P84577 G 

Sheet 1 of 14

 

 

273 Branchport Avenue 
Long 

Branch, 

N.J. 

 

07740          

 

 

 

 

Thank you for using our products.

 

(800)  631-2148 
www.wheelockinc.com

 

         INSTALLATION 

INSTRUCTIONS 

ADDRESSABLE PAGING SPLITTER 

  (FOR SP40/2, SPB-160, SPB-80/4, and SPB-320) 

 

Use this product according to this instruction manual.  Please keep this instruction manual for future reference. 

 

MODEL NUMBER: 

        109920 

 

SP4-APS 

 

 

1.0

 

GENERAL: 

 

The Addressable Paging Splitter module (SP4-APS) is designed to be used with Wheelock’s SP40/2 SAFEPATH4 panel and 
the SP4-TZC Zone Controller. The SP4-APS can also be mounted in SAFEPATH4 Audio Booster (SPB-160, SPB-80/4, and 
SPB-320) panels.  The SP4-APS provides a means for expanding one supervised audio output zone to four Class B or two 
Class A supervised zones.  The SP4-APS also provides two expansion outputs that can be used to add additional audio 
booster modules in Class A or B configuration. 

The SP4-APS is UL Listed under Standard 864, 

Control Units for Fire 

Protective Signaling Systems.  It is for indoor use only.   

 

One SP4-APS can be mounted inside the SP40/2 panel. The use of the Splitter Mounting Bracket (SPMB4Z) is required 
when mounting the SP4-APS splitter(s) inside the Audio Booster panels. 

 

The Addressable Paging Splitter  module (SP4-APS) is also used to expand and distribute supervised telephone paging and 
background music to selected zones when the SAFEPATH4 system is not in the alarm condition. When the SAFEPATH4 
system is in the alarm condition all telephone paging and background music inputs are silenced and the emergency message 
is broadcast on all zones. The SP4-APS is used with the Telephone Zone Controller (SP4-TZC) and controls the distribution 
of the telephone paging and background music functions. 

 

NOTE:

  Use of the Telephone Zone Controller (SP4-TZC) is supplementary. 

 

The SP4-APS contains 16 LED indicators used to monitor and troubleshoot the module.

 

 

Refer to the Installation Instructions for the Telephone Zone Controller (SP4-TZC) P84567 when connecting the SP4-APS 
modules for telephone paging and background music operation. 

 

NOTE:

  All 

CAUTIONS

 and 

WARNINGS

 are identified by the symbol 

.  All warnings are printed in bold capital 

letters. 

 

WARNING:  PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE USING THIS PRODUCT.  

FAILURE TO COMPLY WITH ANY OF THE FOLLOWING INSTRUCTIONS, CAUTIONS AND WARNINGS 
COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION OF THESE 
PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE AND 
SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. 

 

2.0

 

SPECIFICATIONS: 

 

The SP4-APS has a maximum power output per zone that cannot exceed what is listed in Table 1. 

 

Table 1:  SP4-APS Specifications

 

Rated 

Voltage 

Rated 

Current 

Audio Input 

Voltage 

Max Power 

Per Zone 

25VRMS 40W 

24VDC 0.120A 

70.7VRMS 40W 

 
The total audio power output from all zones on the SP4-APS cannot exceed the audio input power. 

 

Copyright 2005 Wheelock, Inc.  All rights reserved. 

Содержание SP4-APS

Страница 1: ...SAFEPATH4 system is not in the alarm condition When the SAFEPATH4 system is in the alarm condition all telephone paging and background music inputs are silenced and the emergency message is broadcast on all zones The SP4 APS is used with the Telephone Zone Controller SP4 TZC and controls the distribution of the telephone paging and background music functions NOTE Use of the Telephone Zone Controll...

Страница 2: ...an be configured for either CLASS A or CLASS B It cannot do both at the same time The maximum audio power output on any zone is 40 watts Expansion EX1 EX2 terminals follow the Class A or B setting that applies to all zones Instead of speakers up to four SPB 160 or SPB 80 4 or two SPB 320 Audio Boosters may be connected to an audio output zone provided that nothing else is on that zone The total nu...

Страница 3: ...LASS B Note that end of line resistors UL Listed 10K Ohm EOLR are required at the end of each audio output zone even if no speakers are present on a zone End of line resistors are required on the EX1 and EX2 connections whether they are used or not Figure 4 shows the SP4 APS set for CLASS B audio field wiring The audio zone outputs are either 25Vrms or 70 7Vrms matching the audio input voltage Rem...

Страница 4: ...setting If SW2 is set for CLASS A then all zone outputs and expansion outputs must be wired for CLASS A When using the SP4 APS in CLASS B configuration end of line resistors UL Listed 10K Ohm EOLR must be used at the end of each expansion circuit 3 2 2 24VDC Wiring The SP4 APS requires 24VDC input in order to operate Wire the 24VDC from 24VDC connections on the SP40 2 or the DC OUT connections on ...

Страница 5: ...CTING ALL POWER SOURCES TO THIS UNIT FIRST FAILURE TO DO SO MAY RESULT IN DAMAGE TO THE PC BOARDS DISCONNECTING FIRST DISCONNECT BATTERY POWERAT BATTERY TERMINALS THEN DISCONNECTAC POWERAT THE POWER SOURCE RECONNECTING FIRST RECONNECTAC POWERAT THE POWER SOURCE THEN RECONNECT BATTERY POWERAT THE BATTERY TERMINALS WARNING BGM VOLUME SP4 APS MOUNTING STUDS SP40 2 BACKPLANE MOUNTING STUDS COVER STAND...

Страница 6: ...W4 J2 W7 W8 P84014 REV ZONES OUT TO SPEAKERS OR UP TO FOUR SPB 160 S OR SPB 80 4 S OR TWO SPB 320 S PER ZONE Power Limited SW1 CC 10K OHM EOLR EXPANSION OUT TO AUDIO BOOSTERS Power Limited CC ALARM INPUT Power Limited 24VDC Power Limited AUDIO Power Limited N L 120VAC INPUT Non Power Limited RUN POWER LIMITED WIRING AWAY FROM NON POWER LIMITED WIRING USING THE KNOCKOUTS ON THE RIGHT SIDE OF THE PA...

Страница 7: ...hows the mounting location of the SP4 APS Splitter to the Splitter Mounting Bracket SPMB4Z PS PS TB1 N L ADDRESSABLE PAGING SPLITTER SP4 APS SPLITTER MOUNTING BRACKET SPMB4Z 24VDC POWER SUPPLY ZO N E ZO NE IN EX1 EX2 IN OUT ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 1 ZONE 2 CLASS B WIRING CLASSA WIRING 24 VDC AUDIO ALARM RS 485 TROUBLE POWER IN OUT IN OUT Z2 Z1 Z3 Z4 IN EX1 EX2 IN OUT ZONE 1 ZONE 2 ZONE 3 ...

Страница 8: ...above the top and down the right side of the splitter module s EX1 and EX2 are not used when the SP4 APS is connected to an Audio Booster Terminate as follows CLASS A Jumper to and to CLASS B UL Listed 10K Ohm EOLR across each EX zone OUT IN OUT IN OUT IN 24 VDC AUDIO RS 485 ALARM POWER TROUBLE Z1 Z2 Z3 Z4 EX1 EX2 IN CLASS B A SW2 SP4 APS JP1 NAC CC SW1 TB1 TB2 TB7 TB6 TB5 TB4 TB3 JP1 Shorted 70Vr...

Страница 9: ... AUD IN J4 J5 AUD2 OPEN AUD2 SHORT D30 D29 TRANSFORMER 25 70 25 70 25 70 25 70 AUDIO INPUT POWER LIMITED AUDIO RETURN POWER LIMITED Battery 1 Battery 2 Battery 4 Battery 3 120VAC INPUT NON POWER LIMITED BATTERY LEADS NON POWER LIMITED PLACE WIRE RUN AT LEAST 1 4 ABOVE THE TOP OF THE CIRCUIT BOARD AND AT LEAST 1 4 FROM POWER LIMITED WIRING 1 ALARM ZONE OUTPUTS AND RS485 POWER LIMITED IN EX1 EX2 IN ...

Страница 10: ...30 D29 TRANSFORMER 25 70 25 70 25 70 25 70 Audio Zones Out POWER SUPPLY SW1 NAC EX1 and EX2 are not used when the SP4 APS is connected to an Audio Booster Terminate as follows CLASS A Jumper to and to CLASS B 10K Ohm EOLR across each EX zone 10K Ohm EOLR OUT IN OUT IN OUT IN 24 VDC AUDIO RS 485 ALARM POWER TROUBLE Z1 Z2 Z3 Z4 EX1 EX2 IN CLASS B A SW2 SP4 APS JP1 NAC CC SW1 TB1 TB2 TB7 TB6 TB5 TB4 ...

Страница 11: ...P4 Telzone Programmer software See the SP4 TZC installation sheet P84567 for further information 6 1 3 TELEPHONE PAGING MODE Paging Mode occurs when telephone paging commands are sent from the SP4 TZC to the SP4 APS Splitter s via RS 485 digital control signals See Figure 13 for location See the SP4 TZC installation sheet P84567 for further information on the RS485 connections When the addressed S...

Страница 12: ...O TROUBLE LEDS NETWORK TROUBLE LEDS RS 485 IN TRB RS 485 OUT TRB GENERAL TROUBLE LED POWER LED Figure 15 SP4 APS Power and Trouble LED Indicators Figure 15 shows the Power and Trouble LED indicators on the SP4 APS PC board 1 Ensure that the green POWER LED is ON If no LED s are lighted check the 24VDC input power 2 Verify that SW1 NAC CC switch is set to the desired position 3 Verify the SW2 CLASS...

Страница 13: ...nt SP4 APS s Subsequent SP4 APS s will have the RS485 IN LED ON RS485 OUT Open X RS485 OUT wiring open No communication to subsequent SP4 APS s Subsequent SP4 APS s will have the RS485 IN LED ON 24VDC Wiring Disconnected X All LED indicator will be OFF See Note 2 Ground Fault on any terminal except RS485 X No indication on SP4 APS Trouble LED and Ground Fault LED indicators will light on the SP40 ...

Страница 14: ...R SPECIFICATION ABUSE ACCIDENT OR OTHER OPERATING CONDITIONS BEYOND WHEELOCK S CONTROL SOME WHEELOCK PRODUCTS CONTAIN SOFTWARE WITH RESPECT TO THOSE PRODUCTS WHEELOCK DOES NOT WARRANTY THAT THE OPERATION OF THE SOFTWARE WILL BE UNINTERRUPTED OR ERROR FREE OR THAT THE SOFTWARE WILL MEET ANY OTHER STANDARD OF PERFORMANCE OR THAT THE FUNCTIONS OR PERFORMANCE OF THE SOFTWARE WILL MEET THE USER S REQUI...

Отзывы: