background image

 

TCY-FT-U 

Temperature PID controller 

 

Doc: 70-00-0128B, V1.2, 20110621 

© Vector Controls GmbH, Switzerland 

Page 1 

Subject to alteration 

TCY-FT-U Series Intelligent Temperature Controller 

 

Features 

 

Temperature PID control for HVAC systems.  

 

Up to two 3-point outputs for 24VAC actuators.  

 

1 internal temperature sensor and up to 2 external sensor inputs 

 

Multiple remote control functions on external input 

 

Password protected programmable user and control parameters 

 

Blue backlight 

Applications 

 

Various temperature control applications 

 

Water Only Systems: Radiator, floor heating or chilled ceilings 

 

Individual room control for offices, residential, hotel rooms, 
meeting rooms, etc.  

General Description 

The TCY-FT-U is a stand-alone electronic universal controller with one 
temperature control loop. It may use up to 2 PID sequences. The TCY-FT-U 
features 1 internal NTC temperature sensor, up to two external sensors 
inputs and up to four binary outputs. The configuration has been reduced to 
a minimum to allow for a simple and off the shelf usage. For more advanced 
features the TCI product range may be used. The TCY-FT-U can be 
configured using the standard operation terminal. No special tool or 
software is required.  
 

Name  

 

Ordering 

Item Name 

Item code 

Control Type 

Key-data 

TCY-FT2-U-W01 

40-10 0068-1 

Cooling only 

Compact PID controller with: 
2 TI, 1 3-point output 

TCY-FT2-U-W02 

40-10 0068-2 

Heating only 

TCY-FT2-U 

40-10 0068 

2-Pipe system 

TCY-FT4-U 

40-10 0072 

4-Pipe system 

1 TI, 2 3-point outputs 

 

Accessories

 

S-Tn10-2 
SD-Tn10-12-2 
SD-Tn10-20-2 
SDB-Tn10-12 
SDB-Tn10-20 
SRA-Tn10 

40-20 0001 
40-20 0002 
40-20 0003 
40-20 0051 
40-20 0004 
40-20 0005 

Flying lead sensor with 2 m cable 
Flying lead duct sensor 12cm immersion depth, 2m cable 
Flying lead duct sensor 20cm immersion depth, 2m cable 
Duct sensor with housing, 12cm immersion depth 
Duct sensor with housing, 20cm immersion depth 
Room sensor 

Selection of actuators and sensors 
Temperature Sensors:  

Use only our approved NTC sensors to achieve maximum accuracy.  Recommended is SDB-Tn10-20 as Duct sensor, SRA-
Tn10 as Room sensor and SDB-Tn10-20 with AMI-S10 as immersion sensor.  

3-point Actuators:  

Actuators with constant running time are recommended. Observe power limits. Do not use actuators with power 
consumption > 6VA. Adjust running time in SW. Default running time is 90s for fully open / close running time.  
 

Housing:  

U  = Vertical (2x4”) housing, Standard is square housing 

Function: 

2  = 2 = 2-Pipe, 4 = 4-Pipe

 

Input: 

T  = Temperature, H = Humidity 

Output:  

F  = 3-point, M = Modulating, B = Binary 

Series: 

TCY

 

T  C  Y 

-  F 

-  U 

Summary of Contents for TCY-FT2-U-W01

Page 1: ...No special tool or software is required Name Ordering Item Name Item code Control Type Key data TCY FT2 U W01 40 10 0068 1 Cooling only Compact PID controller with 2 TI 1 3 point output TCY FT2 U W02...

Page 2: ...condensing Transport Storage Climatic Conditions Temperature Humidity Mechanical Conditions To IEC 721 3 2 and IEC 721 3 1 class 3 K3 and class 1 K3 25 70 C 13 158 F 95 r H non condensing class 2MT2 S...

Page 3: ...ation of mounting is less critical if external temperature sensors are used Installation 1 Connect the wires to be connected to the terminals of the power case according to wiring diagram 2 Install th...

Page 4: ...o a power supply for at least 10 hours for the backup function to operate accordingly Error messages The TCY FT U may display the following error condition Err1 The connection to the temperature senso...

Page 5: ...using UP or DOWN buttons Select 009 in order to get access to the user parameters 241 for controls parameters Press OPTION after selecting the correct password 3 Once logged in the parameter is displa...

Page 6: ...1 Cooling only 1 TCY FT2 U W2 Heating only 2 TCY FT2 U Heating and Cooling 2 pipe system 3 TCY FT4 U Heating and Cooling 4 pipe system TCY FT2 U 0 2 TCY FT4 U 0 3 TCY FT2 U W1 0 TCY FT2 U W2 1 TCY FT2...

Page 7: ...open 0 255s 90s CP 14 Minimum running time FO1 TCY FT4 U heating output The minimum time the output runs once it starts This setting prevents frequent switches with very short running times 0 255s 3s...

Page 8: ...offices CP18 2 Switching Energy Hold OFF and Comfort modes Opening the external temperature input will force the unit into the OFF operation mode The operation mode cannot be overridden by using the t...

Reviews: