TCY-FT-U
Temperature PID controller
Doc: 70-00-0128B, V1.2, 20110621
© Vector Controls GmbH, Switzerland
Page 1
Subject to alteration
TCY-FT-U Series Intelligent Temperature Controller
Features
•
Temperature PID control for HVAC systems.
•
Up to two 3-point outputs for 24VAC actuators.
•
1 internal temperature sensor and up to 2 external sensor inputs
•
Multiple remote control functions on external input
•
Password protected programmable user and control parameters
•
Blue backlight
Applications
•
Various temperature control applications
•
Water Only Systems: Radiator, floor heating or chilled ceilings
•
Individual room control for offices, residential, hotel rooms,
meeting rooms, etc.
General Description
The TCY-FT-U is a stand-alone electronic universal controller with one
temperature control loop. It may use up to 2 PID sequences. The TCY-FT-U
features 1 internal NTC temperature sensor, up to two external sensors
inputs and up to four binary outputs. The configuration has been reduced to
a minimum to allow for a simple and off the shelf usage. For more advanced
features the TCI product range may be used. The TCY-FT-U can be
configured using the standard operation terminal. No special tool or
software is required.
Name
Ordering
Item Name
Item code
Control Type
Key-data
TCY-FT2-U-W01
40-10 0068-1
Cooling only
Compact PID controller with:
2 TI, 1 3-point output
TCY-FT2-U-W02
40-10 0068-2
Heating only
TCY-FT2-U
40-10 0068
2-Pipe system
TCY-FT4-U
40-10 0072
4-Pipe system
1 TI, 2 3-point outputs
Accessories
S-Tn10-2
SD-Tn10-12-2
SD-Tn10-20-2
SDB-Tn10-12
SDB-Tn10-20
SRA-Tn10
40-20 0001
40-20 0002
40-20 0003
40-20 0051
40-20 0004
40-20 0005
Flying lead sensor with 2 m cable
Flying lead duct sensor 12cm immersion depth, 2m cable
Flying lead duct sensor 20cm immersion depth, 2m cable
Duct sensor with housing, 12cm immersion depth
Duct sensor with housing, 20cm immersion depth
Room sensor
Selection of actuators and sensors
Temperature Sensors:
Use only our approved NTC sensors to achieve maximum accuracy. Recommended is SDB-Tn10-20 as Duct sensor, SRA-
Tn10 as Room sensor and SDB-Tn10-20 with AMI-S10 as immersion sensor.
3-point Actuators:
Actuators with constant running time are recommended. Observe power limits. Do not use actuators with power
consumption > 6VA. Adjust running time in SW. Default running time is 90s for fully open / close running time.
Housing:
U = Vertical (2x4”) housing, Standard is square housing
Function:
2 = 2 = 2-Pipe, 4 = 4-Pipe
Input:
T = Temperature, H = Humidity
Output:
F = 3-point, M = Modulating, B = Binary
Series:
TCY
T C Y
T
- F
- U
(
)
2