Remote control

and monitoring server

PCS200

User manual

Version 1.1

TERRA

Summary of Contents for PCS200

Page 1: ...Remote control and monitoring server PCS200 User manual Version 1 1 TERRA ...

Page 2: ... 5 13 Temperature sensor _________________________ 7 5 14 Ethernet port _______________________________ 7 5 15 Secondary Ethernet port optional _____________ 7 5 16 Console port RS232 debug ___________________ 7 6 Connecting to the network _________________________ 8 7 Default settings __________________________________ 8 8 PCS200 web control ______________________________ 8 8 1 Front page access ...

Page 3: ...supply if the power cord or plug are damaged Do not plug the server into the mains supply until all cables have been connected correctly To disconnect the server disconnect plug from mains socket The mains socket must be easily accessible The server shall not be exposed to dripping or splashing water and no objects filled with liquids such as vases shall be placed on it Avoidplacingservernexttocen...

Page 4: ... Status indicator 6 Ground clamp 10 UPScommunicationport 14 Ethernet port 7 230V 50Hzpowersupplyinput 11 Digitalopto isolatedinputs 15 SecondaryEthernetport optional 8 Coolingfan 12 Digitalrelayoutputs 16 Console port RS232 debug 9 Terrabus databusconnectors 13 Temperaturesensor 17 Antenna port not used Back view ...

Page 5: ...r Repeat this sequence untill the last number is set After finishing the configuration select Reboot and press Enter Systemwillrebootbyindicating Systembusy inthe Systemstatus screen Afterchangingstatusto Ok systemisrunningwithnewnetworksettings 5 4 Addressed indicator Green Addressed indicator turns on when USB cable is connected 5 5 Status indicator Green Status indicator stays on as long as PCS...

Page 6: ... pins female D SUB 9 1 4 0V logicground 2 5 Battery Low open collector output from UPS Normallylow 0V goeshighwhenlowbattery 3 4 0V logicground 4 2 Power Failure RS232 level output from UPS Normally RS232 low level 12V goes to RS232highlevel 12V whenlinepowerfailure 5 11 Digital opto isolated inputs There are two general purpose inputs Recommendedmatingterminalblockconnector TycoElectronics p n 28...

Page 7: ...raturesensor 1 Wirecompatible Pin out Pin 1 5V power supplied by PCS200 Pin 2 not used Pin 3 1 Wire data bus Pin 4 0V logic ground Temperature sensors can be supplied as an option please contact manufacturer for further information 5 14 Ethernet port This Ethernet port is used to connected PCS200 to the network PCS200 supports 10 100Mbps Ethernet If PCS200 is placed behind a firewall or a router m...

Page 8: ...ed 1 HTTP port 80 TCP 2 Extended HTML mode ports 81 TCP and 1000 TCP 3 Advanced terminal mode 2300 TCP 4 Other TCP or UDP ports if Video monitor feature is used See Video monitor section 8 3 for moreinformation If remote location with TerraBus managed devices and PCS200 server doesn t have access to the Internet then GSM data networking option could be used as alternative solution See Appendix Net...

Page 9: ...onfiguration page By pressing on the existing device it is possible to view and change device sparameters Afterselectingdesiredsettings pressbutton ApplyChanges toactivateconfiguration Set Default Parameters and Firmware upgrade options are only available in PCS200 with firmware version of 1 20 and above Set Default Parameters button sets default module parameters After operation completes SYSTEM ...

Page 10: ...ostreamofanIPstreamingdevice IPcamera videoserver connected to a secondary Ethernet port 5 15 IP streaming device must be configured with the following manual static network settings before connecting to PCS200 server IP address 192 168 99 2 SubnetMask 255 255 255 0 Gateway 192 168 99 1 AlsocheckIPstreamingdevicemanufacturerdocumentationorconfigurationsettingstofindoutwhichportsand which protocols...

Page 11: ... enter port number leave TCP and UDP selections blank and press CHANGE Once all needed ports have been modified press DONE to save new internal firewall configurations And press Videomonitor linkagain Internal IP streaming device web interface should open up in the main frame It is very likely that IP streaming devicewillhavesomedefaultloginprompt againcheckIPstreamingdevicemanufacturerdocumentati...

Page 12: ...f the inputs change User can tick which parameters should be monitored and reported For this feature to work email settings must be correctly set in Network page PCS200hasinternaltemperaturesensor Externaltemperatureismonitoredonlyifexternaltemperaturesensoris connected to connector 11 Digital inputs are located in connector 9 ...

Page 13: ...mment button tosave the information Eventslogwilldisplay A relay state change by user Digitalinputtrigeredbyexternaldevice Power line status change is reported by UPS 8 6 View configuration View configuration submenu allows user to choose number of subracks to be shown in SYSTEM MANAGEMENT page This parameter defines how many devices should be scanned by Terra Bus Recommendation use only groups wh...

Page 14: ...ton Locate file on the computer Press Send button Uploadtimedependsonfilesizeandnetworkconditions Systemdisplaysconfirmationmessageiffileisuploadedsuccessfully Todownloadfile Press in the button named Description 1 3 FILE Confirmfiledownload 8 8 Time Date PCS200 internal battery backed system clock can by adjusted by synchronizing with PC time in Time Date submenupagebypressingbutton SYNC ...

Page 15: ...values on the web page Network Deviceisshippedwithsettings IP address 192 168 0 99 Netmask 255 255 255 0 If device is used not in the same subnet as the user s workstation Gateway IP address is also required e g 192 168 0 1 At least one DNS address should be supplied Ifemailstatusreportsarerequired see Status page thenSMTPserverandemailaddressesmustbesupplied ...

Page 16: ... levels Administrator and User User access level is prevented from accessing followingfunctions Upgrademodulefirmware Set default module parameters Add delete modifyusers Viewlogs Upgrade PCS200 server firmware 8 11 View logs Anysuccessfulor unsuccessfulloginofexistinguserwillbeshowinthelogfile Logintimeandremoteuser sIP address are saved Administrator can clear access log by pressing Clear ALL hi...

Page 17: ... update allows user to upload and upgrade PCS200 server firmware supplied by manufacturer PCS200 firmware version is printed on top of each page after serial number 8 13 Restart Reboots PCS200 server 8 14 LOGOUT Allows user to log out ...

Page 18: ...ocal cellular operator It might also be possible to use SIM card with dynamic IP address then dynamic DNS service e g www dyndns org could be used to provide symbolic domain name But it s important that cellular network provider SIM card ISP public IP would matchISPlocalIPaddress otherwiseGSMrouterandPCS200willnotbevisibleandaccessiblefromtheInternet Insomecasesthiscouldberequestedasextraservicefr...

Page 19: ... TCP o 81 TCP o 1000 TCP o 2300 TCP o possiblyadditionalIPstreamingportsif VideoMonitor featureisused notrecommended becauseofhighamountofnetworktrafficandlimitedspeed Internal tests and step by step procedure is based on using RUT100 3G Mobile Router manufactured by Teltonika http www teltonika lt Althoughanyother3G EDGErouterwithsimilarcharacteristicscouldbeused too RUT100 by default comes with ...

Page 20: ...Thenenternetworksettingsasshown Next add following ports to forward to IP 192 168 0 99 80 TCP 81 TCP 1000 TCP 2300 TCP 20 ...

Page 21: ...reboot RUT100 router Then connect RUT100 LAN port to PCS200 Ethernet port 14 Enter provided static IP address or dynamic DNS domain name in the Internet Explorer address bar and you should see PCS200 server startup screen 21 ...

Page 22: ...TERRA UAB Draugystes str 22 LT 51256 Kaunas Lithuania Tel 370 37 31 34 44 fax 370 37 31 35 55 E mail sales terraelectronics com http www terraelectronics com ...