Installation Smoke Detector 
ELQZ-2-428-2, GOLD

General

The ELQZ-2-428-2 smoke detector is used for measuring 
any smoke present in ventilation ducts. It consists of an 
ionising detector mounted in an adaptor system where 
both the tube and enclosure are designed for optimum 
airflow through the detector. The system meets all the 
fire safety requirements for air velocities between 0.2 m/s 
and 20 m/s. The smoke detector is used together with a 
control unit (fitted inside an ELQA equipment cubicle or a 
separate equipment cubicle for the smoke detection and 
warning function) for controlling fans, fire and smoke 
dampers.

Operation

If any smoke is detected, a red LED on the detector lights 
up and the detector transmits an alarm signal to the con-
trol unit.
Any accumulation of impurities in the smoke detector will 
make it more sensitive and gradually approach its alarm 
condition. To avoid unnecessary alarms caused by fouling, 
the detector is equipped with a service alarm (green LED). 
When lit, this LED indicates that the detector ought to be 
cleaned.

Tecnical details

Type of detector Ionising
Power supply 

 

24VDC (from control unit)

Power consumption: 

 

In-operation

 

 

Max 0,04mA

Service alarm

 

 

~ 13mA

Smoke alarm

 

 

~ 48mA

Permissible
ambient temperature 

-20°C to +50°C

Permissible humidity 

Max 99% rH

Inclosure Class   

IP54

Weight   

 

800g

Accessories

The ELQZ-1-428-2-1 Mounting bracket should be used for 
mounting the detector on a circular or insulated duct.

Maintenance

Whenever the smoke detector becomes fouled, it will be 
more sensitive and may trip the service alarm. This situa-
tion can easily be delayed by vacuum cleaning the detec-
tor once a year.

Dimensions

Venturi tube length 600 mm.

(All dimensions in mm)

 

 

 

 

Summary of Contents for GOLD ELQZ-2-428-2

Page 1: ...tor transmits an alarm signal to the con trol unit Any accumulation of impurities in the smoke detector will make it more sensitive and gradually approach its alarm condition To avoid unnecessary alarms caused by fouling the detector is equipped with a service alarm green LED When lit this LED indicates that the detector ought to be cleaned Tecnical details Type of detector Ionising Power supply 2...

Page 2: ...conden sation inside the detector housing To ensure satisfactory smoke detection the smoke detector should be located at a distance in the direction of airflow that is equivalent to at least 3 x the hydraulic diameter of the duct upstream of the nearest source of disturbance in the ducting see the examples of sources of disturbance below If it is located downstream of the nearest source of disturba...

Page 3: ...m dia opening for smoke detector with mounting bracket see item 10 3 Do not cut this end Measure the ventilation duct Cut the tube to an appropriate length if needed The tube should penetrate 90 of the duct diameter into the duct Insert the end plug End plug Lock the tube in position by means of the stop screw Slip the seal onto the tube Insert the tube in the bottom of the detector housing 4 Moun...

Page 4: ...sable to consider relocating the detec tor 6 Insert the block 7 Electric wiring Connect the electric wiring as shown in the wiring diagram If only one smoke detector is connected to the system install the final resistor 2 2kΩ in this detector If several smoke detectors are to be connected to one control unit wire the final resistor 2 2kΩ in the last detector in the loop Fit only one resistor per loo...

Page 5: ...era tes correctly Expose the detec tor to smoke from a match or a suitable spray for testing smoke detectors Secure the cover by means of screws Fit the cover on the detector Do not drill any holes in the plastic cover for fitting identification plates or the like Doing so will cause leakage which will seriously impair detector performance ...

Page 6: ...n no smoke is present The smoke detector has been located where condensa tion can form inside it such as outdoors in a cold attic a kitchen or the like An alarm is indicated by the control unit only Measure the resistance of the loop 2 2kΩ from the control unit Check that the control unit is OK by wiring the final resistor to the smoke detector output on the control unit Use a voltmeter to check th...

Reviews: