Sun Fire

6800 System and

Sun Fire Cabinet

Rackmount Placement Matrix

Part No. 816-2062-18
June 2003

, Revision 01

Summary of Contents for Fire 6800

Page 1: ...0 Network Circle Santa Clara CA 95054 U S A Send comments about this document to http www sun com hwdocs feedback Sun Fire 6800 System and Sun Fire Cabinet Rackmount Placement Matrix Part No 816 2062...

Page 2: ...osystems Inc 4150 Network Circle Santa Clara CA 95054 Etats Unis Tous droits r serv s Ce produit ou document est prot g par un copyright et distribu avec des licences qui en restreignent l utilisation...

Page 3: ...n Fire 6800 System Rackmount Matrix 2 1 3 Sun Fire 4810 System Rackmount Placement Matrix 3 1 4 Sun Fire 4800 System Rackmount Placement Matrix 4 1 5 Sun Fire 3800 System Rackmount Placement Matrix 5...

Page 4: ...4 Sun Fire 6800 System and Sun Fire Cabinet Rackmount Placement Matrix June 2003...

Page 5: ...FIGURE A 3 RTU and RTS Modules A 3 FIGURE A 4 Sun Fire 6800 System and One Two or Three Sun StorEdge D240 Media Trays A 4 FIGURE A 5 Sun Fire 6800 System and One Sun StorEdge D240 Media Tray and One...

Page 6: ...0 Systems Two Sun StorEdge D240 Media Trays and One or Two Sun StorEdge A1000 Arrays or Sun StorEdge D1000 Arrays or Sun StorEdge T3 Arrays A 12 FIGURE A 15 Three Sun Fire 3800 Systems and Three Sun S...

Page 7: ...rEdge D1000 or A1000 or T3 Array 3 2 TABLE 3 3 Sun Fire 4810 System With Sun StorEdge D240 Media Trays and Sun StorEdge T3 Dual Array 3 3 TABLE 3 4 Sun Fire 4810 System With Sun StorEdge D240 Media Tr...

Page 8: ...Arrays 5 4 TABLE 5 5 Sun Fire 3800 System With Sun StorEdge D240 Media Trays and Sun StorEdge A1000 or D1000 Array and Sun StorEdge T3 Array 5 5 TABLE 5 6 Sun Fire 3800 System With Sun StorEdge D240...

Page 9: ...r wiring diagrams for connecting power cables between the respective systems and storage products to the redundant transfer unit s RTU within the cabinet Who Should Use This Book Caution This book is...

Page 10: ...vices are mounted Appendix A describes all of the power wiring configurations Related Documentation Accessing Sun Documentation You can view print or purchase a broad selection of Sun documentation in...

Page 11: ...areas can result in serious injury or death Caution Improper handling by unqualified personnel can cause serious damage to this equipment Unqualified personnel who tamper with this equipment may be he...

Page 12: ...Placement Matrix June 2003 For system compliance class and conformity information refer to the system installation guide that came with your system Procedures contained in this document must be perfor...

Page 13: ...they may touch dangerous voltage points or short out components that could result in fire or electric shock Refer servicing of equipment to qualified personnel To protect both yourself and the equipme...

Page 14: ...roperly grounded power outlets as described in the installation guides Caution DO NOT make mechanical or electrical modifications to the system or the cabinet Sun Microsystems is not responsible for r...

Page 15: ...depending on what system is installed in the Sun Fire Cabinet Sun Fire cabinet N A 325 lbs 147 kg 2 to 4 N A N A Sun Fire 6800 system 31 1030 lbs 467 2 kg 4 1 N A Sun Fire 4810 system 21 326 lbs 147...

Page 16: ...ement Matrix June 2003 Caution To prevent personal injury use a computer equipment mechanical lift and two people to move any system or array weighing more than 50 lbs 22 7 kg safely into the cabinet...

Page 17: ...acks When considering third party rack mounting the third party thermal guidelines and the third party rack mounting guidelines should be reviewed The Sun Fire 280R Sun Enterprise 420R Sun Netra T1 AC...

Page 18: ...re Cabinet Rackmount Placement Matrix June 2003 Note Before you begin carefully read each of the procedures in this manual If you have not performed similar operations on comparable equipment do not a...

Page 19: ...2 1 CHAPTER 2 Sun Fire 6800 System Rackmount Matrix This chapter describes where to mount various storage devices within the Sun Fire 6800 system cabinet FIGURE 2 1 Sun Fire 6800 System Front View...

Page 20: ...ck Hole Numbers Used To Mount Rails Rack Holes To Mount Device Used Rack Units Available Rack Units Sun Fire 6800 system 31 Sun StorEdge D240 media tray 1 110 113 111 112 2 Sun StorEdge D240 media tra...

Page 21: ...3 Sun Fire 6800 System With Sun StorEdge D240 Media Tray and Sun StorEdge T3 Array System Storage Device Rack Hole Numbers Used To Mount Rails Rack Holes To Mount Device Used Rack Units Available Rac...

Page 22: ...2 4 Sun Fire 6800 System and Sun Fire Cabinet Rackmount Placement Matrix June 2003...

Page 23: ...ER 3 Sun Fire 4810 System Rackmount Placement Matrix This chapter describes where to mount various storage devices within the Sun Fire 4810 system cabinet FIGURE 3 1 Sun Fire 4810 Rackmounted System F...

Page 24: ...Mount Rails Rack Holes To Mount Device Used Rack Units Available Rack Units RTU Rear 1 7 3 RTU Front for reference only 10 16 3 Sun Fire 4810 system 20 22 21 Sun StorEdge D240 media tray 1 110 113 111...

Page 25: ...Sun StorEdge D240 media tray 2 104 107 105 106 2 Sun StorEdge T3 dual array 85 90 100 85 90 7 Total 38 0 See FIGURE A 12 for power wiring diagram for TABLE 3 4 TABLE 3 4 Sun Fire 4810 System With Sun...

Page 26: ...112 2 2 Sun StorEdge D240 media tray 2 104 107 105 106 2 Sun StorEdge D1000 array or Sun StorEdge A1000 array 84 87 86 89 4 4 Sun StorEdge D1000 array or Sun StorEdge A1000 array 96 99 98 101 4 Total...

Page 27: ...ER 4 Sun Fire 4800 System Rackmount Placement Matrix This chapter describes where to mount various storage devices within the Sun Fire 4800 system cabinet FIGURE 4 1 Sun Fire 4800 Rackmounted System F...

Page 28: ...ays Rack Hole Numbers Used To Mount Rails Rack Holes To Mount Device Used Rack Units Available Rack Units RTU Rear 1 7 3 RTU Front for reference only 10 16 3 Sun Fire 4800 system 21 24 66 68 18 Sun Fi...

Page 29: ...Used To Mount Rails Rack Holes To Mount Device Used Rack Units Available Rack Units RTU Rear 1 7 3 RTU Front 10 16 3 Sun Fire 4800 system 21 24 66 68 18 Sun Fire 1 2 RU filler panel 71 tabs down Sun S...

Page 30: ...4 Sun StorEdge T3 array 2 89 93 90 93 4 4 Total 35 33 37 3 or 5 or 1 See FIGURE A 12 for power wiring diagram for TABLE 4 5 and TABLE 4 6 TABLE 4 5 Sun Fire 4800 System With Sun StorEdge D240 Media Tr...

Page 31: ...dge T3 Array Rack Hole Numbers Used To Mount Rails Rack Holes To Mount Device Used Rack Units Available Rack Units RTU Rear 1 7 3 RTU Front 10 16 3 Sun Fire 4800 system 21 24 66 68 18 Sun Fire 1 RU fi...

Page 32: ...4 6 Sun Fire 6800 System and Sun Fire Cabinet Rackmount Placement Matrix June 2003...

Page 33: ...5 Sun Fire 3800 System Rackmount Placement Matrix This chapter describes where to mount various storage devices within the Sun Fire 3800 system cabinet FIGURE 5 1 Two Sun Fire 3800 Rackmounted Systems...

Page 34: ...re 3800 systems are installed you must always have a 1 2 RU metal filler panel in the space above it Empty space in the cabinet must be filled with filler panels to prevent the recycling of heated exh...

Page 35: ...ystem See TABLE 5 1 9 Sun StorEdge D240 media tray 1 110 113 111 112 2 Sun StorEdge D240 media tray 2 104 107 105 106 2 Total 19 19 TABLE 5 3 Sun Fire 3800 System With Sun StorEdge D240 Media Trays an...

Page 36: ...Numbers Used To Mount Rails Rack Holes To Mount Device Used Rack Units Available Rack Units RTU Rear 1 7 3 3 3 RTU Front 10 16 3 3 3 Sun Fire 3800 system See TABLE 5 1 9 9 9 Sun StorEdge D240 media t...

Page 37: ...rray and Sun StorEdge T3 Array Rack Hole Numbers Used To Mount Rails Rack Holes To Mount Device Used Rack Units Available Rack Units RTU Rear 1 7 3 RTU Front 10 16 3 Sun Fire 3800 system See TABLE 5 1...

Page 38: ...e D240 Media Trays and Sun StorEdge T3 Dual Array Unit Rack Hole Numbers Used To Mount Rails Rack Holes To Mount Device Used Rack Units Available Rack Units RTU Rear 1 7 3 RTU Front 10 16 3 Sun Fire 3...

Page 39: ...rays Rack Hole Numbers Used To Mount Rails Rack Holes To Mount Device Used Rack Units Available Rack Units RTU Rear 1 7 3 3 3 RTU Front 10 16 3 3 3 Sun Fire 3800 system See TABLE 5 1 9 9 9 Sun StorEdg...

Page 40: ...To Mount Rails Rack Holes To Mount Device Used Rack Units Available Rack Units RTU Rear 1 7 3 3 3 RTU Front 10 16 3 3 3 Sun Fire 3800 system 1 See TABLE 5 1 9 9 9 Sun Fire 3800 system 2 See TABLE 5 1...

Page 41: ...Rack Holes To Mount Device Used Rack Units Available Rack Units RTU Rear 1 7 3 3 3 RTU Front 10 16 3 3 3 Sun Fire 3800 system 1 See TABLE 5 1 9 9 9 Sun Fire 3800 system 2 See TABLE 5 1 9 9 9 Sun StorE...

Page 42: ...k Hole Numbers Used To Mount Rails Rack Holes To Mount Device Used Rack Units Available Rack Units RTU Rear 1 7 3 3 RTU Front 10 16 3 3 Sun Fire 3800 system 1 See TABLE 5 1 9 9 Sun Fire 3800 system 2...

Page 43: ...StorEdge T3 Dual Array Unit Rack Hole Numbers Used To Mount Rails Rack Holes To Mount Device Used Rack Units Available Rack Units RTU Rear 1 7 3 RTU Front 10 16 3 Sun Fire 3800 system 1 See TABLE 5 1...

Page 44: ...rays Rack Hole Numbers Used To Mount Rails Rack Holes To Mount Device Used Rack Units Available Rack Units RTU Rear 1 7 3 RTU Front 10 16 3 Sun Fire 3800 system 1 SEE Table 5 1 8 5 Sun Fire 3800 syste...

Page 45: ...Fire 4800 3800 Systems Rackmount Placement Matrix This chapter describes where to mount various storage devices within the Sun Fire 4800 3800 systems cabinet FIGURE 6 1 Sun Fire 4800 3800 Rackmounted...

Page 46: ...el in the space above it Empty space in the cabinet must be filled with filler panels to prevent the recycling of heated exhausted air from the rear of the system Filler panels range from 1 RU to 5 RU...

Page 47: ...media tray 1 110 113 111 112 2 Sun StorEdge D240 media tray 2 104 107 105 106 2 Total 37 1 TABLE 6 1 Sun Fire 4800 3800 Systems With One or Two Sun StorEdge D240 Media Trays Continued Rack Hole Number...

Page 48: ...6 4 Sun Fire 6800 System and Sun Fire Cabinet Rackmount Placement Matrix June 2003...

Page 49: ...fer Units RTUs with four Redundant Transfer Switches RTSs Two totally independent AC power sources are needed for input power redundancy The AC power sources must be derived from independent power com...

Page 50: ...e front on the left and one in the rear of the system on the left FIGURE A 2 Connecting the alternate RTS units to outlets that use the same power source as the default RTS units is not supported and...

Page 51: ...A Functional Power and Data Wiring Diagrams A 3 FIGURE A 3 RTU and RTS Modules RTS0 module J1 is only for use with the Sun Fire 6800 system only J2 is never to be used J11 J12 J1 J3 J5 J7 J9 J8 J10 J...

Page 52: ...media tray 2 Fan power Media tray power System power Note J11 J12 are unswitched Note Switched outlet callouts are for reference only Power connectionscan be with any switched outlet of the same RTU...

Page 53: ...J3 J5 J7 J9 J1 RTU rear 1 J11 J3 J5 J7 J9 J1 J12 J4 J6 J8 J10 RTS0 RTS1 RTS3 RTS2 RTF1 RTF0 Sun StorEdge A1000 array or Sun StorEdge D1000 array or Sun StorEdge T3 array Fan power Media tray power Sys...

Page 54: ...configurations with two RTU assemblies and one AC power sources there will be two cables to connect one in the front on the left and one in the rear of the system on the left FIGURE A 7 Connecting the...

Page 55: ...AC Power Sources In configurations with one RTU assembly and one AC power sources there will be only one cable to connect in the rear of the system on the left FIGURE A 9 FIGURE A 9 One RTU Assembly a...

Page 56: ...r 1 J11 J3 J5 J7 J9 J1 J12 J4 J6 J8 J10 J2 RTS0 RTS1 Sun StorEdge D240 media tray 2 RTF0 RTF1 Fan power Media tray power System power Note J11 J12 are unswitched Note Switched outlet callouts are for...

Page 57: ...rear 1 J11 J3 J5 J7 J9 J1 J12 J4 J6 J8 J10 J2 RTS0 RTS1 RTF1 RTF0 Sun StorEdge A1000 array or Sun StorEdge D1000 array or Sun StorEdge T3 array Fan power Media tray power System power Note J11 J12 are...

Page 58: ...2 J11 J3 J5 J7 J9 J1 RTU rear 1 J11 J3 J5 J7 J9 J1 J12 J4 J6 J8 J10 J2 RTS0 RTS1 RTS3 RTS2 Sun StorEdge A1000 array or Sun StorEdge D1000 array or Sun StorEdge T3 array Sun StorEdge A1000 array or Sun...

Page 59: ...n Fire 3800 system 2 RTU front 2 J12 J4 J6 J8 J10 J2 J11 J3 J5 J7 J9 J1 RTU rear 1 J11 J3 J5 J7 J9 J1 J12 J4 J6 J8 J10 J2 RTS0 RTS1 RTS3 RTS2 RTF0 RTF1 Fan power Media tray power System power Note J11...

Page 60: ...11 J3 J5 J7 J9 J1 RTS3 RTS2 RTU rear 1 J11 J3 J5 J7 J9 J1 J12 J4 J6 J8 J10 J2 RTS0 RTS1 RTF0 RTF1 Sun StorEdge A1000 array or Sun StorEdge D1000 array or Sun StorEdge T3 array Sun StorEdge A1000 array...

Page 61: ...front 2 J12 J4 J6 J8 J10 J2 J11 J3 J5 J7 J9 J1 RTS3 RTS2 RTU rear 1 J11 J3 J5 J7 J9 J1 J12 J4 J6 J8 J10 J2 RTS0 RTS1 RTF0 RTF1 Sun Fire 3800 system 3 Y power Sun StorEdge D240 media tray 3 Note J11 J...

Page 62: ...ont 2 J12 J4 J6 J8 J10 J2 J11 J3 J5 J7 J9 J1 RTU rear 1 J11 J3 J5 J7 J9 J1 J12 J4 J6 J8 J10 J2 RTS0 RTS1 RTS3 RTS2 Sun Fire 3800 system RTF1 RTF0 Fan power Media tray power System power Note J11 J12 a...

Page 63: ...connects to B of A B splitter for SC1 Connector P2 connects to B of A B splitter for SC0 Connectors A of both A B splitter cables are for NTS tip console con nections RTU front 2 RTS2 RTS3 RTU rear 1...

Page 64: ...or P3 connects to B of A B splitter for SC1 Connector P2 connects to B of A B splitter for SC0 Connectors A of both A B splitter cables are for NTS tip console con nections RTU front 2 RTS3 RTS2 RTU r...

Page 65: ...s to B of A B splitter for SC1 Connector P2 connects to B of A B splitter for SC0 Connectors A of both A B splitter cables are for NTS tip console con nections RTU front 2 RTS2 RTS3 RTU rear 1 RTS1 RT...

Page 66: ...A 18 Sun Fire 6800 System and Sun Fire Cabinet Rackmount Placement Matrix June 2003...

Reviews: