ENERGY RECOVERY VENTILATOR

Venmar AVS S10 ERV
Part no. 41700

Low speed: 50 CFM (0.2 in. w.g.), selectable 65 CFM
High speed: 100 CFM (0.4 in. w.g.), selectable 85 CFM

VB0198

CONSTRUCTION

•  22 ga. galvanized steel housing and door

•  One-piece molded insulation shell,
  (expanded polystyrene; UL 94 HF-1 certifi ed)

•  Galvanized steel 5" diameter ports*

•  Steel door hinges and latches

•  Cold side ports with plastic ring; allow vapor barrier sealing

•  No drain required

*All units ports were created to be connected to ducts having a 
minimum of 5” diameter, but if need be, they can be connected to 
bigger sized ducts by using an appropriate transition (e.g.: 5” diameter 
to 6” diameter transition).

MOTORS

•  Two high reliability, external rotor PSC motors, totally enclosed and 
 thermally 

protected

•  Backward blowers, can support high static pressure environment

FILTERS

•  Two washable 20 ppi reticulated polyester urethane foam fi lters, 
  UL 900 class 2 certifi ed

•  Optional MERV 7 fi lter kit, part no.: 21030 (additional 0.1 in. w.g. 
  static pressure to be considered) (sold separately)

ERV CORE

• Crossfl ow aluminum-polymerized paper core, UL723 certifi ed

•  Hydroscopic polymer exchange water by direct vapor transfer using 
  molecular transport without the need of condensation

• Constructed of alternate layers of corrugated aluminum material 
  and polymeric bactericide dessiccant impregnated media; will not 
  promote growth of mold or bacteria

•  Unique rectangular fl ute design to provide very low pressure drop 
 values

Controls

•  Integrated push-button control for Low or High speed operation.

•  For a complete list of optional main and auxiliary controls available, 
  refer to the 

Wall Control Compatibility Chart

 on last pages of wall 

 controls 

specifi cation sheet, available at www.venmar.ca.

•  For more details about controls, refer to the 

Main and auxiliary wal

 

controls

 user guide, also available at www.venmar.ca.

•  Removable terminal block included for quicker low voltage control 
 connections.

•  LED indicator shows operating modes and error codes.

•  Unit must be permanently energized, no control should be installed 
  on power supply of unit.

Air Flow

•  Pressure taps and balancing chart to allow easier balancing of the 
 unit

• Integrated balancing/backdraft dampers in cold supply and cold 
 exhaust 

ports

Defrost Cycles

•  Choice of regular or extended defrost cycles, according to climatic 
 conditions

•  To set extended defrost cycles, refer to unit installation manual

Requirements and standards

• 

HVI certifi ed

•  Complies with the UL 1812 requirements regulating the installation 
  of Energy Recovery Ventilators

•  Complies with the CSA C22.2 no. 113 Standard applicable to ventilators

•  Complies with CSA C444 requirements regulating the installation of 
 Energy 

Recovery 

Ventilators

R

EGULAR

 D

EFROST

 C

YCLES

O

UTSIDE

 T

EMPERATURE

*

D

EFROST

 

IN

 M

INUTES

 / A

IR

 E

XCHANGE

 

IN

 M

INUTES

°C

°F

L

OW

 S

PEED

H

IGH

 S

PEED

W

ARMER

 

THAN

 -10

W

ARMER

 

THAN

 14

N

O

 

DEFROST

N

O

 

DEFROST

FROM

 -10 

TO

 -15

FROM

 14 

TO

 5

6/40

9/40

FROM

 -15 

TO

 -27

FROM

 5 

TO

 -17

6/20

9/20

-27 

AND

 

LESS

-17 

AND

 

LESS

8/12

11/12

Warranty

The Venmar AVS S10 ERV is protected by a 5-year warranty on parts 
only, with the original proof of purchase.

* Outside temperature is read by a thermistor located inside the unit, 
next to fresh air from outside port.

Summary of Contents for AVS S10 ERV 41700

Page 1: ...l for Low or High speed operation For a complete list of optional main and auxiliary controls available refer to the Wall Control Compatibility Chart on last pages of wall controls specification sheet available at www venmar ca For more details about controls refer to the Main and auxiliary wall controls user guide also available at www venmar ca Removable terminal block included for quicker low v...

Page 2: ...vanized steel door HORIZONTAL INSTALLATION ONLY 32 lb UNIQUE 3 EASY STEPS FOR CEILING INSTALLATION TOP VIEW BOTTOM VIEW Removable terminal block to ease wall control connection Use 4 wire 22 AWG cable purchase separately Bend integrated hooks 2 on the same side and hang the unit Mount brackets to ceiling Clip the other side of the unit to the brackets OR ALTERNATE INSTALLATION Integrated dampening...

Page 3: ...SED ON AIR DISTRIBUTION TEMPERATURE VF0060 VF0060 VF0059 VENTILATION PERFORMANCE 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 1 0 0 10 20 30 40 50 60 70 80 90 100 110 120130 1 2 LOW SPEEDS 1 2 HIGH SPEEDS VG0094A NET AIRFLOW CFM E XTERNAL STATIC PRESSURE IN W G 3 4 3 4 NOTE Low speed and high speed are factory set low speed and high speed are selectable Simplified Installation connection to a forced air ...

Page 4: ...ot promote growth of mold or bacteria The ERV core design shall be made of rectangular flutes to provide very low pressure drop values Controls Unit shall be equipped with an integrated push button control for Low or High speed operation Choice of low voltage main controls not included shall be energized by ERV unit Optional low voltage auxiliary controls not included shall be energized by ERV uni...

Reviews: