Cleveland Controls

Division of UniControl Inc

.

(Figure 1)

APPLICATION

The 

Model AFS-460–136 

is a general pur-

pose  airflow  proving  switch  designed  for  

120 VAC HVAC and Energy Management 

applications  where  a  manual  reset  switch 

with DPDT contacts is desirable. It may be 

used to sense positive, negative, or differ

-

ential air pressure.

GENERAL DESCRIPTION & 

OPERATION

The plated housing contains a diaphragm, a 

calibration spring, a snap-acting switch with 

manual reset button, and  a dpdt relay.
The  sample  connections  located  on  each 

side of the diaphragm accept .25" OD tub

-

ing via the integral compression ferrule and 

nut.
An  enclosure  cover  guards  against  acci

-

dental contact with the live switch terminal 

screws  and  the  set  point  adjusting  screw. 

The enclosure cover will accept a 0.5" con

-

duit connection. The manual reset button is 

located on the top surface of the enclosure 

cover.

MOUNTING (SEE FIGURE 1)

Select  a  mounting  location  which  is  free 

from vibration. The 

AFS-460–136

 must be 

mounted with the diaphragm in any vertical 

plane in order to obtain the lowest specified 

operating set point. Avoid mounting with the 

(Figure 2)

sample line connections in the "up" position. 

Surface  mount  via  the  two 

3

/

16

"  diameter 

holes in the integral mounting bracket. The 

mounting holes are 3-

7

/

8

" apart. 

AIR SAMPLING  

CONNECTION 

(SEE FIGURE 2)

The 

AFS-460–136

  is  designed  to  accept  

firm-wall sample lines of ¼" OD tubing by 

means of  ferrule and nut compression con

-

nections. An  optional  ¼"  adapter,  suitable 

for slip-on flexible tubing is available.  For 

sample lines of up to 10 feet, ¼" OD tubing 

is acceptable. For lines up to 20 feet, use ¼" 

ID tubing. For lines up to 60 feet, use ½" ID 

tubing. Locate the sampling probe a  mini

-

mum of 1.5 duct diameters downstream from 

the air source. Install the sampling probe as 

close to the center of the airstream as pos

-

sible. Refer to Figure 2 to identify the high 

pressure inlet (H), and the low pressure inlet 

(L). Select one of the five application options 

listed below, and connect the sample lines 

as recommended.

POSITIVE PRESSURE ONLY:  

 Connect 

the sample line to inlet H; inlet L remains 

open to the atmosphere.

NEGATIVE PRESSURE ONLY:

  Connect 

the sample line to inlet L; inlet H remains 

open to the atmosphere.

TWO NEGATIVE SAMPLES:

  Connect the 

higher negative sample to inlet L. Connect 

the lower negative sample to inlet H.

TWO POSITIVE SAMPLES:

  Connect the 

higher positive sample to inlet H. Connect 

the lower positive sample to inlet L.

ONE POSITIVE AND ONE NEGATIVE 

SAMPLE: 

  Connect  the  positive  sample 

to  inlet  H.  Connect  the  negative  sample 

to inlet L. 

Model

AFS–460–136

 

Manual Reset DPDT Air Pressure  Sensing Switch for 120 VAC Applications

 

Reviews: