background image

Vertiv Liebert® EDGE

Installer/User Guide

Summary of Contents for EDGE-1000IMT

Page 1: ...Vertiv Liebert EDGE Installer User Guide...

Page 2: ...r damages resulting from use of this information or for any errors or omissions Refer to other local practices or building codes as applicable for the correct methods tools and materials to be used in...

Page 3: ...External Battery Cabinet Connection on 2U and 3U VRLA Models Optional 12 3 9 Network Communication Card Connection Optional 13 3 9 1 Connecting AC Input 13 4 Operations 15 4 1 Modes of Operation 15 4...

Page 4: ...ttings 35 4 3 1 Changing the Password 36 5 Maintenance and Battery Replacement 39 5 1 Precautions 39 5 2 Battery Charging 39 5 3 Replacing the UPS Batteries 39 6 Specifications 43 6 1 Battery Run Time...

Page 5: ...the installation and maintenance of the UPS and batteries Read this manual thoroughly and the safety and regulatory information available at https www vertiv com ComplianceRegulatoryInfo before attem...

Page 6: ...1 Important Safety Instructions 2 This page intentionally left blank Liebert EDGEInstaller User Guide...

Page 7: ...twork Communication Card makes advanced monitoring and control available 2 1 Available Models BATTERY TYPE MODEL FROM FACTOR MODEL NUMBER NOMINAL POWER RATING 230 V INPUT VRLA Valve Regulated Lead Aci...

Page 8: ...breaker 6 Non programmable receptacles 2 AC input 7 EmergencyPower Off EPO connector 3 USB communication port 8 Output circuit breakers 4 IntelliSlot port 9 Ground Screw 5 Programmable receptacles 10...

Page 9: ...rols Figure 2 2 Controls and Display ITEM DESCRIPTION 1 ESC MUTEbutton SeeControls for details 2 DOWN LEFT button SeeControls for details 3 UP RIGHT button See Controls for details 4 ENTER button See...

Page 10: ...2 EDGE Description 6 This page intentionally left blank Liebert EDGEInstaller User Guide...

Page 11: ...ko to IEC C13 Input power cable BS1362 to IEC C13 Input power cable AUS to IEC C13 Input power cables 2200 3000VA models Input power cable IEC Schuko to IEC C19 Input power cable BS1362 to IEC C19 Inp...

Page 12: ...l NFPA 75 NOTE Operating the UPS in temperatures above 25 C reduces battery life 3 3 2 Installation Clearances Maintain at least 100 mm clearance in the front and rear Do not obstruct the air inlets o...

Page 13: ...attery ITEM DESCRIPTION 1 Connect the two halves of the stand to the spacer after installing the additionalstand components shown in item 4 and installthe securing screws 2 Place the UPS and externalb...

Page 14: ...the front member of the railto the front of the rack and secure the two bottom holes to the rack with two railkit screws Tighten allscrews Repeat for the second rail 3 Place the UPS with assembled rac...

Page 15: ...hutdown of your computer in case of a power failure can be done using the Vertiv Power Assist software via the USB port Visit www vertiv com powerassist for additional information 3 7 Emergency Power...

Page 16: ...UPS and one end to the battery cabinet as shown in Figure 3 4 below 2 If connecting more than one external battery connect one end of the external battery cable to the second connector on the battery...

Page 17: ...at www Vertiv com for cable connection and operation 3 9 1 Connecting AC Input Ensure that all the loads are first powered off Connect to an input power supply wall outlet that is properly protected...

Page 18: ...3 Installation 14 This page intentionally left blank Liebert EDGEInstaller User Guide...

Page 19: ...batteries are charging 4 1 5 On Automatic Voltage Regulation AVR Buck Mode The UPS input is plugged in but the voltage source is abnormally high The UPS automatically corrects the high voltage and all...

Page 20: ...s this button to select the upper or right item in the menu previous page in the screen or increase the number in setting 4 ENTER Enter Press this button to enter the main menu from the flow screen or...

Page 21: ...ton to select the highlighted setting c Use the arrow buttons to alternate between setting options d Press the Enter button to select the setting option or press the ESC button to cancel 3 To navigate...

Page 22: ...ver if there is no active alarm or user interaction for two minutes After 5 minutes the screen will turn off Any button press will wake it If an alarm or fault occurs or if any button is pressed the U...

Page 23: ...ns to move the cursor left right and select a tab then press Enter to display the status information for the selected tab 3 Use the the arrow keys to move the cursor through status information for the...

Page 24: ...ining capacity Percent of capacity remaining for battery Discharge count Number of discharges for the battery module Total discharge time Min Number of minutes until battery is fully discharged Batter...

Page 25: ...the Settings password Use the arrow buttons to increase the digit or change to the next digit Press Enter when finished The default Settings password is 111111 six ones 3 Use the arrow buttons to move...

Page 26: ...he amp hour rating of the external battery This setting should only be adjusted when using third party external batteries with the External battery cabinets setting set to 0 Amp hours are calculated a...

Page 27: ...lt of 4320 Max Charge current 2U and 3U VRLA models only Sets the maximum charge current for the battery A higher charge current will charge the battery more quickly but can shorten battery life A low...

Page 28: ...he detected orientation of the UPS default Horizontal Screen rotated for rack use Vertical Screen rotated for tower use Audible alarm If enabled the UPS will beep when an alarm is generated If disable...

Page 29: ...t when power returns after the battery has been fully depleted Disable The UPS cannot start with a fully depleted battery default Remote control Allows the UPS to be controlled remotely via the SNMP c...

Page 30: ...Active close The UPS will activate the EPO function when Pin 1 and Pin 2 are closed shorted 4 Operations 26 Liebert EDGEInstaller User Guide...

Page 31: ...When this option is enabled the programmable outlet will turn off if the UPS is overloaded while in battery mode Enable Disable default Settings based on discharge time Controls outlets based on amoun...

Page 32: ...ct the checkbox to enable or disable default the option 0 30 minutes default of 0 Settings based on capacity Control outlets based on battery capacity remaining Threshold of turning off the outlet Whe...

Page 33: ...ry manual test Starts the battery self test manually If the manual self test is already running stop the self test Clear faults Clears displayed faults after the issue causing the fault is resolved Re...

Page 34: ...ccur Battery reversed The battery positive and negative are reversed Reconnect the battery and check the battery cable connections Battery test fail The voltage of the battery was low when the periodi...

Page 35: ...exceed the normalrange or that the mains has power off Input ground lost Check that the PEline is wellconnected and that the alarm can be cleared at the display Input neutrallost The mains input neutr...

Page 36: ...load 100 50 linear derating Remote power on The UPS was powered on remotely This willdisplay in the log whenever the event occurs Remote shut off The UPS was powered on remotely This willdisplay in t...

Page 37: ...ce start up of the UPS UPS FW version Version of UPS firmware on the control board Communication FW version Version of communication firmware on the communication board LCD module FW version Version o...

Page 38: ...arrow buttons to select Yes and press Enter NOTE The operation is password protected The password is 12345 Restore factory default If the operation success it will restore configuration to factory de...

Page 39: ...ears when attempting to change the Settings password but the new and confirmation passwords do not match Operation failed condition is not met Appears when attempting to execute aoperation for which t...

Page 40: ...y from the mains In this mode when the battery is fully charged the fan willturn off for energy saving Buck mode When the input voltage is higher than the voltage regulation range but lower than high...

Page 41: ...unding every 10 seconds Battery low pre warning Sounding every 2 seconds Overload pre warning Sounding every second No battery Sounding every 2 seconds Battery overcharge Sounding every 2 seconds Inpu...

Page 42: ...4 Operations 38 This page intentionally left blank Liebert EDGEInstaller User Guide...

Page 43: ...ime This is an agency tested and certified requirement now eliminating the industry wide safety risk known with previous Li Ion batteries 5 3 Replacing the UPS Batteries IMPORTANT Before you proceed p...

Page 44: ...to the UPS Reinstallthe metalbattery cover 5 Reconnect the battery connectors Snap the front bezelback on To replace the batteries on MT models 1 Place the unit on its left side and remove the 6 screw...

Page 45: ...e the battery cover 3 Slide out the battery kit and disconnect the battery connector 4 Connect the battery connector to the replacement battery 5 Slide the replacement battery kit into the UPS 6 Repla...

Page 46: ...5 Maintenance and Battery Replacement 42 This page intentionally left blank Liebert EDGEInstaller User Guide...

Page 47: ...245 260 272 284 VAC High Line Normalto Buck 220 229 242 253 264 VAC High Line Buck to Normal 215 224 237 248 259 VAC Low Line Boost1 to Normal 185 192 203 212 221 VAC Low Line Normalto Boost1 180 187...

Page 48: ...current short circuit w latching shutdown AC mode Efficiency 98 or greater for 200 208 220 230 240 VAC Buck Boost1 and Boost2 mode 94 or greater for 200 208 220 230 240 VAC 96 or greater for 200 208 2...

Page 49: ...13 2 20 Input Voltage Input Range with battery operation 0 to 300 VAC Voltage Input Range without battery operation 144 to 290 VAC Input Voltage Measurement Tolerance 5 NominalVoltage Setting 200 208...

Page 50: ...on 101 alarm warning 106 alarm warning and shutdown after 60 seconds 126 alarm warning and shutdown after 50 seconds 151 alarm warning and shutdown after 2 seconds 201 alarm warning and immediate shut...

Page 51: ...8A 3000VA 2700W 13 3A Dimensions D W H in mm Unit Dimensions Wx D x H mm 438 x 510 x 86 438 x 630 x 86 438 x 485 x 132 Shipping Dimensions Wx D x H mm 565 x 700 x 240 600 x 800 x 240 550 x 670 x 282 W...

Page 52: ...Battery to Normalcomeback at 60Hz 57 to 63Hz InternalRear panel Input Breaker Rating 10 A 16 A Input Surge Protection EN61000 4 5 Line to Line Level2 Line to Earth Level3 Input Power 624J L N 624J L...

Page 53: ...tion Electronic overcurrent short circuit with latching shutdown Type Valve regulated lead acid VRLA in compliance with UL 1989 Quantity x Voltage x Ah 4 x 12V x 9Ah 6 x 12V x 7Ah 6 x 12V x 10Ah Exter...

Page 54: ...W 13 3A Audible Noise 45 dBA AVR mode 70 load 55 dBA Battery mode Agency Compliance CE CB Report Safety IEC EN62040 1 2008 A1 2013 RFI EMI EN62040 2 2006 C1 Transportation ISTA 2A Table 6 3 Specificat...

Page 55: ...72 284 VAC High Line Normalto Buck 220 229 242 253 264 VAC High Line Buck to Normal 215 224 237 248 259 VAC Low Line Boost1 to Normal 185 192 203 212 221 VAC Low Line Normalto Boost1 180 187 198 207 2...

Page 56: ...latching shutdown AC mode Efficiency 97 5 or greater for 200 208 220 230 240 VAC Buck Boost1 and Boost2 mode 95 or greater for 200 208 220 230 240 VAC Recharge Time 1 7 hours to recover 90 1 7 hours...

Page 57: ...sportation ISTA 2A UN38 3 Lithium ion Table 6 4 Specifications EDGELI 1500IRT2U EDGELI 2200IRT2U EDGELI 3000IRT2U continued 6 1 Battery Run Times LOAD Internal Battery Only VA W Minutes 100 500 450 5...

Page 58: ...0 100 90 88 7 Table 6 6 Battery Run Time in Minutes EDGE 1000IRM1U LOAD Internal Battery Only VA W Minutes 100 1500 1350 5 4 90 1350 1215 6 5 80 1200 1080 7 9 75 1125 1012 5 8 6 70 1050 945 9 6 60 900...

Page 59: ...150 135 47 1 10 75 67 5 92 7 Table 6 8 Battery Run Time in Minutes EDGE 750IMT LOAD Internal Battery Only 10 AH VA W Minutes 100 1000 900 5 4 90 900 810 6 5 80 800 720 7 9 75 750 675 8 7 70 700 630 9...

Page 60: ...3 9 97 4 131 4 165 7 200 2 80 1200 1080 8 8 37 7 74 5 112 7 151 4 190 4 229 5 75 1125 1012 5 9 7 40 7 80 1 120 8 162 0 203 5 245 0 70 1050 945 10 9 45 0 87 9 132 0 176 6 221 5 266 5 60 900 810 13 6 55...

Page 61: ...52 4 1729 7 Table 6 12 Battery Run Time in Minutes EDGE 2200IRT2UXL LOAD INTERNAL BATTERY ONLY NUMBER OF EXTERNAL BATTERY CABINETS 1 2 3 4 5 6 VA W Minutes 100 3000 2700 6 1 19 8 39 9 61 5 83 7 106 2...

Page 62: ...Minutes 100 2200 1980 9 3 90 1980 1782 10 5 80 1760 1584 12 0 70 1540 1386 13 9 60 1320 1188 16 6 50 1100 990 20 2 40 880 792 25 5 30 660 594 34 3 20 440 396 47 1 10 220 198 90 7 Table 6 15 Battery R...

Page 63: ...NTERNAL BATTERY ONLY 40 1200 1080 28 6 30 900 810 38 5 20 600 540 52 4 10 300 270 102 6 Table 6 16 Battery Run Time in Minutes EDGELI 3000IRT2U continued 6 Specifications 59 Liebert EDGEInstaller User...

Page 64: ...6 Specifications 60 This page intentionally left blank Liebert EDGEInstaller User Guide...

Page 65: ...arranty channel emea vertiv com p Toll free 0080011554499 In the Asia Pacific APAC Technical support and warranty e DPG Warranty vertiv com p AU Australia 1300 367 686 opt 1 PH Philippines 620 3655 op...

Page 66: ...Appendices 62 This page intentionally left blank Liebert EDGEInstaller User Guide...

Page 67: ...Liebert EDGEInstaller User Guide...

Page 68: ...gistered trademarks of their respective owners While every precaution has been taken to ensure accuracy and completeness here Vertiv Group Corp assumes no responsibility and disclaims all liability fo...

Reviews: