3.  Unit Mounting

GND NO COM NC

DT-RLC

2-WIRE SYSTEM

12V

S2

S1 GND

POWER    IN-USE

BUS BUS

RISER

1
2
3

DIN Rail Mounting

4.  How To Set The Work Mode

Note that the factory default is lock control mode.
1).In DIP1 = ON, DIP2 = ON, DIP3 = OFF status, exit button(S1 and GND) short-
circuit, meanwhile, the DT-RLC will power-on to activate the setting mode;
2).In setting status, struck repeatedly DIP1 four times to switch work modes:
    A.When the IN-USE indicator flashes once, it means the system will enter the lock   

control mode.

    B.When the IN-USE indicator flashes two times, it means the system will enter the 

light control mode.

3).When the setting complete,it will automatically restart.
Please note the setting state valid within 5 seconds, more than five seconds without 
operation, it will exit the setting mode automatically.

NC:The normally-closed contact to COM.
COM: The common contact of the unlock/light relay.
NO: The normally-open contact to COM.

Lock Control Jumper: To select the lock type: 

see section 5.3, 5.4. 

POWER:Working indicator, it will light up when plugs in power supply.
IN-USE:Unlock/light indicator, it will light up when unlock(or turn on the light).
Bus:Connect to the bus line, no polarity.
DIP :Used for setting the address of the RLC.

Содержание DT-RLC

Страница 1: ...before using the product you purchase and keep it well for future use We reserve the right to modify the specification in this manual at any time without notice GND NO COM NC DT RLC 2 WIRE SYSTEM 12V...

Страница 2: ...ght control mode Allows to open gate door locks or control lights Support high power consumption lock With configurable unlock timed output or light control timed output Support exit control button wh...

Страница 3: ...n the IN USE indicator flashes two times it means the system will enter the light control mode 3 When the setting complete it will automatically restart Please note the setting state valid within 5 se...

Страница 4: ...ght 3 Short circuit again S2 meanwhile the time of short circuit equal to unlock time the IN USE indicator flashes once per second Less than two seconds by one second calculation The maximum setting t...

Страница 5: ...ON 1 2 3 ON 1 2 3 ON 5 3 Internal powered lock connection only suitable for Power on to unlock type BUS IM BUS DS PC6 Exit Button GND S1 S2 12V NC COM NO GND E lock AC monitor L1 L2 PL S S 1 Camera D...

Страница 6: ...ock Exit Button DT RLC DT RLC connect lock 5 4 External Power Supply powered lock connection BUS IM BUS DS PC6 Exit Button GND S1 S2 12V NC COM NO GND AC monitor L1 L2 PL S S adaptor for the lock E lo...

Страница 7: ...c lock DT RLC connect lock BUS IM BUS DS PC6 Exit Button GND S1 S2 12V NC COM NO GND AC monitor L1 L2 PL S S adaptor for the lock EM lock 1 Camera Device Address 0 NO POWER IN USE BUS GND COM NC DT RL...

Страница 8: ...conds and the IN USE indicator always light 3 Short circuit again S2 meanwhile the time of short circuit 1 seconds equal to light working time 30 seconds the IN USE indicator flashes once per second T...

Страница 9: ...he sixth DT RLC ON ON OFF Set to the seventh DT RLC ON ON ON Set to the eighth DT RLC 1 2 3 ON 1 2 3 ON 1 2 3 ON 1 2 3 ON 1 2 3 ON 1 2 3 ON 1 2 3 ON 6 3 DT RLC Connections for Light Control 110 250V A...

Страница 10: ...POWER IN USE GND S1 S2 12V NC COM NO GND LED Exit Button DT RLC POWER IN USE GND S1 S2 12V NC COM NO GND adaptor for the lock E lock Safety Type power on to open power off to lock 1 2 3 ON DIP 1 2 3 O...

Страница 11: ...1s Lock Power supply 12Vdc 450mA Internal Power Working Temperature 100 C 400 C Dimension 89 H 71 W 45 D mm The design and specifications can be changed without notice to the user Right to interpret a...