Installation Guide

502-025

HPU2 & HPU3 Water Source Heat Pump Controller

Self-Contained Interoperable Controller Model UCP-1

SUPERSEDES: February 28, 2012

EFFECTIVE: April 17, 2013

Plant ID: 001-3982

SPECIFICATIONS

Electrical Inputs

Cabling:

 twisted shielded pair, 18

 AWG 

recommended—500

 

feet max. (152

 

meters), 10 bit resolution

Space Temp (optional):

 Precon Type II or Type III 10k thermistor

Supply Air Temp (HPU3 only):

 Precon Type III 10K thermistor 

Heat Pump Power Transducer (HPU3 only): 

0 to 10 Volts DC

Equipment Status, High Pressure Alarm (HPU3 only), Low Pressure Alarm (HPU3 only):

 Dry Contact, Normally Open, 

5 Volts DC Max

Thermostat Network:

 12 Volt nominal, internally limited to 0.04 A (TS300 Series)

Electrical Outputs

Modulated Fan (HPU3 only):

 Analog 0-10 Vdc, 2K Ohm minimum load, 8 bit resolution

Stage 1, Stage 2, Reversing Valve, Fan, Dehumidification (HPU3 only):

 Triac 24 VAC, 1A @ 50C, 0.5A @ 60C, limited 

by the Class 2 supply rating

Recommended Sensor Wire 

Recommended LON Bus FTT-10A Network Wire

Speed:

 78KBPS

Max Volts:

 42.4 Volts DC 

Cabling:

 Maximum node-to-node distance: 1312 feet (400 meters); Maximum total distance: 1640 feet (500 meters) 

Mechanical

Dimensions:

 5.55” (141mm) high, 6.54” (166 mm) wide, 1.75” deep (44

 mm), 

ABS

Controller Weight:

 0.70

 pounds 

(0.32

 kilograms)

Shipping Weight:

 1.0

 pounds 

(0.46

 kilograms)

Processor:

 3150 Neuron 10 MHz

Flash:

 48

 Kilobytes 

Cable Type

Pairs

Details

Taco Catalog No.

18AWG 

1

Stranded Twisted Shielded Pair, Plenum

WIR-018

Cable Type

Pairs

Details

Taco Catalog No.

Level 4 22AWG (0.65mm)

1

Unshielded, Plenum, U.L. Type CMP

WIR-022

Summary of Contents for iWorx HPU2

Page 1: ...internally limited to 0 04 A TS300 Series Electrical Outputs Modulated Fan HPU3 only Analog 0 10 Vdc 2K Ohm minimum load 8 bit resolution Stage 1 Stage 2 Reversing Valve Fan Dehumidification HPU3 only...

Page 2: ...lass 2 external power source not supplied to operate The controller power input requires a voltage of 24 Volts AC To calculate power source current requirements add the power consumption of all periph...

Page 3: ...onnect the equipment to a power source different from that to which the receiver is connected Consult the equipment supplier or an experienced radio TV technician for help You are cautioned that any c...

Page 4: ...iWorx HPU Series 4 502 025 Effective April 17 2013 2013 Taco Electronic Solutions Inc...

Page 5: ...iWorx HPU Series 502 025 Effective April 17 2013 5 2013 Taco Electronic Solutions Inc...

Page 6: ...be shorted Setup Instructions 1 Press Controllers from main screen 2 Select required HPU from controller list and press appropriate controller 3 Press All Settings 4 Press Thermostat 5 The Thermostat...

Page 7: ...p Stages 9 The Comp Stages menu opens a Select number of Stages of equipment 1 or 2 b Select the stage Control Band in degrees Cannot be set to 0 c Select the Stage Time in minutes Cannot be set to 0...

Page 8: ...iWorx HPU Series 8 502 025 Effective April 17 2013 2013 Taco Electronic Solutions Inc...

Page 9: ...iWorx HPU Series 502 025 Effective April 17 2013 9 2013 Taco Electronic Solutions Inc...

Page 10: ...shorted Setup Instructions 1 Press Controllers from main screen 2 Select required HPU3 from controller list and press appropriate controller 3 Press All Settings 4 Press Dehumidification 5 The Dehumid...

Page 11: ...s 1 Press Controllers from main screen 2 Select required HPU3 from controller list and press appropriate controller 3 Press All Settings 4 Press Next 3 5 Press Mod Fan Settings 6 The Mod Fan Settings...

Page 12: ...lot relay have been pow ered with 24 VAC and the output has been correctly wired to the coil of the pilot relay Also ensure that the pilot relay has a 24 VAC coil The 10K thermistor reading is at its...

Page 13: ...ormation please refer to the last page of this Document for the company s Limited Warranty Statement which is also issued with the product or available at www taco hvac com Notes Description Audience...

Page 14: ...iWorx HPU Series 14 502 025 Effective April 17 2013 2013 Taco Electronic Solutions Inc...

Page 15: ...iWorx HPU Series 502 025 Effective April 17 2013 15 2013 Taco Electronic Solutions Inc...

Page 16: ...be covered by this warranty TES products are not intended for use to support fire suppression systems life support systems critical care applications commercial aviation nuclear facilities or any othe...

Reviews: