background image

  

1

 

 

 

 

Uninterruptible Power Systems 

EVO DSP TT 

10-100kVA 

 

User’s manual 

 

Summary of Contents for EVO DSP TT

Page 1: ...1 Uninterruptible Power Systems EVO DSP TT 10 100kVA User s manual...

Page 2: ...s This symbol points out the instructions which are especially important This symbol points out the risk of electric shock if the following instruction is not obeyed This symbol points out the instruc...

Page 3: ...th1 1 Keypad 15 4th1 2 Mimic Panel 16 4th1 3 Liquid Crystal Display LCD and User Menu 17 4th1 4 Buzzer 20 5 Operating Procedures 21 5th1 Commissioning 21 5th2 Decommissioning 21 5th3 Switching into ma...

Page 4: ...ree Contact Communication 30 9 Maintenance 31 9th1 Battery fuses 31 9th2 Batteries 31 9th3 Fans 31 9th4 Capacitors 31 10 Troubleshooting 32 11 Technical Specifications 35 12 Internal Battery Location...

Page 5: ...persons Cables crossing a path must be protected in accordance with local electrical and safety regulations Do not expose UPS to rain or liquids in general Do not put any solid objects into any access...

Page 6: ...ment Key of the cabinet door Battery fuses three pieces Test report 2 1 Storage Recommended storage temperature humidity and altitude values are listed in the Technical Specifications section If the b...

Page 7: ...nd the cable cross sections for the linear loads UPS Input thermal protection Bypass mains input thermal protection Input cable cross section Bypass mains input cable cross section Battery cable cross...

Page 8: ...case wait for two hours before beginning with the installation Layout of the connection terminals and boards are shown below A1 Communication interface board A2 Parallel connection board optional F1 I...

Page 9: ...ction L1 input L1 bypass etc BATTERY BATTERY NEUTRAL BATTERY PE INPUT L1 INPUT L2 INPUT L3 INPUT NEUTRAL OUTPUT L1 OUTPUT L2 OUTPUT L3 OUTPUT NEUTRAL SPLIT BYPASS NEUTRAL SPLIT BYPASS L3 SPLIT BYPASS...

Page 10: ...nd with a low impedance connection PE terminals of the loads shall be connected to output protective earth terminal of the UPS If there is an external battery cabinet present it shall be grounded via...

Page 11: ...ls To connect external batteries do the following Switch the circuit breaker of the external batteries to OFF or 0 position Connect the pole of the external batteries to the battery terminal Connect t...

Page 12: ...d from the mains input Thus if such a device is in question mains input shall be comprehended when the bypass mains input is referred in the following sections of the manual UPS behavior at the start...

Page 13: ...n this mode When the upper provisions are met the UPS works in bypass mode in the following conditions During the start up If the bypass priority is selected If the inverter is disabled or blocked In...

Page 14: ...er and the inverter shall be enabled for the UPS to operate in this mode When the upper provisions are met the UPS works in normal mode in the following conditions If the inverter priority is selected...

Page 15: ...al display offers detailed information and provides access to controls Keypad enables the user to move in the menu and to make selections 4 1 1 Keypad Functions of the buttons are given below BUTTON S...

Page 16: ...the bypass voltage Off Battery Red Battery mode is active and battery voltage is OK Steady UPS is performing battery test and battery voltage is OK Battery mode is active and battery voltage is close...

Page 17: ...llowing structure OPERATING MODE or VSECFLR MENU or PARAMETER NAME If there is no voltage on the output VSECFLR message is displayed on the upper line Operation mode parameter is one of the notations...

Page 18: ...al operation or mains voltage is very low A22 INP SEQ FAIL Phase sequence of input mains voltages is not OK A23 REC TMP HIGH Rectifier block temperature is very high A24 REC OVERLOAD RMS current drawn...

Page 19: ...modes Push ENTER to switch between INVRTR and BYPASS START B TEST Push ENTER to start battery test BUZZER ENBLD DSBLD Enable or disable the buzzer Push ENTER to switch between ENBLD and DSBLD COMM RS2...

Page 20: ...t description For events descriptions see ALARM DEFINITIONS on page 17 Events stored in EPROM using FIFO method Order number of last occurred event is 001 To look event details you must press ENTER ke...

Page 21: ...matically switches to normal mode NORMAL message will not be displayed until the UPS switches to normal mode Frequency waveform rms value of the bypass mains voltage shall be within acceptable limits...

Page 22: ...nd F5 to OFF 0 position LCD and buzzer will stop operation in a few minutes During manual bypass operation loads are fed directly from bypass mains Therefore no protection against mains disturbances o...

Page 23: ...llel to the existing UPS to increase the output power capacity The AC inputs of all UPS s in the parallel system are connected to the same mains and all the AC outputs are connected to each other Each...

Page 24: ...CANBUS Before starting up the UPS s make the connection of communication cables between UPS s as per below diagram COMMUNICATION CABLE CONNECTION BETWEEN PARALLEL UPS s CAUTION Do not remove the commu...

Page 25: ...4pcs parallel system In this case the system will operate as 2 2 redundancy mode and the total load that is going to be connected to the system can not be more than 2x One UPS Power N Value here can b...

Page 26: ...on any UPS all the UPS s will pass to Static Bypass mode at the same time In order to pass to static bypass mode from the LCD panel menu go to Commands Menu Extcmnd Select the SYS TO BYP ENBLD from t...

Page 27: ...ts Bypass mains limits are software parameters They can be changed upon request 7 3 Battery test This feature enables the user to obtain information about the battery condition If the batteries have a...

Page 28: ...ttempts to force the thermal magnetic protection devices between the output terminals and the short circuited load to open by supplying current to the short circuited load for a limited duration The U...

Page 29: ...n be activated at one time The selection between RS232 and RS422 communications can be done by setting the COMM parameter in COMMANDS menu as desired 8 2 RS422 Communication DSUB 9 male connector with...

Page 30: ...s sinus or 60 Vdc Maximum contact current depends on the applied voltage and the load characteristic Both maximum voltage and maximum contact current corresponding to the applied voltage shall not be...

Page 31: ...fuse of same rating or equivalent 9 2 Batteries Battery life strongly depends on the ambient temperature There are also other factors like the number of charge discharge cycles and discharge depth Bat...

Page 32: ...Make sure that the bypass circuit breaker is I ON if the UPS has no separate bypass mains input make sure that the input circuit breaker is I ON e g its beyond its limits or it has a total harmonic di...

Page 33: ...igher than its upper limit Check if the bypass mains voltage is in specified limits VIN LOW alarm is present Input line neutral voltage is lower than its lower limit IN SYN FLR alarm is present Freque...

Page 34: ...es BATT C OPEN alarm is present A difference between battery DC bus voltage is present Battery circuit breaker F5 is probably open 0 OFF Make sure that the battery circuit breaker is I ON If not do th...

Page 35: ...evel 187 100 load line neutral 120 64 load line neutral 80V 42 load line neutral Upper limit 280 Nominal frequency Hz 50 60 Frequency range Hz 10 Nominal current A wave form sinusoidal rms value 2 13...

Page 36: ...DS Safety EN 62040 1 2 EN 60950 1 Performance EN 62040 3 EMC EN 50091 2 Product Certification CE COMMUNICATIONS Free contact communication AC failure battery under voltage bypass and output failure Se...

Page 37: ...nect the 41 numbered cable to the negative pole of the 41st battery Insert the drawer to the middle shelf and place it on the right side where the poles of the batteries face inside as shown in the di...

Page 38: ...to 30kVA Red B Blue Black B 110cm 160cm 70cm 145cm 56 42 43 48 55 49 62 56 55 49 48 35 22 23 28 34 29 41 35 34 29 28 8cm 15 55cm 20cm 1 2 7 14 8 21 15 14 8 7 32 31 22 21 42 41 110cm 7 9 8 4 6 5 1 3 2...

Reviews: