background image

INSTALLATION AND MAINTENANCE INSTRUCTIONS

BEFORE INSTALLING 

Please read the 

System Smoke Detectors Application Guide

, which provides 

detailed information on detector spacing, placement, zoning, wiring, and spe-
cial applications.Observe guidelines for NFPA 72.

NOTICE

: This manual should be left with the owner/user of this equipment.

IMPORTANT

:  Use  only  with  compatible  UL-listed  detector  heads  for 

proper  system  function.  The  detector  used  with  this  base  must  be  tested 
and  main-tained  regularly  following  requirements  of  NFPA  72  (depending 
on location). The detector should be cleaned at least once a year.

GENERAL DESCRIPTION

The  TR-B501-WHITE,  TR-B501-IV,  and  TR-B501-BL  are  plug  in  detector 
bases  intended  for  use  in  an  intelligent  system  with  screw  terminals 
provided  for  power  (+  and  –),  and  remote  annunciator  connections. 
Communication takes place over the power lines (+ and –). 

BASE TERMINALS

No. Function

Power (–), Remote Annunciator (–)

Power (+)

Remote Annunciator (+)

FIGURE 1. TERMINAL LAYOUT

TAMPER PROOF

TAB

TERMINAL 3 

TERMINAL 2 

TERMINAL 1 

 C0131-01

SPECIFICATIONS

Base Diameter: 

4.0" (10.2 cm)

Base Height: 

0.74" (18.8 mm) 

Operating Temperature Range: 

Refer to the applicable sensor’s operating temperature range provided in the sensor’s installation manual. 

Electrical Ratings – includes base and detector

Operating Voltage: 

15 to 32 VDC

Standby Current: 

150 µA 

Listing: UL268

I56-3738TRG-004

MOUNTING

This detector base mounts directly to 4" (10.2 cm) square with plaster ring, 
3½" (8.9 cm) octagon, 50 mm, 60 mm, and 70 mm centers.

INSTALLATION AND WIRING GUIDELINES (SEE FIGURE 2)

All wiring must be installed in compliance with all applicable local codes 
and any special requirements of the local authority having jurisdiction. Proper 
wire gauges should be used. The conductors used to connect smoke detectors 
to control panels and accessory devices should be color-coded to reduce the 
likelihood of wiring errors. Improper connections can prevent a system from 
responding properly in the event of a fire.

For signal wiring (the wiring between interconnected detectors and modules), 
it is recommended that the wiring be no smaller than 18 AWG (0.823 mm²). 
Wire sizes up to 12 AWG (3.31 mm²) may be used with the base. 

Alarm system control panels have specifications for allowable loop resistance. 
Consult the control panel specifications for the total loop resistance allowed 
before wiring the detector loops. 

Make wiring connections by stripping about 

3

/

8

" (10 mm) of insulation from 

the wire end (use strip gauge molded in base). Then slide the wire under the 
clamping plate and tighten the clamping plate screw. Do not loop the wire 
under the clamping plate. (See Figure 3.)

Check the zone wiring of all bases in the system before installing the detec-
tors. This includes checking the wiring for continuity, correct polarity, ground 
fault testing and performing a dielectric test. 

The base includes an area for recording the zone, address, and type of detec-
tor to be installed at that location. This information is useful for setting the 
detector head address and for verification of the detector type required for 
that location.

Once all detector bases have been wired and mounted, and the loop wiring 
has been checked, the detector heads may be installed in the bases. 

FIGURE 2. TYPICAL WIRING DIAGRAM FOR 2-WIRE LOOP

(–)

(+)

+

-

UL Listed Compatib

le

Control P

anel

CAUTION: Do not loop wire under terminal 1 or 2.  Break wire run to 

provide supervision of connections.

CLASS A OPTIONAL WIRING

REMOTE 

ANNUNCIATOR

(–)

(+)

3

2

1

3

2

1

3

2

1

C0133TRG-03

TRIGA Life Safety Systems, LLC

7600 Olde Eight Rd.

Hudson, Ohio 4426-1057

Tel: +1 330-577-5199. Email: [email protected] 

TR-B501-WHITE, TR-B501-IV, 

and TR-B501-BL  

4" Plug-in Detector Bases

I56-3738TRG-004 

4/22/2021

Reviews: