background image

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5-Button Capacitive Touch Panel  

with Upper Graphic Display 

 

 

 

 

 

 

U

SE

R M

AN

U

AL

 

 

 

 

ZVI-SQTMDD

 

 

Application Program Version: [1.0]  

User Manual Version: [1.0]_a 

 

 

www.zennio.com

 

 

 
 
 

 

Summary of Contents for ZVI-SQTMDD

Page 1: ...5 Button Capacitive Touch Panel with Upper Graphic Display USER MANUAL ZVI SQTMDD Application Program Version 1 0 User Manual Version 1 0 _a www zennio com...

Page 2: ...lt Configuration 9 2 2 General 11 2 2 1 CONFIGURATION 11 2 2 2 Temperature Sensor 13 2 2 3 Screensaver 13 2 2 4 LEDs Display 14 2 2 4 1 LED Brightness Levels 15 2 2 4 2 Display 17 2 2 5 Sounds 17 2 2...

Page 3: ...nnioenglish zendesk com 3 2 3 3 Pair 32 2 3 4 Individual 51 2 4 Display 64 2 4 1 CONFIGURATION 64 2 4 2 Disabled 67 2 4 3 Single 67 2 4 4 Double 80 2 4 5 Borders 81 2 5 Inputs 83 2 6 Thermostat 84 ANN...

Page 4: ...in ZAS and Roll ZAS from Zennio Square TMD Display is a fully customisable solution for the room control including hotel rooms offices or any other environment where the user needs to control climate...

Page 5: ...g function Welcome greeting on the display and Welcome Back object binary or scene Central touch area with a customisable object sending when pressed Screensaver function Up to 5 switchable languages...

Page 6: ...air button functions numeric counter light dimmer shutter controller temperature setpoint etc Individual button functions binary switch hold release scenes light dimmer shutter controller numeric cons...

Page 7: ...the KNX terminal are connected the device can be easily mounted on the metallic plate by the action of the built in magnets After that it is necessary to slide it downwards to fix it through the secu...

Page 8: ...te whenever the device recovers the bus power an immediate self calibration process of the touch panel takes place Please ensure to avoid touching the front glass while powering the device If undesire...

Page 9: ...quare TMD Display features two opto coupled inputs each of which may be independently configured as switches sensors push buttons temperature probes or motion detectors so that external accessories ca...

Page 10: ...rmostat or the external inputs See section 2 2 for details Buttons contains the parameters involved in the configuration of the touch buttons of the device See section 2 3 for details Display contains...

Page 11: ...2 3 for details Display read only parameter to make it evident that the Display tab is always enabled in the tab tree on the left See section 2 4 for details Inputs enables or disables the Inputs tab...

Page 12: ...for details Sounds sets whether the sound functions button beeps alarm and doorbell should work according to the pre defined configuration Default or to a user defined configuration Custom See section...

Page 13: ...creensaver to only show the current Time the current Temperature selecting the desired measurement source the internal temperature sensor or an external value or both alternating every 5 seconds Notes...

Page 14: ...hile the screensaver is active should cause the execution of the button action apart from hiding the screensaver Figure 6 General Screensaver 2 2 4 LEDs DISPLAY As anticipated in section 2 2 the integ...

Page 15: ...ect to change the display contrast in real time ETS PARAMETERISATION Figure 7 General LEDs Display configuration After selecting Custom for LEDs and Display config see section 2 2 1 a new tab will be...

Page 16: ...mode some more options can be configured Control object 1 bit when marked it will be possible to switch the mode by writing to a binary object General LEDs Disp Brightness Mode A specific drop down l...

Page 17: ...configure the Square TMD Display so that a brief beep is emitted as an acoustic feedback in the following cases When a button is pressed short beep indicating that the user has pressed a button This...

Page 18: ...sound matches the requirements of the installation and the doorbell and alarm functions are not necessary the Sounds parameter in the general Configuration tab see section 2 2 1 can be set to Default...

Page 19: ...ic object General Sounds Doorbell will be included into the project topology The value that will trigger the sound 1 or 0 must be set in Value Object for alarm bell enables or disables the alarm funct...

Page 20: ...rs may prefer to hide these texts to have simpler parameter screens Hide INFO parameters displays or hides the INFO textboxes on the top of the parameter screen of each control These textboxes have no...

Page 21: ...the language codes ETS PARAMETERISATION After enabling Translations in the Advanced configuration screen see section 2 2 6 a new tab will be incorporated into the tree on the left Figure 13 General Tr...

Page 22: ...ded for this purpose It can also be done through scene values While locked user presses on the touch buttons will be ignored no actions will be performed and no LEDs will change their states when the...

Page 23: ...n These values are to be received through the general General Scene Receive object Indication comprises a parameter to select how to show the lock status How to show lock status Sets whether to displa...

Page 24: ...to exit cleaning status timeout to deactivate the cleaning function once triggered Range from 5 to 65535 seconds 15 by default How to show cleaning status sets whether to show a message during the cle...

Page 25: ...4 byte objects that define the text lines receives a new value from the bus It is also possible to make the button LEDs flash during the welcome state ETS PARAMETERISATION After enabling Welcome greet...

Page 26: ...esses a touch button after a significant amount of time since the last press Sending it or not can also depend on an additional configurable condition consisting in the evaluation of up to five binary...

Page 27: ...e 0 Do not send unless all additional conditions are 1 the welcome back object will only be sent if all the condition objects are found to have the value 1 Do not send unless at least one of the addit...

Page 28: ...chnical Support http zennioenglish zendesk com 28 function is triggered and the condition if any evaluates to true The desired scene number 1 through 64 should to be entered in Value Figure 21 General...

Page 29: ...being possible to combine any two of them within one pair All the buttons are identical this brings a high level of versatility for a wide variety of applications The following is a list of the funct...

Page 30: ...tab for the parameterisation of the buttons is shown in ETS by default initially containing only a sub tab named Configuration One drop down list with the following options is shown per button 1 to 5...

Page 31: ...viour of the LED or LEDs Figure 23 Buttons Configuration Advanced options Finally if at least one two button control is being configured either Pair A or Pair B an additional parameter Action of the p...

Page 32: ...s permits sending specific binary values both after a short or a long press on any of the two buttons i e they will work as a joint control for independent buttons please configure them as individual...

Page 33: ...in motion and such function is available Hold Release as soon as the button is held the device will send the KNX bus an order to start moving the shutter upwards or downwards depending on the button O...

Page 34: ...mination Modes for details Climate Temperature setpoint permits controlling the temperature setpoint of an external thermostat by means of a button pair and the display This function can also be linke...

Page 35: ...pendent from the fan control object or alternatively consist in the speed level 0 In the latter case one 0 will trigger the Auto mode The three control types available are 1 bit decrease increase one...

Page 36: ...lue on the display Under a state dependent LED illumination the LED of the corresponding button will remain on off according to the current state of the fan On the other hand under a state dependent b...

Page 37: ...ed for the name of the communication objects as X depends on the button pair A B Switch Figure 25 Pair Buttons Switch Action assigns each of the two buttons the value to be sent through Btn PX Switch...

Page 38: ...trol All Buttons see 2 1 Two Objects short Press long press Figure 27 Pair Buttons Two Objects Short Press Long Press Long press threshold time sets the minimum time the user should hold the button in...

Page 39: ...wever selecting State dependent or State dependent both LEDs brings an additional parameter State Object to make the state of the LEDs correspond either to object Btn PX Two switches Short press Short...

Page 40: ...rmed progressively and since Square TMD Display sends an order to interrupt the step dimming once the user releases the button it is advisable to configure a step of 100 This way the user can perform...

Page 41: ...nces between them have been explained in previous pages Action assigns each of the two buttons the order to be sent Left Down Right Up Left Up Right Down Note this parameter will remain hidden unless...

Page 42: ...the increase or decrease buttons respectively i e the smaller the increment the more presses will be required The available range is 0 100 Increment on Long Press sets the increase or decrease to be...

Page 43: ...nless having selected Every button pair is configured separately in Action of the pair buttons see 2 3 1 Size sets the desired size of the object 1 byte or 2 bytes Signed checkbox to set whether the o...

Page 44: ...ls LED illumination control analogous to the homonymous parameter for the previous functions see above In this case the only options are Regular and Dedicated Object The counter values will be sent to...

Page 45: ...uttons Float Action assigns each of the two buttons the order to be sent Left Decrease Right Increase Left Increase Right Decrease Note this parameter will remain hidden unless having selected Every b...

Page 46: ...ange is 0 1 670760 93750 1 by default Link the control with a box in the display sets the area of the display where to show the indicator of this control i e the current numeric value The selected box...

Page 47: ...ust be configured with the same data type see section 2 4 for details LED illumination control analogous to the homonymous parameter for the previous functions see above In this case the only options...

Page 48: ...de Type Extended Link the control with a box in the display sets the area of the display where to show the indicator of this control i e the current numeric value The selected box must be configured w...

Page 49: ...s whether scrolling through the speed levels is circular or not If checked an increase order in the maximum level switches to the minimum and vice versa in the minimum level a decrease order switches...

Page 50: ...ximum Auto Mode By long press on any of the buttons of the control requires checking Long Press to Activate Auto Mode A further long press deactivates back the Auto mode and resumes the previous fan l...

Page 51: ...Dedicated Object 2 3 4 INDIVIDUAL Buttons configured to work as individual separate controls can be assigned any of the following control functions from the corresponding Button IX tab LED indicator u...

Page 52: ...mode is not available for this function Scaling Constant sends a percentage value configurable to the bus when the user touches the button Under a state dependent LED illumination the LED will remain...

Page 53: ...off according to the status object On the other hand a switch off order will be sent if it is found to be on value greater than 0 Note that the device considers that the current light level is the val...

Page 54: ...will be sent if the last short press caused a step up order or if the current position is found to be 0 As usual in the KNX standard stop step orders are interpreted by the actuators as a request to...

Page 55: ...state dependent LED illumination mode is not available for this function Enumeration implements a one button enumeration control that sends one byte unsigned values to the KNX bus This control is com...

Page 56: ...hutter and Enumeration Depending on the function some more parameters are involved as described next Please note that in the next pages In is used as a general notation for the communication objects w...

Page 57: ...case are Regular State dependent and Dedicated object Hold Release Figure 44 Individual Button Hold Release Action on Hold sets the value to be sent to the bus through Btn In Hold Release when the use...

Page 58: ...byte value In case of selecting the latter an additional parameter Value will be displayed to enter the desired one byte value 0 255 Action on Long press sets the value to be sent to the bus through B...

Page 59: ...ination control analogous to the homonymous parameter for all the above functions see previous pages The options in this case are Regular and Dedicated object Scaling Constant Counter Constant Float C...

Page 60: ...mer Figure 48 Individual Button Dimmer The alternating switch orders will be sent through the Btn In Light On Off one bit object while the alternating increase decrease stop orders will be through the...

Page 61: ...dividual Button Shutter The alternating move up down orders will be sent through the Btn In Shutter Move one bit object while the alternating step up down orders will be through the Btn In Shutter Sto...

Page 62: ...l be distinguished For every distinguished state one parameter Value j will become available in order to set the value sent through the communication object Value j numerical value 0 255 that will be...

Page 63: ...r Send 0 or 1 According to the State Object the direction of the fan control will be upwards or downwards depending on the current state as explained below The first option makes sense when the fan ac...

Page 64: ...ent font sizes for the alphanumeric characters are available Small Big and Extra this one only for numeric characters As Square TMD Display offers the user a sole control page instead of alternating b...

Page 65: ...shown in ETS by default While all the zones remain disabled it will only contain a sub tab named Configuration Figure 53 Display Configuration One drop down list is shown per zone The options under i...

Page 66: ...box border line see section 2 4 5 Indicator representation defines the representation of the indicators on the display The available options are All indicators are type permanent Every indicator is co...

Page 67: ...te and another one represents the Off state Enumeration up to six different states can be represented through one icon each Number the indicator will represent a number received through the associated...

Page 68: ...cation object There are two Mode Types Heat Cool only the Heat and Cool modes will be represented according to the value of a one bit object Extended up to five HVAC climate modes will be represented...

Page 69: ...ers that need to be configured are Label sets the box name see section 2 4 Indicator sets the desired indicator to display in the box Icon Number Text Time of day Text from object Climate Temperature...

Page 70: ...nfigured Select icon for 0 1 sets the icon to display for each value Representation sets the icon representation The options are Permanent Temporary Intermittent and Progressive Note this parameter wi...

Page 71: ...hen the above value is received Representation sets the icon representation The options are Permanent Temporary Intermittent and Progressive Note this parameter will remain hidden unless having select...

Page 72: ...three characters are possible Note this parameter is not available for Scaling as the suffix is always Suffix font size sets the font size of the above suffix The options are Small and Big Note this...

Page 73: ...lecting this type the following parameters need to be configured Value 0 1 Text sets the text to be displayed for each value Maximum 12 characters allowed Representation sets the text representation T...

Page 74: ...eived Representation sets the text representation The options are Permanent Temporary Intermittent and Progressive Note this parameter will remain hidden unless having selected Every indicator is conf...

Page 75: ...rary Intermittent and Progressive Note this parameter will remain hidden unless having selected Every indicator is configured separately in Indicator representation see 2 4 1 Object to show hide indic...

Page 76: ...l remain hidden unless having selected Enable the option in every box in Object to show hide the indicator see 2 4 Climate Temperature Figure 63 Display indicator Climate Temperature The temperature n...

Page 77: ...hether only the Heat and Cool modes should be represented Heat Cool or up to five HVAC modes Extended Heat Cool the icon Heat or Cool will depend on the value of the Disp x Climate Mode one bit object...

Page 78: ...cator Climate Fan The value should be updated through the Disp x Fan one byte communication object Off Auto 0 defines whether the Off Auto level is required to be represented or not If enabled the fol...

Page 79: ...s parameter will remain hidden unless having selected Enable the option in every box in Object to show hide the indicator see 2 4 1 Climate On Off Mode Status Figure 67 Display indicator Climate On Of...

Page 80: ...tion in every box in Object to show hide the indicator see 2 4 2 4 4 DOUBLE Double boxes have a size of 32 x 32 pixels so the display can be divided into up to 8 double boxes two per zone Double boxes...

Page 81: ...parate for each as shown in Figure 69 Figure 69 Borders Different configuration for each border ETS PARAMETERISATION After selecting Customize every border in the Border lines parameter see section 2...

Page 82: ...Technical Support http zennioenglish zendesk com 82 Lower lines vertical configures the lower vertical lines c1 c2 c2 d1 and d1 d2 The options available for all the lines are Solid line Invisible and...

Page 83: ...pabilities only motion detection Therefore the two models mentioned offer equivalent functionality when connected to this device The two models mentioned incorporate a voltage selection microswitch on...

Page 84: ...e TMD Display implements one Zennio thermostat which can be enabled and fully customised Please refer to the specific manual Zennio Thermostat for Square TMD Display available at the Zennio homepage w...

Page 85: ...another and is detailed for each function State Dependent Illumination both LEDs only applies to buttons configured as pair controls The two LEDs of the control will light or not depending on the valu...

Page 86: ...Dimmer Shutter Scaling Counter Enumeration Float Climate Temperature Climate Mode Climate Fan INDIVIDUAL Disabled Binary Hold Rel Two Objects Scene Constants Dimmer Shutter Enumeration DISABLED Table...

Page 87: ...t One binary communication object per control will be included in the project topology so that the LED of every control turns on off depending on its own object ETS PARAMETERISATION For details on the...

Page 88: ...alue and therefore can be assumed to maintain their previous value after the failure or with the corresponding updated value in case they depend on external elements sensors etc Moreover if the object...

Page 89: ...thing 1 Bit I C W DPT_Trigger 0 1 General Sounds Doorbell 0 Play a doorbell sound 1 Nothing 24 1 Bit I C W DPT_Alarm 0 1 General Sounds Alarm 1 Play alarm intermittent sounds 0 Stop alarm sounds 1 Bit...

Page 90: ...nt 32768 32767 Btn In Counter 2 bytes signed Send selected value on short press 2 Byte I C T W 9 xxx 671088 64 670760 96 Btn In Float Send selected value on short press 1 Byte I C T W DPT_Value_1_Ucou...

Page 91: ...nt 0 255 Btn In Fan control enumerated 0 1 2 3 4 5 1 Byte I C T W DPT_Value_1_Ucount 0 255 Btn In Fan control enumerated 1 2 3 4 5 35 41 47 53 59 1 Byte I C T W DPT_Value_1_Ucount 0 255 Btn In Two swi...

Page 92: ...Increase percentage Right Decrease percent 1 Byte I C T W DPT_Value_1_Ucount 0 255 Btn Px Counter 1 byte unsigned Left Decrease Right Increase 1 Byte I C T W DPT_Value_1_Ucount 0 255 Btn Px Counter 1...

Page 93: ...an control scaling Auto 20 40 60 80 100 1 Byte I C T W DPT_Value_1_Ucount 0 3 Btn Px Fan control enumerated 0 1 2 3 1 Byte I C T W DPT_Value_1_Ucount 1 3 Btn Px Fan control enumerated 1 2 3 1 Byte I C...

Page 94: ...255 Disp X Text Enumeration Parameterized text shown on new value reception 1 Byte I C W DPT_HVACContrMode 0 Auto 1 Heat 3 Cool 9 Fan 14 Dry Disp X Climate Mode Extended Mode icon is shown 1 Byte I C...

Page 95: ...9_1 Disp X Text from object Received text is shown 14 Byte I C W DPT_String_8859_1 Disp X1 Text from object Received text is shown 90 106 122 138 1 Bit I C W DPT_Heat_Cool 0 1 Disp X Climate On Off Mo...

Page 96: ...ue is shown 99 C to 199 C 96 112 128 144 4 Byte I C W DPT_Value_4_Ucount 2147483648 2147483647 Disp X2 Number Counter 4 bytes unsigned Object numeric value is shown 97 113 129 145 14 Byte I C W DPT_St...

Page 97: ...Setpoint Status Current Basic Setpoint 165 2 Byte O C T R DPT_Value_Tempd 670760 0 670760 0 T1 Setpoint Offset Status Current Setpoint Offset 166 1 Bit I C W DPT_Reset 0 1 T1 Setpoint Reset Reset Set...

Page 98: ...Error 0 No Error 1 Short Circuit Error 195 219 1 Byte O C T R DPT_Scaling 0 100 Ix Presence State Scaling 0 100 196 220 1 Byte O C T R DPT_HVACMode 1 Comfort 2 Standby 3 Economy 4 Building Protection...

Page 99: ...Ix C3 Detection State Binary Binary Value 214 238 1 Bit I C W DPT_Switch 0 1 Ix C3 Channel Lock According to parameters 215 239 1 Bit I C W DPT_Switch 0 1 Ix C3 Force State 0 No Detection 1 Detection...

Page 100: ...Byte C T DPT_Value_2_Ucount 0 65535 W W Ix Short Press Constant Value Integer 0 65535 2 Byte C T 9 xxx 671088 64 670760 96 W W Ix Short Press Constant Value float Float value 242 248 1 Byte I C W DPT...

Page 101: ...0 63 128 191 W W Ix Long Press Run Scene Sending of 0 63 1 Byte C T DPT_SceneControl 0 63 128 191 W W Ix Long Press Save Scene Sending of 128 191 1 Bit C T DPT_Alarm 0 1 W W Ix Switch Sensor Alarm Bre...

Page 102: ...your inquiries about Zennio devices http zennioenglish zendesk com Zennio Avance y Tecnolog a S L C R o Jarama 132 Nave P 8 11 45007 Toledo Spain Tel 34 925 232 002 Fax 34 925 337 310 www zennio com...