   User instruction for  SEM210X  electrical apparatus for use in a hazardous area. 
   Important:  Read and understand this document before any installation.

 ATEX 

& IECEx 

Instructions

For safe installation of the SEM210X in hazardous areas the following instructions must be observed. The transmitter must be installed by 
competent  personnel,  who  are  familiar  with  national  and  international  laws,  directives  and  standards  that  apply  to  their  region.  For 
installation  in  European  Economic  Area  (EEA)  member  countries    users  must  follow  requirements  for  electrical  equipment  for  use  in 
potentially explosive atmospheres, e.g. EN60079-14 & EN60079-17. This instruction sheet describes installation, which conforms with BS 
EN60079-14 & BS EN60079-17. Important - Particular attention must be paid to the section titled "Special conditions for safe use", failure 
to comply to this requirement will result in an unsafe system.
The SEM210X has been issued with a EU-type examination certificate, confirming compliance with European ATEX directive 2014/34/EU 
for the following specification :-

Manufacturer

Status Instruments Ltd

Type Number

SEM210X

Zones

Product Information 

Certificate Ref

EMT16ATEX0005X

Classification

The following Information is printed on the 
product label

Working Parameters

Additional Information

EMC

BS EN 61326-1
(Sensor wires maximum length 3 metres to comply.)

Enclosure

Colour Blue 

SER No. 000000 - 0001

www.status.co.uk

Made in UK

0891

II 1 GD

IECEx TRC 10.0008X

Ex ia IIC T4 Ga

Ex iaD 20 T135 °C Da

Tamb = -40 °C to 85 °C

 Terminals
+ / -

Ui

=

30 V

Ii

=

100 mA

Pi

=

750 mW

Ci

=

0

Li 

=

0

Uo =

-

Io

=

-

Po

=

-

D2578-01-02 SEM210X  User Guide

Page 1 of 4

Area Classification

 

Gases 

Dusts 

Zone Criteria for  Application Atmosphere

 

Zone 0 

 

 

Zone 20 

Present continuously or for long periods

(> 1000 hours per annum)

 

 

Zone 1 

 

Zone 21 

Likely to occur in normal operation occasionally

(> 10 to < 1000 hours per annum)

 

 

Zone 2 

 

Zone 22 

Unlikely to occur in normal operation

(< 10 hours per annum)

 

 

 

“Model” 

TRAC ????

SEM210X

2016-11

         Example of Type and Range shown below

Summary of Contents for SEM210X

Page 1: ...th BS EN60079 14 BS EN60079 17 Important Particular attention must be paid to the section titled Special conditions for safe use failure to comply to this requirement will result in an unsafe system The SEM210X has been issued with a EU type examination certificate confirming compliance with European ATEX directive 2014 34 EU for the following specification Manufacturer Status Instruments Ltd Type...

Page 2: ...transmitter Electrical Detail REFER TO CONDITIONS FOR SAFE USE Special conditions for safe use 1 a For gas applications the SEM210X temperature transmitters must be mounted in an ATEX IECEx approved enclosure rated for IP54 and located in an area where the enclosure will not be subject to impact or friction b For dust applications the SEM210X temperature transmitters must be mounted in a suitably ...

Page 3: ...k expanding library common type PT100 PT1000 PT500 Ni CU KTY series Sensor s Fail Value on sensor A sensor B fail Sensor Pre set Override sensor signal with pre set value primary function diagnostics PROCESS Scaling Scale sensor signal to PV options Off Two point scaling or 4 to 22 step profile Units Set PV units mA Output Damping Profile out damping 0 to 32 seconds Range Range PV units For 4 to 2...

Page 4: ...r Connection 4 Install assembly Care must be taken to ensure the SEM210X is located to ensure the ambient temperature does not exceed the specified operating temperature 40 to 85 C 5 Wire 4 to 20 mA Loop Ensure all other aspects of the installation comply with the requirements of this document paying particular attention to the loop barrier The 4 to 20 mA loop is connected as follows Barrier dc Su...

Reviews: