background image

© 2014 UTC Fire & Security. All rights reserved. 

1 / 4 

P/N 501-1786ZE-1-08 • REV 08 • ISS 30JAN14  

 

ZP755W-2R Addressable Weatherproof Sounder 

Installation Sheet 

 

Description 

The ZP755W-2R is an addressable, weatherproof sounder, 

designed for use on Ziton addressable fire detection and alarm 

systems. The sounder is rated for outdoor, wet applications. It 

provides audible warnings from a single, addressable, loop-

wired unit. 
The device includes a volume control, an address-setting 

switch, programmable tone settings, and a pair of jumpers to 

select the operating power — from the analogue addressable 

loop or an external supply. 

Installation 

To install the device follow these general steps. 
1.  Wire the PCB. 

2.  Set the operating power. 

3.  Set the address. 

4.  Set the operating mode. 

5.  Set the tone. 

6.  Set the volume. 

7.  Mount the sounder. 
The details of each step are given below. 

Wiring the PCB 

Connect the loop wiring and the optional external power cables 

to the terminals on the PCB as shown Figure 1.

 

Figure 1: Connecting the wiring 

3072-01

3072-01

24 VOLTS

0 VOLTS

SCREEN

(+VE LOOP)

(_VE LOOP)

1

1

2

3

4

5

 

1.  PCB 

2.  Six-way terminal connector 

3.  Header socket 

4.  Connect to sounder 

5.   External power 

Setting the operating power 

The sounder includes a pair of power selection jumpers, J1 

and J2. To select the source of the sounder operating power, 

position the jumpers as shown in Figure 2. 

Figure 2: Power selection jumper configuration 

J1

J1

J2

J2

2

1

 

1.  Loop powered 

 

2.  External 24 VDC 

Note: 

When using an external power supply, use only one that 

is CE and EN 54-4 compliant to power all the sounders on the 

same loop. 

Setting the address 

The sounder includes a seven-segment DIP switch (SW1) for 

assigning device addresses. Each switch segment has a 

decimal value as shown in Figure 3. The address is the sum of 

all the switch segments in the ON position. The switch is used 

to set the device address in binary code. The switch may be 

set to represent any address from 1 to 127. 
For example, to select a device address of 007, set SW1-1, 

SW1-2, and SW1-3 to the ON position and the remaining 

switch segments to the OFF position. 