background image

SSE-X3348T and SSE-X3348TR

48-Port 10G

Top-of-Rack Switches

Installation Manual

Revison 1.0

Summary of Contents for SSE-X3348T

Page 1: ...SSE X3348T and SSE X3348TR 48 Port 10G Top of Rack Switches Installation Manual Revison 1 0 ...

Page 2: ...s total liability for all claims will not exceed the price paid for the hardware product FCC Statement This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment This equipment ge...

Page 3: ...nents included with the switch and describes its main features Chapter 2 System Safety You should familiarize yourself with this chapter for a general overview of safety precautions that should be followed when installing and servicing the switch Chapter 3 Network Planning Refer here for details on network planning for the switch Chapter 4 Installation This chapter describes how to install the swi...

Page 4: ...s optimum operational mode e g speed and duplex mode based on the capabilities of the node to which it is connected Bandwidth The difference between the highest and lowest frequencies available for network signals Also synonymous with wire speed the actual speed of the data transmission along the cable Collision Domain Single CSMA CD LAN segment CSMA CD CSMA CD Carrier Sense Multiple Access Collis...

Page 5: ... Now incorporated in IEEE 802 3 2005 LAN Segment Separate LAN or collision domain LED Light emitting diode used for monitoring a device or network condition Local Area Network LAN A group of interconnected computer and support devices Media Access Control MAC A portion of the networking protocol that governs access to the transmission medium facilitating the exchange of data between network nodes ...

Page 6: ...SSE X3348T SSE X3348TR Switch Installation Manual vi Notes ...

Page 7: ...ed Warning Statements 2 1 2 1 About Standardized Warning Statements 2 1 Warning Definition 2 1 Installation Instructions 2 3 Circuit Breaker 2 4 Power Disconnection Warning 2 5 Equipment Installation 2 6 Restricted Area 2 7 Battery Handling 2 9 Redundant Power Supplies 2 10 Backplane Voltage 2 11 Comply with Local and National Electrical Codes 2 12 Product Disposal 2 13 Hot Swap Fan Warning 2 14 P...

Page 8: ... Initial Configuration Changes 4 8 Task 6 Install Transceivers and Connect Cables 4 9 4 4 Power and Grounding 4 10 Power Supply Modules 4 10 Grounding the Chassis 4 12 How to Connect to AC Power 4 12 Chapter 5 Making Network Connections 5 1 5 1 Cable Labeling and Connection Records 5 1 5 2 Understanding the Port Status LEDs 5 2 5 3 How to Install a QSFP Transceiver 5 3 5 4 How to Connect to Twiste...

Page 9: ... 2 6 5 Compliances 6 3 Chapter 7 Switch Management 7 1 7 1 Understanding the System Status LEDs 7 1 7 2 How to Connect to the Console Port 7 2 7 3 How to Reset the Switch 7 4 Chapter 8 Troubleshooting 8 1 8 1 Diagnosing LED Indicators 8 1 8 2 System Self Diagnostic Test Failure 8 1 8 3 Power and Cooling Problems 8 1 8 4 Installation 8 2 8 5 In Band Access 8 2 ...

Page 10: ...SSE X3348T SSE X3348TR Switch Installation Manual x Notes ...

Page 11: ... and a fan tray module The switch supports a full set of Layer 2 switching data center bridging and Layer 3 routing features The switch can be deployed as a top of rack TOR or distributed spine switch to form a network fabric that can reduce infrastructure expenses and power consumption in the data center This network fabric can be used to interconnect tens of thousands of servers delivering cloud...

Page 12: ... Mbps copper links to other devices For more information see Section 5 4 How to Connect to Twisted Pair Copper Ports on page 5 4 40G QSFP Slots The switch contains four Quad Small Form Factor Pluggable Plus QSFP transceiver slots that operate up to 40 Gbps full duplex For more information see Section 5 5 How to Connect to QSFP Fiber Optic Ports on page 5 8 1000BASE T RJ 45 Ports The switch include...

Page 13: ...n to a terminal or a PC running terminal emulation software The port can be used for performing switch monitoring and configuration For more information see Section 7 2 How to Connect to the Console Port on page 7 2 USB Port The USB port on the switch rear panel is reserved for future use Fan Tray Module The fan tray module provides air cooling for the switch system For more information see Switch...

Page 14: ...SSE X3348T SSE X3348TR Switch Installation Manual 1 4 Notes ...

Page 15: ...e Supermicro chassis These warnings may also be found on our web site at http www supermicro com about policies safety_information cfm Warning Definition Warning This warning symbol means danger You are in a situation that could cause bodily injury Before you work on any equipment be aware of the hazards involved with electrical circuitry and be familiar with standard practices for preventing acci...

Page 16: ... INSTRUCCIONES IMPORTANTES INFORMATIONS DE SÉCURITÉ Ce symbole d avertissement indique un danger Vous vous trouvez dans une situation pouvant entraîner des blessures ou des dommages corporels Avant de travailler sur un équipement soyez conscient des dangers liés aux circuits électriques et familiarisez vous avec les procédures couramment utilisées pour éviter les accidents Pour prendre connaissanc...

Page 17: ...n van de standaard procedures om ongelukken te voorkomen Gebruik de nummers aan het eind van elke waarschuwing om deze te herleiden naar de desbetreffende locatie BEWAAR DEZE INSTRUCTIES Installation Instructions Warning Read the installation instructions before connecting the system to the power source 設置手順書 システムを電源に接続する前に 設置手順書をお読み下さい 警告 将此系统连接电源前 请先阅读安装说明 警告 將系統與電源連接前 請先閱讀安裝說明 Warnung Vor dem A...

Page 18: ... Produkt ist darauf angewiesen dass im Gebäude ein Kurzschluss bzw Überstromschutz installiert ist Stellen Sie sicher dass der Nennwert der Schutzvorrichtung nicht mehr als 250 V 20 A beträgt Advertencia Este equipo utiliza el sistema de protección contra cortocircuitos o sobrecorrientes del edificio Asegúrese de que el dispositivo de protección no sea superior a 250 V 20 A Attention Pour ce qui e...

Page 19: ...m the power supply module s before accessing the chassis interior to install or remove system components 電源切断の警告 システムコンポーネントの取り付けまたは取り外しのために シャーシー内部にアクセ スするには システムの電源はすべてのソースから切断され 電源コードは電源モジュールから取り 外す必要があります 警告 在你打开机箱并安装或移除内部器件前 必须将系统完全断电 并移除电源线 警告 在您打開機殼安裝或移除內部元件前 必須將系統完全斷電 並移除電源線 Warnung Das System muss von allen Quellen der Energie und vom Netzanschlusskabel getrennt sein das von den Spg Verso...

Page 20: ...야 합니다 Waarschuwing Voordat u toegang neemt tot het binnenwerk van de behuizing voor het installeren of verwijderen van systeem onderdelen dient u alle spanningsbronnen en alle stroomkabels aangesloten op de voeding en van de behuizing te verwijderen Equipment Installation Warning Only trained and qualified personnel should be allowed to install replace or service this equipment 機器の設置 トレーニングを受け認定され...

Page 21: ... mag alleen worden geïnstalleerd vervangen of hersteld door geschoold en gekwalificeerd personeel Restricted Area Warning This unit is intended for installation in restricted access areas A restricted access area can be accessed only through the use of a special tool lock and key or other means of security This warning does not apply to workstations アクセス制限区域 このユニットは アクセス制限区域に設置されることを想定しています アクセス制限...

Page 22: ...zones d accès réservés L accès à une zone d accès réservé n est possible qu en utilisant un outil spécial un mécanisme de verrouillage et une clé ou tout autre moyen de sécurité 경고 이 장치는 접근이 제한된 구역에 설치하도록 되어있습니다 특수도구 잠금 장치 및 키 또는 기타 보안 수단을 통해서만 접근 제한 구역에 들어갈 수 있습니다 Waarschuwing Dit apparaat is bedoeld voor installatie in gebieden met een beperkte toegang Toegang tot dergelijke gebieden kunnen alle...

Page 23: ...nutzten Batterien nach den Anweisungen des Herstellers Attention Danger d explosion si la pile n est pas remplacée correctement Ne la remplacer que par une pile de type semblable ou équivalent recommandée par le fabricant Jeter les piles usagées conformément aux instructions du fabricant Advertencia Existe peligro de explosión si la batería se reemplaza de manera incorrecta Reemplazar la batería e...

Page 24: ...置 このユニットは複数の電源装置が接続されている場合があります ユニットの電源を切るためには すべての接続を取り外さなければなりません 警告 此部件连接的电源可能不止一个 必须将所有电源断开才能停止给该部件供电 警告 此裝置連接的電源可能不只一個 必須切斷所有電源才能停止對該裝置的供電 Warnung Dieses Gerät kann mehr als eine Stromzufuhr haben Um sicherzustellen dass der Einheit kein trom zugeführt wird müssen alle Verbindungen entfernt werden Advertencia Puede que esta unidad tenga más de una conexión para fuentes de alimentación Para co...

Page 25: ...意ください 警告 当系统正在进行时 背板上有很危险的电压或能量 进行维修时务必小心 警告 當系統正在進行時 背板上有危險的電壓或能量 進行維修時務必小心 Warnung Wenn das System in Betrieb ist treten auf der Rückwandplatine gefährliche Spannungen oder Energien auf Vorsicht bei der Wartung Advertencia Cuando el sistema está en funcionamiento el voltaje del plano trasero es peligroso Tenga cuidado cuando lo revise Attention Lorsque le système est en fonctionnement des tensio...

Page 26: ...拠 機器の取り付けはその地方および国の電気規格に準拠する必要があります 警告 设备安装必须符合本地与本国电气法规 警告 設備安裝必須符合本地與本國電氣法規 Warnung Die Installation der Geräte muss den Sicherheitsstandards entsprechen Advertencia La instalacion del equipo debe cumplir con las normas de electricidad locales y nacionales Attention L équipement doit être installé conformément aux normes électriques nationales et locales ﻫﻨﺎﻙ ﺧﻄﺮ ﻣﻦ ﺍﻟﻜﻬﺮﺑﺎﺋﻲ ﺍﻟﺘﻴﺎﺭ ﻋﻠﻰ ﺍﻟﻤﻮﺟﻮﺩﺓ...

Page 27: ...规章进行 警告 本產品的廢棄處理應根據所有國家的法律和規章進行 Warnung Die Entsorgung dieses Produkts sollte gemäß allen Bestimmungen und Gesetzen des Landes erfolgen Advertencia Al deshacerse por completo de este producto debe seguir todas las leyes y reglamentos nacionales Attention La mise au rebut ou le recyclage de ce produit sont généralement soumis à des lois et ou directives de respect de l environnement Renseignez vous...

Page 28: ...可能仍在轉動 小心不要將手指 螺絲起子和其他物品 太靠近風扇 Warnung Die Lüfter drehen sich u U noch wenn die Lüfterbaugruppe aus dem Chassis genommen wird Halten Sie Finger Schraubendreher und andere Gegenstände von den Öffnungen des Lüftergehäuses entfernt Advertencia Los ventiladores podran dar vuelta cuando usted quite ell montaje del ventilador del chasis Mandtenga los dedos los destornilladores y todos los objetos lejos ...

Page 29: ... fire Electrical Appliance and Material Safety Law prohibits the use of UL or CSA certified cables that have UL CSA shown on the code for any other electrical devices than products designated by Supermicro only 電源コードと AC アダプター 製品を設置する場合 提供または指定された接続ケーブル 電源コードと AC アダプ ターを使用下さい 他のケーブルやアダプタを使用すると故障や火災の原因になるこ とがあります 電気用品安全法は UL または CSA 認定のケーブル UL CSE マークが コードに表記 を Supermicro が指定する製品以外に使用することを禁止しています 警...

Page 30: ...o solamente Attention Lors de l installation du produit utilisez les bables de connection fournis ou désigné L utilisation d autres cables et adaptateurs peut provoquer un dysfonctionnement ou un incendie Appareils électroménagers et de loi sur la sécurité Matériel interdit l utilisation de UL ou CSA câbles certifiés qui ont UL ou CSA indiqué sur le code pour tous les autres appareils électriques ...

Page 31: ...인증한 케이블 전선 위에 UL CSA 가 표시 들의 사용을 금지합니다 Waarschuwing Bij het installeren van het product gebruik de meegeleverde of aangewezen kabels stroomkabels en adapters Het gebruik van andere kabels en adapters kan leiden tot een storing of een brand Elektrisch apparaat en veiligheidsinformatiebladen wet verbiedt het gebruik van UL of CSA gecertificeerde kabels die UL of CSA die op de code voor andere elektr...

Page 32: ...SSE X3348T SSE X3348TR Switch Installation Manual 2 18 Notes ...

Page 33: ...s part of a distributed spine network providing full line rate switching at Layer 2 or Layer 3 across all ports In many data center configurations Ethernet connections link servers and data networks and Fibre Channel connections link servers to storage networks This switch enables the creation of a converged network which employs lossless Ethernet connections between FCOE storage servers and other...

Page 34: ... 6X 8X A 1X Li nk Mode 2X 3X 4X 5X 7X 6X 8X A 1X Li nk Mode 2X 3X 4X 5X 7X 6X 8X A 1X Li nk Mode 2X 3X 4X 5X 7X 6X 8X A 1X Li nk Mode 2X 3X 4X 5X 7X 6X 8X A 1X Li nk Mode 2X 3X 4X 5X 7X 6X 8X Consol e Reset Cl ear Mode Sel ect Act Fdx 100 Swi t chEngi neFai l Sel fTest A 1X Li nk Mode 2X 3X 4X 5X 7X 6X 8X A 1X Li nk Mode 2X 3X 4X 5X 7X 6X 8X A 1X Li nk Mode 2X 3X 4X 5X 7X 6X 8X A 1X Li nk Mode 2X ...

Page 35: ...rom the front and expel hot air at the rear The SSE X3348T top of rack switch includes power supply units and a fan tray module that have a front to back F2B airflow direction that maintains cool aisles in the data center Figure 3 3 When mounted in a rack with other network equipment that may have a back to front B2F airflow direction the SSE X3348TR top of rack switch includes power supply and fa...

Page 36: ...SSE X3348T SSE X3348TR Switch Installation Manual 3 4 Figure 3 4 B2F Airflow Cooling Servers ToR Switch Front of Rack Rear of Rack Cool Aisle Hot Aisle ...

Page 37: ...es below when choosing a location The installation location should be able to maintain its temperature within 0 to 45 C 32 to 113 F and its humidity within 5 to 95 non condensing provide adequate space approximately five centimeters or two inches on all sides for proper air flow be accessible for installing cabling and maintaining the device allow the status LEDs to be clearly visible Make sure tw...

Page 38: ...t to rack mount the switch be sure to have the following items available Four mounting screws for each device you plan to install in a rack these are not included Be sure to use the rack mounting screws that are supplied with the rack A screwdriver Phillips or flathead depending on the type of screws used Rack Mount Procedure The switch can be mounted in a rack using the included mounting brackets...

Page 39: ...4 3 Chapter 4 Installing the Switch Figure 4 1 Switch Cooling B2F Airflow SSE X3348TR F2B Airflow SSE X3348T ...

Page 40: ...witch includes plug in power supply and fan tray modules that are installed into its chassis All installed modules must have a matching airflow direction That is all modules must have a front to back F2B airflow direction or all modules must have a back to front B2F airflow direction The airflow direction of PSUs and fan trays is indicated by labels on the modules The fan tray located in the rear ...

Page 41: ...o the Quick Installation Guide For general rack installation information see the chapter Section 4 2 Switch Chassis on page 4 1 Task 3 Install Power Modules and Power On Install power modules connect the power cord then power on The switch supports up to two PSUs that have a matching airflow direction as the installed fan tray Figure 4 2 Installing the Power Modules and Powering On 1 If not alread...

Page 42: ...SSE X3348T SSE X3348TR Switch Installation Manual 4 6 Figure 4 2 Connecting AC Power 1 2 ...

Page 43: ...system LEDs Figure 4 3 When operating normally the PSU1 PSU2 Diagnostic and Fan LEDs should all be on green If any of the LEDs are on amber see Section 8 1 Diagnosing LED Indicators on page 8 1 Go to the section Section 7 1 Understanding the System Status LEDs on page 7 1 Figure 4 3 System LEDs System Status LEDs ...

Page 44: ... this task The serial port s configuration requirements are as follows 9600 bps 8 characters no parity one stop bit 8 data bits and no flow control You can log in to the command line interface CLI using default settings User ADMIN password ADMIN Go to Section 7 2 How to Connect to the Console Port on page 7 2 For information on initial switch configuration refer to the 1 10 and 10 Gigabit Layer 2 ...

Page 45: ...ble for 10GBASE T connections or Category 5 5e or better cable for 1000BASE T connections Connect DAC cables to the QSFP slots Or first install QSFP transceivers and then connect fiber optic cabling to the transceiver ports As connections are made check the port status LEDs to be sure the links are valid Go to Chapter 5 for further details Figure 4 5 Making a Connection to an QSFP Port SFP Transce...

Page 46: ...rovides two AC power supply module options which are listed below SSE X3348T ACPWR front to back airflow SSE X3348TR ACPWR back to front airflow CAUTION The switch includes plug in power supply and fan tray modules that are installed into its chassis All installed modules must have a matching airflow direction That is all modules must have a front to back F2B airflow direction or all modules must ...

Page 47: ... A DC Output 5 VDC 3 A 12 VDC 33 A Power Supply 100 240 VAC 50 60 Hz auto sensing hot pluggable 400 Watts 220V 110V per module Power Consumption 325 9 Watts maximum Maximum Current 6 A 100 VAC 3 A 240 VAC Size W x D x H 220 x 54 5 x 40 25 mm 8 66 x 2 15 x 1 58 inches Table 4 3 Power Supply Module LED LED Condition Status AC Green External AC power is connected to the module Off External power is n...

Page 48: ...rounded through an installed AC PSU when it is connected to a grounded AC power outlet by an AC power cord There are no grounding points on the switch that require a connection to a rack ground or other earth ground How to Connect to AC Power To supply AC power to the switch first verify that the external AC power supply can provide 100 to 240 VAC 50 60 Hz 3 A minimum NOTE For electrical safety pu...

Page 49: ...international use you may need to change the AC power cord You must use a cord set that has been approved for the socket type in your country 3 Insert the plug on the other end of the power cord directly into the socket on the AC PSU 4 Check the LED indicators on the PSU and switch front panel as the unit is powered on to verify that power is being received If not recheck the PSU and power cord co...

Page 50: ...SSE X3348T SSE X3348TR Switch Installation Manual 4 14 Notes ...

Page 51: ...ces isolate faults and change your topology without need for unnecessary time consumption To best manage the physical implementations of your network follow these guidelines Clearly label the opposing ends of each cable Using your building s floor plans draw a map of the location of all network connected equipment For each piece of equipment identify the devices to which it is connected Note the l...

Page 52: ...ort has a valid 10G link Flashing indicates activity on the port On Flashing Amber Port has a valid 100 1000 Mbps link Flashing indicates activity on the port Off The link is down 40G QSFP Ports QX1 4 Link Activity On Flashing Green Port has a valid 40G link Flashing indicates activity on the port Off The link is down 1G RJ 45 Ports Gi1 2 Link Speed On Green Port has a valid 1000 Mbps link On Ambe...

Page 53: ...s also compatible with the switch transceiver support 2 If the QSFP slot is covered with a rubber protective cap remove the cap and keep it for later replacement 3 Insert the transceiver with the optical connector facing outward and the slot connector facing down Note that QSFP transceivers are keyed so they can only be installed in the correct orientation 4 Slide the transceiver into the slot unt...

Page 54: ...twisted pair STP cables with RJ 45 connectors Category 5e 6 6a or 7 cable for 10GBASE T connections Category 5 5e or better cable for 1000BASE T connections Category 5 or better for 100BASE TX connections and Category 3 or better for 10BASE T connections Protection from radio frequency interference emissions Electrical surge suppression Separation of electrical wires switch related or other and el...

Page 55: ...e are connected straight through to pins 1 2 3 and 6 at the other end of the cable Figure 5 3 RJ 45 Connector Table 5 3 10 100BASE TX MDI and MDI X Port Pinouts Pin MDI Signal Namea a The and signs represent the polarity of the wires that make up each wire pair MDI X Signal Name 1 Transmit Data plus TD Receive Data plus RD 2 Transmit Data minus TD Receive Data minus RD 3 Receive Data plus RD Trans...

Page 56: ... 10GBASE T connections as specified in Table 5 2 Also be sure that the length of any twisted pair connection does not exceed the lengths specified in this table The primary cable specified for 10GBASE T is augmented Category 6 Category 6a Other types also work but the specific installation may have to be qualified for 10G operation See the IEEE 802 3an 2006 standard and the relevant TIA specificat...

Page 57: ...orts 1 Attach one end of a twisted pair cable segment to the device s RJ 45 connector 2 Attach the other end to an available port on the switch Make sure each twisted pair cable does not exceed 100 meters 328 ft in length For 10GBASE T connections make sure cables do not exceed the lengths specified in Table 5 4 3 As each connection is made the Link LED on the switch corresponding to each port wil...

Page 58: ...idering safety please make sure that it can function at a temperature that is not less than the recommended maximum operational temperature of the product You must also use an approved Laser Class 1 QSFP transceiver Connecting Cables to SFP SFP Transceiver Ports 1 Remove and keep the port s protective cover When not connected to a fiber cable the cover should be replaced to protect the optics 2 Ch...

Page 59: ...connectors 5 6 DAC Connections Direct Attach Cable DAC is a method of connecting two QSFP interfaces without using optics and fiber cable A fixed length of twinax copper cable is terminated at each end with physically compliant QSFP transceivers that do not include all their normal electronic and optical components The result is a low cost low latency 40G Ethernet solution for short distances idea...

Page 60: ... the link device 2 Plug the other end of the twinax cable into an QSFP slot on the switch 3 Check that the Link LED on the switch turns on green to indicate that the connection is valid Table 5 6 Maximum 40GBASE CR4 40 Gigabit Ethernet Cable Lengths Cable Type Cable Lengths Connector Pre terminated Direct Attach Cable DAC twinax copper cable 1 m 3 28 ft 2 m 6 56 ft 3 m 9 8 ft 5 m 16 4 ft 7 m 22 9 ...

Page 61: ...5 11 Chapter 5 Making Network Connections ...

Page 62: ... 45 10GBASE T RJ 45 connector Ports QX1 4 QSFP 40 Gbps QSFP transceivers 40GBASE CR4 40GBASE SR4 Ports Gi1 2 RJ 45 10 100 1000BASE T RJ 45 connector Buffer Architecture 9 MB packet buffer Aggregate Bandwidth 1280 Gbps Switching Database 128K MAC address entries LEDs System PS1 PS2 Diag Diagnostic Fan Ports 1 54 Status link activity and speed Weight 9 2 kg 20 3 lb with two installed power supply mo...

Page 63: ...ch feature specifications are shown below Forwarding Mode Store and forward Throughput Wire speed Flow Control Full Duplex IEEE 802 3x Half Duplex Back pressure 6 3 Management Features Management feature specifications are shown below In Band Management SSH Telnet SNMP or HTTP Out of Band Management RS 232 DB 9 console port Software Loading HTTP FTP TFTP in band 6 4 Standards Applicable standards ...

Page 64: ...IEEE 802 1Q IEEE 802 1P ISO IEC 8802 3 6 5 Compliances Switch compliances are shown below Emissions EN55022 CISPR 22 Class A EN 61000 3 2 3 FCC Class A CE Mark C Tick Mark Immunity EN 61000 4 2 3 4 5 6 8 11 Safety UL cUL CSA 22 2 NO 60950 1 UL 60950 1 CB IEC EN60950 1 Additional compliance certificates are pending ...

Page 65: ...SSE X3348T SSE X3348TR Switch Installation Manual 6 4 Notes ...

Page 66: ...LEDs The switch includes a display panel of key system LED indicators Figure 7 1 The LEDs which are located on the front panel are shown below and described in the following table Figure 7 1 System Status LEDs Table 7 1 System Status LEDs LED Condition Status PSU1 PSU2 On Green Power supply 1 2 is installed and operating normally On Amber The power supply has detected a fault Off The power supply ...

Page 67: ...oks or other PCs that do not have a DB 9 COM port use a USB to male DB 9 adapter cable not included with the switch The following table describes the pin assignments used in the console cable The serial port s configuration requirements are as follows Default Baud rate 9600 bps Character Size 8 Characters Parity None Stop bit One Data bits 8 Flow control none Figure 7 2 Console Port Table 7 2 Cons...

Page 68: ... cable to the Console port on the switch 3 Configure the PC s COM port required settings using VT 100 terminal emulator software such as HyperTerminal running on the management PC 4 Log in to the command line interface CLI using default settings User ADMIN Password ADMIN For a detailed description of connecting to the console and using the switch s command line interface CLI refer to the Supermicr...

Page 69: ...the switch can be used to restart the device and set the configuration back to factory default values Use a long thin object such as the end of a paperclip to depress the Reset button One push of the button restarts the system software using default values Figure 7 4 Reset Button Reset Button ...

Page 70: ... cord or PSU However if the switch powers off after running for a while check for loose power connections power losses or surges at the power outlet If you still cannot isolate the problem the PSU may be defective Table 8 1 Troubleshooting Chart Symptom Action PSU1 PSU2 LED is Off Check connections between the PSU the power cord and the wall outlet Contact your dealer for assistance PSU1 PSU2 LED ...

Page 71: ...gement agent in the switch through a connection to any port using Telnet a web browser or other network management software tools However you must first configure the switch with a valid IP address subnet mask and default gateway If you have trouble establishing a link to the management agent check to see if you have a valid network connection Then verify that you entered the correct IP address Al...

Page 72: ...SSE X3348T SSE X3348TR Switch Installation Manual 8 3 ...

Page 73: ...cted to result in significant injury or loss of life or catastrophic property damage Accordingly Supermicro disclaims any and all liability and should buyer use or sell such products for use in such ultra hazardous applications it does so entirely at its own risk Furthermore buyer agrees to fully indemnify defend and hold Supermicro harmless for and against any and all claims demands actions litig...

Page 74: ...SSE X3348T SSE X3348TR Switch Installation Manual ...