background image

Technical Support

If you have any further technical queries, please contact technical support on 01924-420029.

PLEASE DO NOT RETURN ANY ITEM WITHOUT AUTHORISATION
PLEASE LEAVE THESE INSTRUCTIONS WITH CUSTOMER

-------------------------------------------------------------------------------------------------------------------------------------

Guarantee

This product is guaranteed from date of purchase to be free from manufacturing defects for a period of 3 
years if registered, with the following conditions :-
1) The product has been properly installed as per instructions.
2) Damage due to water ingress to controller, debris from water supply, hard water erosion (see (2) on 
front page), vandalism or misuse are not included. Statutory rights are not affected.
Service : Springwell Microelectronics Ltd, 197 Raikes Lane, Birstall, Batley WF17 9QF
_______________________________________________________________________________

Environmental information

This product may contain substances that can be hazardous to the environment if not disposed of 
properly. Electrical and electronic equipment should not be dumped with general household waste but 
must be separately collected for proper treatment and recovery. The crossed-out bin symbol is a 
reminder of the need to dispose of the product properly at end of life; in this way you will assist in the 
recovery, recycling and re-use of many of the materials in this product and help to reduce the amount of 
electrical and electronic waste ending up in landfill and to improve quality of life by preventing the release
of potentially hazardous substances into the environment. Please contact us for information on disposal 
arrangements or take to a local recycling facility. Where possible please recycle your packaging.

Producer registration number WEE/DB0002ZR

_________________________________________________________________________________

Carefully designed and distributed by:
SPRINGWELL MICROELECTRONICS LTD, 197 Raikes Lane, Birstall, Batley, West Yorkshire WF17 9QF
The manufacturer reserves the right due to continuous development to change specifications without notice

Tel: 01924 420029    Fax: 0870 7062353 e-mail: 

[email protected]

www.springwellmicro.co.uk

Producer 

registration number WEE/DB0002ZR

sf4minsv1.2.odt

SPRINGWELL SMARTFLUSH SF4M FITTING INSTRUCTIONS

Pack contains: sensing/control unit for 230V power; low-voltage latching valve (as supplied could be 
open or closed), assembled valve cable with gland and connector; clips, screws, wallplugs.

How Smartflush works

Smartflush stands by until movement is detected, then waits before filling and flushing the cistern

Installation

THIS UNIT MUST BE FITTED ONLY BY A COMPETENT ELECTRICIAN

1)

 Fit back box

 of control unit on the wall or ceiling where it can be seen.

2) 

Fit valve :

 Ensure that there is an isolating valve in the feed to the new valve (to comply with 

water regulations). Isolate water supply. Cut out 30mm of pipe feeding cistern and fit valve, with coil 
not below centre line of pipe. 

Direction is IMPORTANT; Valve is marked 'IN' for inlet.

 Fully open 

any existing trickle cock except for very 

hard water

, when a partly open cock avoids excessive wear.

3) 

Fit cable

 and gland to box. (If too short, replace with longer similar cable, 

polarity important

).

4) 

Set 

internal

 switches

 1 and 2 which adjust the cycle time, i.e. the time from detection to end of 

flush. (see diagram above) and ensure switch 3 is on.

Switch settings

1 Off & 2 off = 20 minute cycle
1 On & 2 off = 30 minute cycle (default)
1 Off & 2 on = 40 minute cycle
1 On & 2 on = 60 minute cycle

The cycle time should be set taking into account 
customer requirements and water regulations on the 
amount of water used. A 30 minute cycle caters for 
most users; 20 minutes recommended for schools 
and hospitals.

3 Off

= disable manual flush button

3 On

= enable manual flush button

4 Off

= standard sensitivity detector

4 On

= low sensitivity detector

manual flush

 button is hidden below the dolphin's tail

on the front of the unit. (see diagram overleaf)

Switch on to reduce movement detection range and 
sensitivity. Recommended if scent spray is nearby.

5) Use 3-core flex to 

connect via a 1A fused spur

 to connections marked N (neutral), E (earth) and 

L (live). Seal entry hole with a cable gland so that the unit is watertight. 

Plug in valve. Power on

the red light on the power board should light. Press manual flush button a few times to confirm 
operation of the valve, sharp click with red flash in the lens for "on", dull click with no flash for "off". 

Leave valve closed

. N.B. As supplied, the valve might be latched open or closed, this is normal.

6) 

Turn on water

 with isolating valve fully open. Smartflush is factory pre-set to activate a 

maintenance flush

 at 12 hour intervals if no-one is seen. 

Go to step 7 if this setting is okay.

Switch off switch 3. Hold down internal 

SET

 button, tap the external hidden 

Manual Flush 

button, 

then release 

SET

 button. The red light flashes every 2 seconds; the number of flashes shows the 

maintenance flush setting. Each press of the 

SET

 button changes to the next setting, as follows :-

1 flash = No maintenance flush

2 flashes = 8 hour interval
3 flashes = 12 hour interval, (factory setting)
4 flashes = 24 hour interval

When desired setting is shown, press 

Manual Flush

 button to save setting. Switch on switch 3.

Cycle of operation

Ceiling mounted sensor

Wall mounted

sensor