46
2N TELEKOMUNIKACE a.s., www.2n.cz
945
Minimum
count of
busy tone
periods
2–50
5
948
Minimum
ringback
tone time
50–2000 ms 500 ms
For outgoing call detection:
The ringback tone time is a time
interval before the long gap.
The longest ringing period gap must
be in the interval between parameters
949 and 950.
949
Minimum
ringback
tone long
gap time
100–5000
ms
1000 ms
950
Minimum
ringback
tone long
gap time
500–9999
ms
5500 ms
951
Minimum
ringing time
50–2000 ms 500 ms
For incoming call detection:
The ringtone time is the sum of
sections between which there is no
long gap.
The longest ringing period gap must
be in the interval between parameters
952 and 953.
952
Minimum
ringing long
gap time
100–5000
ms
1000 ms
953
Maximum
ringing long
gap time
500–9999
ms
6000 ms
954
Count of
ringback
tone periods
1–99
10
2N Lift1
®
hangs up after this count
and dials the next number if
Automatic dialling is enabled.
961
Maximum
interdigit
time
5–120 s
10 s
For password entering
962
Minimum
cabin ALARM
button
pressing
time
100–9999
ms
5000 ms
Applies to the ALARM button and
button 2.
964
Minimum
CANCEL
input
activation
time
100–9999
ms
100 ms
971
Message
repeating
count
0–9
3
There is 5-second space between two
announcements.
972
Message
recording
0–30 s
empty
User announcement recording
function, can be used for lift
identification.
974
Lift
identification
number
up to 16
digits: 0–9
empty
Numeric lift identification
Содержание 913621E