Global Installation Guide for Suntech 
Power Standard Photovoltaic Module 

Version 20200601 

Summary of Contents for STP335-A

Page 1: ...Global Installation Guide for Suntech Power Standard Photovoltaic Module Version 20200601 ...

Page 2: ...anical Installation 4 Selecting the location General installation Installation method Attachment guidelines Electrical Installation 10 General installation Grounding Maintenance 12 Please read carefully This document is binding for any warranty case Any installed PV system less than 500m from coastline please refer to the Near coast installation manual 1 ...

Page 3: ...taic solar modules convert light energy to direct current electrical energy They are designed for outdoor use Modules can be ground mounted mounted on rooftops The proper design of support structures lies within the responsibility of the system designers and installers When installing the system abide to all local regional and national statutory regulations Obtain a building permit if necessary Th...

Page 4: ...s of Isc and Voc marked on this module should be multiplied by a factor of 1 25 when determining component voltage ratings conductor current ratings minimum factor of fuse sizes and size of controls connected to the PV output Only use same connectors to connect modules to form a string or connect to another device Removing the connectors will void the warranty Fire Safety Consult your local author...

Page 5: ...ucture approved for your system design In regions with heavy snowfall in winter select the height of the mounting system so that the lowest edge of the module is not covered by snow for any length of time In addition ensure that the lowest portion of the module is placed high enough so that it is not shaded by plants trees or damaged by ground soil moved by or through the air For ground mounting s...

Page 6: ...calculation and security of the system With different installation methods the modules have been tested to withstand the loads of 2400 Pa 3800 Pa and 5400 Pa according to IEC 61215 standard equivalent of 1600 Pa 0 232psi 2500 Pa 0 363 psi and 3600 Pa 0 522 psi respectively under UL 1703 standard For each installation modules can be installed either in portrait or landscape mode If you integrate ou...

Page 7: ...tech Standard Module Type using 166 mm solar cell Module Dimension Length Width Thickness B60 W Half cell solar module 1756 mm 1039 mm 35 mm 1776 mm 1052 mm 35 mm B72 V Half cell solar module 2095 mm 1039 mm 35 mm 2115 mm 1052 mm 35 mm B78 V Half cell solar module 2204 mm 1039 mm 35 mm Suntech Standard Module Type using 180 mm solar cell Module Dimension Length Width Thickness C72 V Half cell sola...

Page 8: ... Series A20 W Series A21 W Series A60 W Series B60 W Series 4 bolts installation Test load positive 5400Pa negative 3800Pa Design load positive 3600Pa negative 2533Pa Safety factor 1 5 16 T Series 24 V Series 4 bolts installation Test load positive 5400Pa negative 2400Pa Design load positive 3600Pa negative 1600Pa Safety factor 1 5 72 V Series 78 V Series A72 V Series A78 V Series B72 V Series B78...

Page 9: ...sitive 1600Pa negative 1600Pa Safety factor 1 5 Clamp zone A 1 4 long frame length 50 mm 16 T Series 20 W Series 24 V Series 60 W Series A16 T Series A20 W Series A21 W Series A60 W Series B60 W Series 4 clamps installation Test load positive 5400Pa negative 3800Pa Design load positive 3600Pa negative 2533Pa Safety factor 1 5 16 T series L 180 mm 20 W series L 180 mm 24 V series L 280 mm A16 T ser...

Page 10: ...A60 W series L 200 mm B60 W series L 200 mm A72 V series L 300 mm B72 V series L 380 mm A78 V series L 390 mm Clamp zone A 200 mm 60 W Series 72 V Series 78 V Series A20 W Series A21 W Series A60 W Series B60 W Series A72 V Series B72 V Series A78 V Series 4 clamps installation Test load positive 5400Pa negative 2400Pa Design load positive 3600Pa negative 1600Pa Safety factor 1 5 B78 V series L 49...

Page 11: ...Pa Safety factor 1 5 Clamp zone A1 100 mm A2 200 mm 16 T Series 20 W Series 24 V Series 60 W Series 72 V Series 78 V Series A16 T Series A20 W Series A21 W Series A60 W Series B60 W Series A72 V Series B72 V Series C72 V Series A78 V Series Insertion installaiton Test load positive 2400Pa negative 2400Pa Design load positive 1600Pa negative 1600Pa Safety factor 1 5 16 T Series 20 W Series A60 W Se...

Page 12: ...es 20 W Series 21 W Series 60 W Series 66 W Series A16 T Series A20 W Series A21 W Series A60 W Series A66 W Series B60 W Series 4 clamps short end Test load positive 5400Pa negative 1600Pa Design load positive 3600Pa negative 1067Pa Safety factor 1 5 A0 1 4 short frame length 50mm 24 V Series 72 V Series A24 V Series A72 V Series 4 clamps mixed mounting Test load positive 2400Pa negative 2400Pa D...

Page 13: ...vant for 2400 Pa The mounting holes reserved for tracker mounting system with special accessories Electrical Installation Electrical property Module under standard testing conditions of irradiance of 1000W m2 cell temperature of 25 C and air mass of AM1 5 maximum over current protection is 15A Under normal conditions a Photovoltaic module is likely to experience conditions that produce more curren...

Page 14: ...oefficient of the selected module Voc Refer to corresponding datasheet Dimension Maximum system voltage Maximum number of modules 1658 992 6mm 1500V 35 1968 992 6mm 1500V 29 Note The data above are calculated based on the temperature in Wuxi The maximum number of modules that can be connected in series within a string for the specific project must be calculated based on the actual local temperatur...

Page 15: ...capacity of the connectors must be selected to suit the maximum system short circuit current The recommended cable is PV wire with a cross section of at least 4mm2 Caution do not secure the cables too tight Any cable damage caused by cable management system is not covered under Suntech s warranty Always refer to the cable manufacturer s bending radius which includes the radius just behind the conn...

Page 16: ...frames metal exposed to touch are always grounded Suntech recommends always refer to local state and national code requirements for PV module grounding Suntech highly recommends negative grounding if it s allowed by local authorities When attaching the frame grounding hardware and wire to the frame it must be placed corresponding to the ground symbol stamped location to ensure proper electrical co...

Page 17: ...olled pollution is voiding the warranty or not cleaning the modules in time voids the warranty Check the electrical grounding and mechanical connections every six months to verify that they are clean secure undamaged and free of corrosion Or else the warranty may be voided In the event of a ground fault condition NEVER wash or spray modules with water until ground fault has been identified correct...

Page 18: ...20200601 版本 No 目录 安全指南 15 总体安全 操作安全 安装安全 消防安全 产品鉴别 16 机械安装 16 场地选择 常规安装 安装方式 安装指南 电气安装 23 常规安装 接地 维护 25 请仔细阅读 该文件对任何保修情况都具有约束力 距海岸线 500 米内安装光伏系统 请参考近海安装手册 16 1 ...

Page 19: ...能使用与之相匹配的设备 连接器 接线和支架 请勿使用反光镜或其他放大镜将阳光直接聚焦于组件上 在183 cm或更高处作业时必须有防坠落保护措施 遵守职业安全和健康法案 OSHA 或当地有关坠落保护的安全规定 仅UL 请勿坐于 站立于 踩踏或行走于组件之上 包括支架 除自然降雨或者阶段性组件清洗外 请勿将组件的任何部位浸泡在水中或者持续用水冲击组件 操作安全 请勿抓住组件接线盒或引出线提起组件 请勿使组件掉落或使物体坠落于组件上 请勿在组件上放置任何重物或尖锐物体 组件要轻拿轻放 不恰当的运输或安装可能损坏组件并使质保无效 请勿拆解组件及组件上的铭牌 请勿在组件玻璃或背板上使用油漆或粘合剂 为避免损坏背板和电池 请勿刮擦 撞击或使背板产生凹痕 运输时 请勿直接施压于组件的背板或玻璃 请勿在边框上钻孔 这可能破坏边框的强度 导致边框生锈并使质保无效 请勿刮擦支架的阳极处理层 除了组件背面接地连...

Page 20: ...伏和1500伏 而其它UL产品为600伏 检查您的产品铭牌或联系您的当地代表获得详细信息 2 条形码 每个单一的组件有一个专属的序列号 该序列号有18位数字 第15位和第16位是周数编码 第17位和第18位是年份编码 例如 STP xxxxxxxxxxxxxx2414 表示组件在2014年第24周组装和检测 每个组件只有一个条形码 它将永远黏贴在组件内部 并且可以从组件前 部顶端看到 该条形码在层压前被插入 条形码标签 3 分档标签 该标签上显示了四个不同的标志 QC Pass 确保组件已通过了质量控制检查 HIPOT 表示已通过了绝缘测试 最后根据组件 的输出电流将组件筛选 由相应的 Ix 符号表示 其中x表示值1 2和3为使组件串获得最优性能 建议只在一个串中选用 Ix 类别相同的组件 例如只有I2组件 条形码 的作用请参考上述 条形码 介绍 分档标签 请勿取下任何标签 取下任一张标签...

Page 21: ...顶前 请确保屋顶的结构合理 另外 任何需要安装组件的屋顶必须密封处理防止漏水 组件表面上积聚的灰尘可能破坏组件性能 安装组件的倾斜角度不宜低于10 以便灰尘被雨水冲刷 倾斜角度过小组件需要更频繁 的清洗 两个组件间的距离建议最少为2厘米 防止热膨胀产生的损坏 将组件安装于立柱上时 选择的立柱和组件支撑结构必须可以承受当地可能的风载荷和雪载荷 确保组件不会承受超过最大允许载荷的风载和雪载 而且不会承受支撑结构热膨胀产生力 不允许组件重叠或者超出屋顶 请参考下 列安装方式获得详细信息 安装方式 组件可以使用安装孔 夹具 或滑槽被安装在支架上 必须根据下列样例安装组件 没有根据下列说明安装组件 会使质保无效 每个夹具最小建议长度为50 mm 组件可以采用横向和纵向安装 组件必须稳固固定在支架上 以便承受相应的正负压 安装人员必须负责确保用于固定组件的夹具有足够的强度 安装指南 根据载荷需求选择合...

Page 22: ...组件 2008 mm 1002 mm 35 mm 2000 mm 992 mm 35 mm 78 V系列 半片组件 2166 mm 992 mm 35 mm 尚德组件型号 使用158 75 mm电池片 组件尺寸 长 宽 厚 A16 T系列 半片组件 1354 mm 1002 mm 35 mm A20 W系列 半片组件 1680 mm 1002 mm 35 mm A21 W系列 半片组件 1762 mm 1002 mm 35 mm A60 W系列 半片组件 1684 mm 1002 mm 35 mm A72 V系列 半片组件 2008 mm 1002 mm 35 mm A78 V系列 半片组件 2178 mm 1002 mm 35 mm 尚德组件型号 使用166 mm电池片 组件尺寸 长 宽 厚 B60 W系列 半片组件 1756 mm 1039 mm 35 mm B72 V系列 半片组件 ...

Page 23: ...1600Pa 安全系数 1 5 60 W 系列 A20 W 系列 A21 W 系列 A60 W 系列 B60 W 系列 四螺栓安装 测试载荷 正压 2400Pa 负压 2400Pa 设计载荷 正压 1600Pa 负压 1600Pa 安全系数 1 5 20 W 系列 60 W 系列 A16 T 系列 A20 W 系列 A21 W 系列 A60 W 系列 B60 W 系列 四螺栓安装 测试载荷 正压 5400Pa 负压 3800Pa 设计载荷 正压 3600Pa 负压 2533Pa 安全系数 1 5 16 T 系列 24 V 系列 四螺栓安装 测试载荷 正压 5400Pa 负压 2400Pa 设计载荷 正压 3600Pa 负压 1600Pa 安全系数 1 5 72 V 系列 78 V 系列 A72 V 系列 B72 V 系列 A78 V 系列 B78 V 系列 C72 V 系列 21 ...

Page 24: ... 系列 A20 W 系列 A21 W 系列 A60 W 系列 四夹具安装 测试载荷 正压 2400Pa 负压 2400Pa 设计载荷 正压 1600Pa 负压 1600Pa 安全系数 1 5 夹具区 A 1 4长边框长度 50 mm 16 T 系列 20 W 系列 24 V 系列 60 W 系列 A16 T 系列 A20 W 系列 A21 W 系列 A60 W 系列 B60 W 系列 四夹具安装 测试载荷 正压 5400Pa 负压 3800Pa 设计载荷 正压 3600Pa 负压 2533Pa 安全系数 1 5 16 T系列 L 180 mm 20 W系列 L 180 mm 24 V系列 L 280 mm A16 T系列 L 180 mm 夹具区 A 300 mm 16 T 系列 20 W 系列 24 V 系列 A16 T 系列 22 ...

Page 25: ...00 mm A21 W系列 L 220 mm A60 W系列 L 200 mm B60 W系列 L 200 mm A72 V系列 L 300 mm B72 V系列 L 380 mm A78 V系列 L 390 mm 夹具区 A 200 mm 60 W 系列 72 V 系列 78 V 系列 A20 W 系列 A21 W 系列 A60 W 系列 B60 W 系列 A72 V 系列 B72 V 系列 A78 V 系列 四夹具安装 测试载荷 正压 5400Pa 负压 2400Pa 设计载荷 正压 3600Pa 负压 1600Pa 安全系数 1 5 B78 V系列 L 490 mm C72 V系列 L 380 mm 夹具区 A 200 mm B78 V 系列 C72 V 系列 23 ...

Page 26: ...测试载荷 正压 5400Pa 负压 3800Pa 设计载荷 正压 3600Pa 负压 2533Pa 安全系数 1 5 夹具区 A1 100 mm A2 200 mm 16 T 系列 20 W 系列 24 V 系列 60 W 系列 72 V 系列 78 V 系列 A16 T 系列 A20 W 系列 A21 W 系列 A60 W 系列 B60 W 系列 A72 V 系列 B72 V 系列 A78 V 系列 滑槽安装 测试载荷 正压 2400Pa 负压 2400Pa 设计载荷 正压 1600Pa 负压 1600Pa 安全系数 1 5 16 T 系列 20 W 系列 滑槽安装 测试载荷 正压 5400Pa 负压 3800Pa 设计载荷 正压 3600Pa 负压 2533Pa 安全系数 1 5 夹具区 A 100mm 16 T 系列 20 W 系列 24 V 系列 A60 W 系列 B60 W 系列...

Page 27: ...21 W 系列 60 W 系列 66 W 系列 A16 T 系列 A20 W 系列 A21 W 系列 A60 W 系列 A66 W 系列 B60 W 系列 四压块 短边安装 测试载荷 正压 5400Pa 负压 1600Pa 设计载荷 正压 3600Pa 负压 1067Pa 安全系数 1 5 A0 1 4 短边框长度 50mm 24 V 系列 72 V 系列 A24 V 系列 A72 V 系列 四压块混合 安装 测试载荷 正压 2400Pa 负压 2400Pa 设计载荷 正压 1600Pa 负压 1600Pa 安全系数 1 5 A 40mm A0 1 短边框长度 50mm A1 280 420mm 16 T 系列 20 W 系列 21 W 系列 60 W 系列 66 W 系列 A16 T 系列 A20 W 系列 A21 W 系列 A60 W 系列 A66 W 系列 B60 W 系列 25 ...

Page 28: ...A0 1 4 短边边框长度 50mm A1 360 560mm 24 V 系列 72 V 系列 78 V 系列 A24 V 系列 A72 V 系列 A78 V 系列 B72 V 系列 任何情况下 组件夹具都不能触碰到前端玻璃或使支架变形 以避免组件夹具和滑槽遮挡电池片 夹具不能封住或盖住组件支架上的排水 孔 2400 Pa 3800 Pa和5400 Pa为IEC标准下的载荷 适用于5400 Pa的安装方式可覆盖3800 Pa和2400 Pa 适用于3800 Pa的安装方式可覆盖2400 Pa 安装孔位为tracker单轴安装支架预留 需搭配tracker专用配件安装使用 26 ...

Page 29: ...致质保无效 不建议在同一个系统中使用配置不同的组件 必须将多余的电缆整理或充分固定 例如 使用非金属绑线将其固定在支架上 组件电缆线 连接器和接线盒不应长时间接触水 雨 雪或浸泡于水中 IP65 67 68 对于需要高操作电压的应用而言 可以将多个组件串联形成组件串 系统电压即等同于每个组件的电压的总和 对于需要高操作电流的应用而言 可以将多个组件串并联 系统电流即等同于每个组件串的电流总和 根据标准 组件的最大系统电压为600伏或1000伏或1500伏 串联连接的组件最大数目由系统设计 所用的逆变器类型和环境条件决定 根据组件最大串联保险丝额定值和当地电气安装规范 如果尚德光伏组件并联 需要装配合适的串保险丝 对于并联连接的组件没有数量上的特殊限制 组件的数量由系统设计参数 例如电流或功率输出决定 27 ...

Page 30: ...再生的能源系统接入电网的政策各不相同 请始终向有资质的系统设计师或集成商咨询相关建议 通常需要安装许可证和当地机构进行检查和批准 对于较大规模的安装 尚德建议采用符合当地要求和规定的防雷法 当安装完成并连接到电网后 请准备一份专业的文件交给业主 包括所需的安装协议 同时为业主提供一份清晰的系统文档 至少包 括以下资料 用户指南 系统配置 数据表 性能预期 电气系统数据 如符合IEC 62446 IEC 60364 6最低要求的安装测试报告的副本 当接入单个逆变器中的陈列较多时 需要考虑随陈列曾加引起的绝缘电阻的降低 接地 对于接地和连接要求 请参考地区性和国家性安全和电气标准 如果要求接地 请为接地接线使用建议的连接器类型 本册中的接地指的是组件支架接地 如果要求接地 确保组件支架 暴露的 可接触的金属部分 始终是接地的 尚德建议始终参考当地和国家有关光伏组件接地的规范和要求 如果当地机构...

Page 31: ...况 经常进行清洁 清除表面所有有机物 有污渍或污染物的组件可能会降低系统的发电量 清 洁组件表面时请使用清水和柔软的非磨蚀性海绵或布料 也可以使用温和的 非磨蚀性的清洁剂去除顽固污渍 不受控制的污染以及未及时清洁组件都将会使质保无效 每隔6个月检查电气 接地和机械连接部位 确保它们干净 安全 没有损坏以及无生锈 否则将会使质保无效 在出现接地故障时 在由授权的太阳能逆变器服务人员校正并在逆变器完全运行前 切勿使用水清洗或喷洒组件 这可能导致点击事 故或严重的安全问题 若有任何问题 请向专业太阳能服务供应商咨询并询求建议 注意 请遵守太阳能制造商对系统中所使用的所有组件的维护说明 例如支架 充电调节器 逆变器 电池等 无锡尚德太阳能电力有限公司 地址 江苏省无锡市新吴区新华路 9 号 客户服务热线 86 400 8888 009 传真 96 510 8534 3321 邮箱 services...