NOTICE TO INSTALLER: Instructions must remain with installation.

FM2922

0716

Supersedes

1015

© Copyright 2016 Zoeller

®

 Co. All rights reserved.

DATE INSTALLED:

MODEL NUMBER:

PREASSEMBLED SUMP PUMP SYSTEM WITH BATTERY BACKUP

MODEL 507 - 12 V DC BATTERY BACKUP SYSTEM WITH 120 V AC POWERED SUMP PUMP, MODEL M73

INSTALLATION INSTRUCTIONS

Product information presented 

here reflects conditions at time 

of  publication. Consult factory 

regarding discrepancies or 

inconsistencies.

MAIL TO:  P.O. BOX 16347 • Louisville, KY  40256-0347

SHIP TO:  3649 Cane Run Road  • Louisville, KY  40211-1961

(502) 778-2731 • 1 (800) 928-PUMP • FAX (502) 774-3624

visit our web site:

www.zoeller.com

®

Your Peace of Mind is Our Top Priority

 

®

NOTICE: VENT HOLE FOR 

CHECK VALVE SEE #1 IN 

CAUTION SECTION BELOW

Register your 

Zoeller Pump Company 

Product on our website:

http://reg.zoellerpumps.com/

507/73

  1.  Make certain that the receptacle is within the reach of the pump’s power supply 

cord.  Do not use primary pump circuit.  DO NOT USE AN EXTENSION CORD.  

Extension cords that are too long or too light do not deliver sufficient voltage 

to the pump motor.  But, more important, they could present a safety hazard 

if the insulation were to become damaged or the connection end were to fall 

into the sump.

 2.  Check to be sure your power source is capable of handling the voltage 

requirements of the motor, as indicated on the pump name plate.

 3.  Make sure the pump electrical supply circuit is equipped with fuses or circuit 

breakers of proper capacity.  A separate branch circuit is recommended, sized 

according to the “National Electrical Code” for the current shown on the pump 

nameplate.

 4.  Testing for ground.  As a safety measure, each electrical outlet should be 

checked for ground using an Underwriters Laboratory Listed circuit analyzer 

which will indicate if the power, neutral and ground wires are correctly connected 

to your outlet.  If they are not, call a qualified, licensed electrician.

 5.  For Added Safety.  Pumping and other equipment with a 3-prong grounded 

plug must be connected to a 3-prong grounded receptacle. For added safety 

the receptacle may be protected with a ground-fault circuit interrupter.  When 

a pump needs to be connected in a watertight junction box, the plug can be 

removed and spliced to the supply cable with proper grounding.  For added 

safety this circuit may be protected by a ground-fault circuit interrupter.  The 

complete installation must comply with the National Electrical Code and all 

applicable local codes and ordinances.

 6.  FOR YOUR PROTECTION, ALWAYS DISCONNECT PUMP FROM ITS 

POWER SOURCE BEFORE HANDLING.  Single phase pumps are supplied 

with a 3-prong grounded plug to help protect you against the possibility of 

electrical shock.  DO NOT, UNDER ANY CIRCUMSTANCES, REMOVE THE 

GROUND PIN.  The 3-prong plug must be inserted into a mating 3-prong 

grounded receptacle.  If the installation does not have such a receptacle, it 

must be changed to the proper type, wired and grounded in accordance with 

the National Electrical Code and all applicable local codes and ordinances.

 7. 

Risk of electrical shock.

  Do not remove power supply cord and strain relief 

or connect conduit directly to the pump.

  8.  Installation and servicing of electrical circuits and hardware should be performed 

by a qualified, licensed electrician.

 9.  Pump installation and servicing  should be performed by a qualified person.

 10. 

Risk of electrical shock.

 These pumps have not been investigated for use 

in swimming pool and marine areas.

 11.  It is the owner’s responsibility to check the battery and battery connection 

at 

least once a month

. Batteries contain acid and caution must be taken when 

handling.

SEE BELOW FOR

LIST OF WARNINGS

SAFETY INSTRUCTIONS

REFER TO CAUTIONS AND WARRANTY ON PAGE 2.

TO AVOID SERIOUS OR FATAL PERSONAL INJURY OR MAJOR 

PROPERTY DAMAGE, READ AND FOLLOW ALL SAFETY 

INSTRUCTIONS IN THIS MANUAL AND ON THE PUMP.

THIS MANUAL IS INTENDED TO ASSIST IN THE INSTALLATION AND 

OPERATION OF THIS UNIT AND MUST BE KEPT WITH THE PUMP.

This is a 

SAFETY ALERT SYMBOL. 

When you see this 

symbol on the pump or in the manual, look for one of the 

following signal words and be alert to the potential for 

personal injury or property damage.

Warns of hazards that 

CAN 

cause serious personal injury, 

death or major property damage.

Warns of hazards that 

CAN 

cause personal injury or 

property damage.

Warns of electrical shock hazards that can cause serious 

personal injury, death or major property damage.

Identifies any terminal which is intended for connection 

to and external conductor for protection against electrical 

shock in case of a fault, or the terminal of a protective 

earth (ground) electrode.
Read operator's manual.

THOROUGHLY REVIEW ALL INSTRUCTIONS AND WARNINGS PRIOR 

TO PERFORMING ANY WORK ON THIS PUMP.

MAINTAIN ALL SAFETY DECALS.

CAUTION

1.   Inspect all materials. Occasionally, products are damaged during shipment.  If the unit is damaged, contact your dealer before using. 

DO NOT

 remove the test/

oil fill plugs from the pump.

2.   Carefully read the literature provided to familiarize yourself with specific details regarding installation and use. These materials should be retained for future reference.

PREINSTALLATION CHECKLIST - ALL INSTALLATIONS

Summary of Contents for ProPak 507

Page 1: ...dinances 6 FOR YOUR PROTECTION ALWAYS DISCONNECT PUMP FROM ITS POWER SOURCE BEFORE HANDLING Single phase pumps are supplied with a 3 prong grounded plug to help protect you against the possibility of electrical shock DO NOT UNDER ANY CIRCUMSTANCES REMOVE THE GROUND PIN The 3 prong plug must be inserted into a mating 3 prong grounded receptacle If the installation does not have such a receptacle it...

Page 2: ...batteries We offer both a Water Acid Deep Cycle Battery and maintenance free AGM battery which can run the pump continuously for over 7 hours These times are based on continuous pumping at 8 2 4 mm of static head Actual times will vary depending on static head volume of water entering the pit and the condition of the battery Follow these recommendations Use a B C I size 27 deep cycle battery 175 m...

Page 3: ...TALLATION FOR ALL APPLICATIONS EASY DO S DON TS FOR INSTALLING A SUMP PUMP 1 DO read thoroughly all installation material provided with the system 2 DO inspect system for any visible damage caused by shipping Contact dealer if system appears to be damaged 3 DO clean all debris from the sump Be sure that the pump will have a hard flat surface beneath it DO NOT install on sand gravel or dirt 4 DO be...

Page 4: ...HTEN ONLY WEEP HOLE MUST BE VISIBLE FLOAT SWITCH DC PUMP M73 PRIMARY PUMP CLAMP TYPICAL INSTALLATION EXPLODED VIEW OF PUMP SYSTEM FIGURE 1 R R DC PUMP PLUMBED IN LINE WITH SUBMERSIBLE PUMP BATTERY BOX IMPORTANT OFF LEVEL OF FLOAT ASSEMBLY MUST BE 1 25 MM MIN ABOVE CENTER OF TEE SEE INSTALLATION NOTE 3 VERIFY WEEP HOLE IS VISIBLE SEE PUMP INSTALLATION INSTRUCTIONS CHECK VALVE WEEP HOLE PROVIDED PUM...

Page 5: ...may be set on a nearby shelf or ledge The control charger should be located 3 0 9 m or 4 1 2 m above the sump 5 Connect the green sensor wire to the sensor connector figure 3 6 Connect the leads from the control charger to the battery terminals White positive lead to positive terminal and black negative lead INITIAL START UP AND OPERATION 1 Test the installation for leaks by running water into the...

Page 6: ...ECKLIST EXPLODED VIEW DC PUMP All installations must comply with all applicable electrical and plumbing codes including but not limited to National Electrical Code local regional and or state plumbing codes etc Not intended for use in hazardous locations SK2501 BATTERY BOX 12 VOLT MARINE BATTERY SUPPLIED BY USER FIG 5 DC BACK UP PUMP CLAMP FLOAT SWITCH WHITE LEAD TO POSITIVE BLACK LEAD TO DC PUMP ...

Page 7: ...condition a mixture of air and water may cause a complete or partial air lock and reduce or stop the flow of water in the discharge pipe b Baffle the incoming stream of water to reduce turbulence Diverting water stream against wall of basin usually corrects an air lock problem 7 Water level stays high DC Pump continues to run a Battery is low b If power has been restored and water in sump remains ...

Page 8: ...CYCLED CHARGING ALARM RESET LOW BATTERY ALARM OFF ALARM CONTACTS GREEN LEAD TO FLOAT SWITCH BLACK LEAD WHITE LEAD FIGURE 4 SK2503 FIGURE 5 SK2958 LCD DISPLAY AND KEYPAD FUNCTIONS There are two buttons on the front of the charger The scroll button is used to cycle through the information on the LCD screen The alarm reset button Can be pressed to clear alarm buzzer light and or display Can be held f...

Page 9: ... la bombanecesiteconectarseaunacajadeconexiónestancaalagua sepuede quitar el enchufe y empalmarla al cable de alimentación debidamente puesto a tierra Para mayor seguridad es posible que este circuito esté protegido con un interruptor con detección de falla a tierra La instalación completa debe cumplir el Código Eléctrico Nacional y todos los códigos y disposiciones locales pertinentes 6 PARA SU P...

Page 10: ...cerá garantía alguna por ningún material o producto que haya sido desarmado sin aprobación previa del Fabricante o que haya sido sometido a uso indebido aplicación indebida negligencia alteración accidente o acto de naturaleza que no haya sido instalado usado o mantenido según las instrucciones de instalación del Fabricante que haya sido expuesto a sustancias foráneas que incluyen pero no se limit...

Page 11: ... el contenedor para agua debe quedar limpio y sin residuos 8 La válvula de paso o la válvula de bola deben ser suministradas por el instalador e instaladas de acuerdo con todos los códigos 9 Se requieren sellos estancos al gas que retengan los gases y olores 10 Ventile los gases y olores hacia la atmósfera a través de una tubería de ventilación 11 Instale el soporte de la bomba Zoeller modelo 10 2...

Page 12: ...EBE ESTAR VISIBLE INTERRUPTOR DE FLOTADOR BOMBA CC M73 BOMBA PRINCIPAL ABRAZADERA INSTALACIÓN NORMAL VISTA EN DESPIECE DEL SISTEMA DE LA BOMBA FIGURA 1 R R BOMBA DE CC CONECTADA EN LÍNEA CON BOMBA SUMERGIBLE CAJA DE BATERÍA IMPORTANTE EL NIVEL DE APAGADO DEL CONJUNTO DE FLOTADOR DEBE ESTAR A UN MIN DE 2 5 CM 1 PULG POR ENCIMA DEL CENTRO DE LA T VEA LA NOTA DE INSTALACIÓN 3 VERIFIQUE QUE EL ORIFICI...

Page 13: ... conveniente el cargador de control puede ajustarse en un estante o repisa que esté cerca El cargador de control debe estar situado a 0 9 o 1 2 m 3 o 4 pies por encima del sumidero 5 Conecte el cable verde del sensor al conector del sensor figura 3 6 Conecte los cables del cargador de control a los terminales de la batería El cable blanco pos al terminal positivo y el cable negro ARRANQUE INICIAL ...

Page 14: ... con todos los códigos eléctricos y de instalación sanitaria aplicables incluyendo pero sin limitarse al Código Eléctrico Nacional los códigos locales regionales y o los códigos estatales de instalación sanitaria etc No se debe usar las instalaciones en lugares peligrosos No está diseñada para uso en lugares peligrosos SK2501 CAJA DE BATERIA BATERÍA MARINA DE 12 V PROVISTA POR EL USUARIO FIG 5 BOM...

Page 15: ...orriente de 115 V y desconecte el cable negro negativo del cargador de la batería Compruebe la batería Reemplace el motor si es necesario Vuelva a conectar y consulte el paso Instalación paso 7 9 La alarma no suena cuando la bomba está en funcionamiento a La bomba tiene que estar en funcionamiento durante 1 o más segundos antes de que suene la alarma b Asegúrese de que alarma no haya sido silencia...

Page 16: ...BAJA ALARMA DESACTIVADA CONTACTOS DE LAALARMA CABLE VERDE AL INTERRUPTOR DE FLOTADOR CABLE NEGRO CABLE BLANCO FIGURA 4 SK2503 FIGURA 5 SK2958 PANTALLA LCD Y FUNCIONES DEL TECLADO Hay dos botones en la parte frontal del cargador El botón de desplazamiento se utiliza para desplazarse por la información en la pantalla LCD El botón de reinicio de la alarma Puede ser presionado para silenciar el timbre...

Page 17: ...A BROCHE DE MISE À TERRE La fiche à 3 broches doit être insérée dans une prise à 3 broches mise à la terre Si l installation ne comprend pas de prise il faut la changer pour le type approprié la câbler et la mettre à la terre en conformité avec le code national de l électricité ainsi que tous les codes et règlements locaux applicables 7 Risqued électrocution Nepasenleverlecordond alimentationniled...

Page 18: ...Il faut utiliser une batterie à décharge poussée B C I de taille 27 avec une réserve de 175 minutes ou de plus grande capacité IL NE FAUT PAS utiliser de batterie sans entretien sauf si elle est du type à électrolyte gélifié ou de type AGM Il faut remplacer la batterie tous les trois ans Il ne faut pas permettre l accumulation de corrosion sur les bornes de la batterie Il ne faut pas mettre la bat...

Page 19: ...nstaller and installed according to any and all codes 9 Gas tight seals required to contain gases and odors 10 Des joints étanches aux gaz sont nécessaires pour contenir les gaz et les odeurs 11 Installer le pied de pompe Zoeller modèle 10 2421 sous la pompe pour fournir une cuve de décantation INSTALLATION RECOMMANDÉE POUR TOUTES APPLICATIONS CONSEILS POUR L INSTALLATION D UNE POMPE DE PUISARD 1 ...

Page 20: ... ÉVENT DOIT ÊTRE VISIBLE INTERRUPTEUR À FLOTTEUR POMPE C C POMPE PRINCIPALE M73 COLLIER INSTALLATION TYPIQUE VUE EXPLOSÉE DE LA POMPE FIGURE 1 R R IMPORTANT LE NIVEAU D ARRÊT DU FLOTTEUR DOIT ÊTRE À 2 5 CM 1 PO AU MINIMUM AU DESSUS DU CENTRE DU TÉ VOIR LE POINT 3 DE L INSTALLATION S ASSURER QUE LE TROU D ÉVENT EST VISIBLE VOIR LES INDICATIONS D INSTALLATION DE LA POMPE CLAPET ANTIRETOUR TROU D ÉVA...

Page 21: ... 3 et 4 pi au dessus du puisard 5 Raccorder le fil vert du capteur au raccordement du capteur figure 3 6 Brancher les fils du chargeur aux bornes de la batterie Le fil positif blanc à la borne positive et le fil négatif noir à la borne négative de la batterie Lorsque la connexion est bonne une alarme de test retentit DÉMARRAGE INITIAL ET FONCTIONNEMENT 1 Tester l installation à la recherche de fui...

Page 22: ...allations doivent être conformes aux codes électriques et de plomberie applicables y compris mais pas limité aux codes électriques nationaux locaux régionaux et aux codes de plomberie provinciaux Pas conçu pour utilisation dans les endroits dangereux SK2501 FIGURE 3 Copyright 2016 Zoeller Co Tous droits réservés BOÎTIER DE LA BATTERIE 12 V BATTERIE MARINE FOURNIE PAR L UTILISATEUR POMPE DE SECOURS...

Page 23: ...e la prise murale 115 V puis débrancher le fil noir du chargeur sur la borne négative de la batterie Vérifier la batterie La remplacer si nécessaire Rebrancher et se référer à l installation étape 7 9 L alarme ne sonne pas lorsque la pompe fonctionne a La pompe doit fonctionner pendant au moins une seconde avant que l alarme ne sonne b S assurer que l alarme n est pas en mode silencieux Appuyer et...

Page 24: ...orsque le flotteur l est aussi L alarme est retardée afin de réduire les nuisances sonores Le voyant jaune alarme désactivée indique que l alarme est actuellement en mode silencieux DÉTECTEURS DE MONOXYDE DE CARBONE Que vous ayez une pompe de secours Basement Sentry ou d une marque concurrente toutes les batteries produisent des sous produits gazeux lorsqu elles sont en charge Certains de ces sous...

Reviews: