

10

ModBUS RTU via 

Rs485

GTC

ou

FUSE

(VENT-EXT)

FUSE

(VENT-INT)

FUSE

(PCB)

FUSE

(PERIPHERY)

!

!

defrost

24VAC

POWER SUPPLY

 MIX POINT

MIX. POINT / OUTDOOR 

UNIT DX

INPUT

MAIN ELECTRIC SUPPLY

EXT. SENSOR

(two-wire shielded cable)

or

INLET -Fresh air

OUTLET

 DX = ON/OFF 

(Output for outdoor unit)

Control panel

EXTERNAL 

CONTROL

FIRE

WATER

PUMP CONTROL

ERROR

CONTACT

PRESENCE

SENSOR

SENSOR

SENSOR

1

5

6

11

17

15

16

2

3

4

7

12

13

14

8

9

10

E-SCH-RGJ-HR85

3-050-D06378    

              

11 12

M

max. 2 

A

max. 2 

A

max. 2 

A

4

66

GND

B

A

64

63

10

NTC 10K

NTC 10K

NTC 10K

SLAVE

B

A

26

25

MODBUS RTU

MODBUS TCP,

BACnet, LAN

13

24V

GND

in control module

in Steuermodul

24V

GND

0-10V

HEAT
0-10V

66

GND

VCST4-AGSU1-M-EC-

EF

VCST4-AGSU1-M-EC-

SO

VCST4-AGSU1-M-EC-

VF

Содержание AirGENIO

Страница 1: ...Superior controls v 1 18 08 21 AirGENIO FINESSE EC STANDESSE EC installation operation and maintenance...

Страница 2: ...y after delivery In case damage on the packaging contact the carrier Claims not filed in due time will be disregarded Check that it corresponds to the type of product ordered In case of discrepancy do...

Страница 3: ...us b t objedn v ny zvl v clona je p ipojena k d c mu modulu Rychl ch p ipojovac ch konektor te d c modul do vzduchov clony 17 STALACE Vzduchov clona mus b t chr n na vhodn m jisti em v souladu s jeho...

Страница 4: ...and your business since 1995 Connection to the regulation control panel and accessories a b c d Connect the remote control and accessories to the terminals on the PCB CONNECTING THE CONTROL CANL 30 C...

Страница 5: ...tawienia SMU heater cooler Segnale di controllo impostabile SMU heater cooler d c sign l nastaviteln SMU heater cooler Czujnik przestrzenny Sensore ambientale Prostorov idlo teploty Klapa wie ego powi...

Страница 6: ...terieure 72 71 CONTACT ERREUR Commande distance 63 64 CONTACT EXTERNE ON OFF CONTACT INCENDIE CMSI 62 61 BOOST BOOST 57 58 boitier de commande J1 J2 20 21 22 23 24 76 75 74 73 25 26 27 28 29 68 67 66...

Страница 7: ...MASTER SLAVE no 1 The total length of the connected air curtains must not exceed 150 m ELECTRICAL DRAWINGS CHAINING SLAVE no 2 SLAVE no 10 SLA VE no 1 1 no 2 2 no 3 3 no 4 4 no 5 5 SLA VE no 6 6 no 7...

Страница 8: ...oor temperature sensor The outdoor temperature sensor is located on the north side of the building so that it is not exposed to direct sunlight or other unwanted heat radiation It is recommended to in...

Страница 9: ...e TV1 1 1 detailed description on the page 399 Three way valve with servo drive ZV 3 detailed description on the page 395 Mischknoten SMU xx xx n here Beschreibung auf de WIRING DIAGRAMS The recommend...

Страница 10: ...it check the following Did you leave inside tools or objects that could damage the unit Is the supply of energy and heating water if applicable adequate Is the unit well closed Is the control module p...

Страница 11: ...ut of order Temperature sensor malfunction on terminals 53 54 Check that the sensor is correctly connected to the electronics or test it measuring its resistance the resistance value at 20 C is around...

Страница 12: ...he supplier s Give the following information to the supplier or service type designation of the air curtain accessories in use place of installation serial number conditions of the installation incl e...

Страница 13: ...RELAY GND 0 10 GND GND GND GND GND 1 2 3 4 5 6 7 8 9 11 10 12 13 14 15 16 17 18 19 20 21 22 23 24 IN 1 IN 2 L F L F INT OUT ERR TERM L L Fu 57 58 59 60 61 62 32 31 56 55 54 53 52 51 50 48 49 47 46 45...

Страница 14: ...GND T2 T3 T4 T5 T6 T7 T8 T9 T10 1 2 3 12V L N GND RPM PWM 31 32 33 34 GND 0 10 29 30 BCD 0 ANALOG GND GND GND 4 5 6 7 8 9 10 11 12 13 14 15 B 2 3 1 A GND 12V SUPPLY CTRL THER DOOR MODBUS RTU USED L 1...

Страница 15: ...SED 0 10V ROOM RELAY RELAY RELAY RELAY GND 0 10 GND GND GND GND GND 1 2 3 4 5 6 7 8 9 11 10 12 13 14 15 16 17 18 19 20 21 22 23 24 IN 1 IN 2 L F L F INT OUT ERR TERM L L Fu 57 58 59 60 61 62 32 31 56...

Страница 16: ...2 T3 T4 T5 T6 T7 T8 T9 T10 12V L N 24V L N 24V GND 0 10V GND RPM PWM 31 32 33 34 GND 0 10 29 30 BCD 0 ANALOG GND GND GND 4 5 6 7 8 9 10 11 12 13 14 15 B 2 3 1 A GND 12V SUPPLY CTRL THER DOOR MODBUS RT...

Страница 17: ...Y RELAY GND 0 10 GND GND GND GND GND 1 2 3 4 5 6 7 8 9 11 10 12 13 14 15 16 17 18 19 20 21 22 23 24 IN 1 IN 2 L F L F INT OUT ERR TERM L L Fu 57 58 59 60 61 62 32 31 56 55 54 53 52 51 50 48 49 47 46 4...

Страница 18: ...T6 T7 T8 T9 T10 1 2 3 12V L N GND RPM PWM 31 32 33 34 GND 0 10 29 30 BCD 0 ANALOG GND GND GND 4 5 6 7 8 9 10 11 12 13 14 15 B 2 3 1 A GND 12V SUPPLY CTRL THER DOOR MODBUS RTU USED L 19 20 16 17 18 GND...

Страница 19: ...you and your business since 1995 CONCLUSION In case of any doubt or query do not hesitate to contact our sales or technical support departments CONTACT Address 2VV s r o F blovka 568 533 52 Pardubice...

Отзывы: