Summary of Contents for SIMOTION P320-4 E

Page 1: ...rial security 2 Description 3 Use planning 4 Mounting 5 Connection 6 Power on and software installation 7 Operator Control hardware 8 Parameter assignment addressing 9 Commissioning software 10 Service and maintenance 11 Alarm error and system messages 12 Troubleshooting FAQs 13 Standards and approvals A ESD guidelines B List of abbreviations C ...

Page 2: ...lified personnel are those who based on their training and experience are capable of identifying risks and avoiding potential hazards when working with these products systems Proper use of Siemens products Note the following WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation If products and components from other manuf...

Page 3: ...ion Manual Edition 11 2016 Validity range This Commissioning and Hardware Installation Manual is valid for the SIMOTION P320 4 E and SIMOTION P320 4 S devices as of product level SIMOTION V4 5 Standards The SIMOTION system has been developed in accordance with ISO 9001 quality guidelines Sections in this documentation The following sections describe the purpose and the use of this documentation Sa...

Page 4: ...rnet and PC internal is described References are supplied for the PROFINET and PROFIBUS communication Commissioning software This section contains information notes and requirements for the commissioning and a recommended sequence for the first commissioning of the SIMOTION P320 4 The topics data backup data storage concept and SIMOTION P general reset are described Service and maintenance Informa...

Page 5: ...e opened with only one click Whether beginner or experienced SIMOTION user the most important downloads manuals tutorials FAQs application examples etc can be found at https support industry siemens com cs ww en view 109480700 Additional information Click the following link to find information on the following topics Documentation overview Additional links to download documents Using documentation...

Page 6: ...ions which are included in the scope of delivery of SIMOTION SCOUT and in the Service Support pages in Product Support https support industry siemens com cs de en ps 14505 faq Technical support Country specific telephone numbers for technical support are provided on the Internet under Contact https support industry siemens com cs ww en sc 2090 Preface SIMOTION P320 4 E P320 4 S 6 Commissioning and...

Page 7: ...2 Possible corporate security holes 26 2 3 General security measures 27 2 3 1 Overview 27 2 3 2 Plant security 29 2 3 2 1 Physical protection of critical production areas 29 2 3 3 Network security 30 2 3 3 1 Network segmentation 30 2 3 4 System integrity 33 2 3 4 1 System hardening 33 2 4 Product specific measures 35 2 4 1 Virus scanners Windows security patches SIMOTION P 35 2 4 2 Changing the Wi...

Page 8: ...il mounting 88 5 6 3 Vertical mounting 91 5 7 SIMOTION P AutoLogin 91 6 Connection 99 6 1 Connection requirements 99 6 2 Overview of connections 100 6 3 Connecting PROFINET 101 6 3 1 PROFINET onboard 101 6 3 2 Connection 102 6 4 Mounting a strain relief 103 6 5 Connecting PROFIBUS 104 6 5 1 Requirement 104 6 5 2 SYNC I O connecting cable Plugging in the IsoPROFIBUS board 105 6 5 3 Connecting the I...

Page 9: ...om the control panel 128 9 3 4 Administration tab 129 9 3 4 1 Start SIMOTION P 131 9 3 4 2 Automatic Restart By Plug In External Memory Card 132 9 3 4 3 Runtime Network Connections 133 9 3 5 License tab 135 9 4 Local communication via PC internal 137 9 4 1 Local communication PC internal overview 137 9 4 2 Checking the PC internal settings 137 9 4 3 Station Configurator 138 9 5 Ethernet communicat...

Page 10: ...ata retain data 166 10 8 4 4 Restoring non volatile SIMOTION data retain data 167 10 8 4 5 Save unit variables and global device variables 168 10 8 5 Defined states 169 10 8 5 1 Overview 169 10 8 5 2 Restore the factory setting using SIMOTION P State 169 10 8 5 3 Overall reset using SIMOTION P State operating mode switch setting MRES 170 10 8 5 4 Delete SRAM via SIMOTION P State button Restart Del...

Page 11: ...arm 196 12 3 Battery alarm 197 12 4 Power failure POWER FAIL 197 12 5 PROFINET bus error occurs 199 12 6 Under licensing 200 12 7 Boot error messages 200 13 Troubleshooting FAQs 201 13 1 Error correction 201 13 2 Hotplug Enabled BIOS settings 203 A Standards and approvals 209 A 1 General rules 209 B ESD guidelines 211 B 1 ESD definition 211 B 2 Electrostatic charging of individuals 211 B 3 Basic m...

Page 12: ...Table of contents SIMOTION P320 4 E P320 4 S 12 Commissioning and Hardware Installation Manual 11 2016 ...

Page 13: ...ether the existing auxiliary supply circuits are de energized Ensure that the motors cannot move 3 Identify all other dangerous energy sources e g compressed air hydraulic systems or water 4 Isolate or neutralize all hazardous energy sources by closing switches grounding or short circuiting or closing valves for example 5 Secure the energy sources against switching on again 6 Ensure that the corre...

Page 14: ...sing potential WARNING Danger to life due to electric shock when not grounded For missing or incorrectly implemented protective conductor connection for devices with protection class I high voltages can be present at open exposed parts which when touched can result in death or severe injury Ground the device in compliance with the applicable regulations WARNING Danger to life due to fire spreading...

Page 15: ...egible warning labels Missing or illegible warning labels can result in accidents involving death or serious injury Check that the warning labels are complete based on the documentation Attach any missing warning labels to the components in the national language if necessary Replace illegible warning labels WARNING Danger to life when safety functions are inactive Safety functions that are inactiv...

Page 16: ...aged by either electric fields or electrostatic discharge NOTICE Damage through electric fields or electrostatic discharge Electric fields or electrostatic discharge can cause malfunctions through damaged individual components integrated circuits modules or devices Only pack store transport and send electronic components modules or devices in their original packaging or in other suitable materials...

Page 17: ...ore secure Siemens strongly recommends to apply product updates as soon as available and to always use the latest product versions Use of product versions that are no longer supported and failure to apply latest updates may increase customer s exposure to cyber threats To stay informed about product updates subscribe to the Siemens Industrial Security RSS Feed under http www siemens com industrial...

Page 18: ...nal movements of driven machine or system components during commissioning operation maintenance and repairs caused by for example Hardware and or software errors in the sensors control system actuators and cables and connections Response times of the control system and of the drive Operation and or environmental conditions outside the specification Condensation conductive contamination Parameteriz...

Page 19: ...f components safely and correctly For more information about the residual risks of the drive system components see the relevant sections in the technical user documentation 1 2 Specific safety instructions for SIMOTION P320 4 1 2 1 General safety instructions for the SIMOTION P320 4 WARNING Life threatening voltages are present with an open control cabinet When you install the device in a control ...

Page 20: ...losure according to UL508 is conditional for approval or operation according to UL508 Battery and rechargeable battery WARNING Risk of explosion and release of harmful substances Improper handling of lithium batteries can result in an explosion of the batteries Explosion of the batteries and the released pollutants can cause severe physical injury Worn batteries jeopardize the function of the devi...

Page 21: ...ity Page 209 ESD Guideline Electrostatic sensitive devices can be labeled with an appropriate symbol NOTICE Electrostatic sensitive devices ESD When you touch electrostatic sensitive components you can destroy them through voltages that are far below the human perception threshold If you work with components that can be destroyed by electrostatic discharge observe the ESD Guideline Further informa...

Page 22: ...tions Ambient conditions for which the device is not suitable can cause faults or damage the device Note the following Operate the device only in closed rooms Failure to comply nullifies the warranty Operate the device only in accordance with the ambient conditions specified in the technical specifications Protect the device against dust moisture and heat Do not expose the device to direct sunligh...

Page 23: ...is essential that the AutoLogin is also adapted for this purpose You can find instructions in the following sections Changing the Windows user password Page 36 AutoLogin for SIMOTION P Page 40 Unlocking Windows Note Windows locked Windows may be accidentally locked e g through shortcut key Windows L If you do not know the password for the SIMOTION P320 4 please contact the Siemens Industry Online ...

Page 24: ...nection Per default the remote desktop connection is already set up Note Deactivating the remote desktop connection If you do not use the remote desktop connection it must be deactivated for security reasons See Section Deactivating the remote desktop connection Page 47 SIMOTION IT Note Security concept Note the security concept of HTTP S FTP and Telnet access on the Web server when working with S...

Page 25: ...s protection security is becoming more and more important in industrial environments The progressive networking of entire industrial plants the vertical integration and networking of the individual levels of a company and new technologies such as remote maintenance and remote access are leading to increased requirements for protecting industrial plants The threats are diverse and the consequences ...

Page 26: ...de remote access to plants machines and mobile applications The Internet of things Millions of electronic devices are becoming network capable and are communicating via the Internet such as onboard computers in cars which send warranty information to dealers or water meter sensors that transmit water consumption data to municipal water suppliers via radio However in order for everything from cloud...

Page 27: ...ct your system from threats All of the measures are recommended Additional specific security measures for SINUMERIK SIMOTION and SINAMICS products can be found in Section Product specific security measures Page 35 Basically the measures should be coordinated with one another and correspond to the ring shaped principle of the Defense in Depth strategy The measures are structured according to the on...

Page 28: ...ective measures This refers to the segmentation of the plant network with limited and secure communication between subnetworks secure islands and the interface check with the use of firewalls System integrity System integrity represents the combination two major measures PC based systems and the control level must be protected against attacks Steps include the following measures User authenticatio...

Page 29: ...n also be ensured via the following measures Separate access control for production areas Installation of critical components in securely lockable cabinets switching rooms including monitoring and alarm signaling options Prohibited production areas with restricted access rights Configuration of the radio field to restrict the WLAN range so that it is not available outside the defined areas e g fac...

Page 30: ...DMZ network In the more secure version the coupling is established via a separate DMZ network In this case direct communication between the production network and the company network is completely prevented by firewalls and only takes place indirectly via servers in the DMZ network Note The production networks should also be divided into separate automation cells in order to protect critical commu...

Page 31: ...nables the secure connection of an additional network for service and remote maintenance purposes S623 also permits the secure redundant connection of subordinate networks by means of routers and firewall redundancy Principle This application example shows cell segmentation by several SCALANCE S modules each of which is upstream of the automation cell The data traffic to and from the devices withi...

Page 32: ...RGXFWLRQ 3URGXFWLRQ 6 0 7 6 ZLWK 3 GYDQFHG 6 ZLWK 60 6 0 7 6 ZLWK 3 HE VHUYHU 6HUYHU 356 8076 QWHUQHW 0 QGXVWULDO WKHUQHW 6HUYHU RPDLQ FRQWUROOHU QWHUQHW URXWHU 6 0 7 73 RPIRUW 6 0 7 7 6 6 1 0 6 6 6 0 7 73 6 0 7 7 63 6 1 0 6 6 0 7 73 6 0 7 7 63 6 1 0 6 6 0 7 73 7 6 0 7 73 6 0 7 6 6 180 5 VO 6 0 7 6 352 1 7 352 1 7 352 1 7 352 1 7 352 1 7 6 1 6 6 1 6 6 1 6 6 1 0 6 1 0 Industrial security 2 3 Genera...

Page 33: ...ecure access data for existing accounts Regular checks especially of the locally configured user accounts Regular change of passwords Passwords NOTICE Changing default passwords The misuse of passwords can also represent a considerable security risk We recommend that default passwords be changed during the commissioning and changed at regularly defined intervals as required Virus scanner The use o...

Page 34: ...ss the local message window because it could obscure important messages from the production process Note Installation of software The installation of software is often a process which represents a serious and complicated change to the respective system The storage location of the files to be installed must always be free of viruses e g a file server with its own virus scanner or DVD checked for vi...

Page 35: ...e Although the SIMOTION Runtime software runs in a real time environment it still depends on the available system resources Note Because of the resulting performance impairments the installation and use of a standard virus scanner on a SIMOTION P320 4 during system runtime does not make sense and is not permitted Using a virus scanner As a standard virus scanner cannot be used for SIMOTION P320 4 ...

Page 36: ...functions 2 4 2 Changing the Windows user password Permitting the Windows password to be changed Before the Windows password can be changed it must be permitted for the user If the following procedure is not observed an error message is issued and the Windows password cannot be changed Industrial security 2 4 Product specific measures SIMOTION P320 4 E P320 4 S 36 Commissioning and Hardware Instal...

Page 37: ...er Management Figure 2 2 Homepage 2 The Users folder is displayed at Local Users and Groups in the Computer Management window Click the Users folder The available user groups are displayed Figure 2 3 Computer management Industrial security 2 4 Product specific measures SIMOTION P320 4 E P320 4 S Commissioning and Hardware Installation Manual 11 2016 37 ...

Page 38: ...r to change the Windows password Figure 2 4 SIMOTION properties Changing the Windows password You can find general information on the Windows password on the website at Microsoft Changing des Windows password http windows microsoft com en us windows change windows password change windows password windows 7 Industrial security 2 4 Product specific measures SIMOTION P320 4 E P320 4 S 38 Commissionin...

Page 39: ... password the Windows window to change the Windows password opens First enter your current password and then the new Windows password You must enter the new Windows password a second time for confirmation Figure 2 6 Entering the new Windows password Industrial security 2 4 Product specific measures SIMOTION P320 4 E P320 4 S Commissioning and Hardware Installation Manual 11 2016 39 ...

Page 40: ... the AutoLogin 2 4 3 1 SIMOTION P AutoLogin The password for the AutoLogin must be changed when the user has changed the Windows password The Windows user password is changed in the normal way e g Change Password screen See also Section Changing the Windows user password Page 36 Automatically Log On SIMOTION P320 4 is preset so that the user does not have to enter the user name and the password to...

Page 41: ...hat an AutoLogin still functions after changing the Windows password the password for the AutoLogin must be changed Industrial security 2 4 Product specific measures SIMOTION P320 4 E P320 4 S Commissioning and Hardware Installation Manual 11 2016 41 ...

Page 42: ...Items Administrative Tools Figure 2 9 Computer Management entry point 2 The Users folder is displayed at Local Users and Groups in the Computer Management window Click the Users folder The available user groups are displayed Figure 2 10 Computer Management Users Industrial security 2 4 Product specific measures SIMOTION P320 4 E P320 4 S 42 Commissioning and Hardware Installation Manual 11 2016 ...

Page 43: ...activate the User cannot change password checkbox in the simotion Properties dialog box Figure 2 11 simotion Properties General dialog box 5 Confirm with OK Industrial security 2 4 Product specific measures SIMOTION P320 4 E P320 4 S Commissioning and Hardware Installation Manual 11 2016 43 ...

Page 44: ...ceed as follows 1 Open the search via Windows Start and enter netplwiz Figure 2 12 Programs netplwiz 2 The following User Accounts dialog box opens Industrial security 2 4 Product specific measures SIMOTION P320 4 E P320 4 S 44 Commissioning and Hardware Installation Manual 11 2016 ...

Page 45: ...Figure 2 13 User Accounts Industrial security 2 4 Product specific measures SIMOTION P320 4 E P320 4 S Commissioning and Hardware Installation Manual 11 2016 45 ...

Page 46: ... so that the Automatically Log On dialog box is subsequently displayed Figure 2 14 User accounts 4 Enter your changed Windows user password in the Automatically Log On dialog box and confirm it by entering it a second time Figure 2 15 Automatically Log On dialog box 5 Confirm the password with OK Industrial security 2 4 Product specific measures SIMOTION P320 4 E P320 4 S 46 Commissioning and Hard...

Page 47: ...top connection we recommend that you explicitly disable the remote desktop connection NOTICE Deactivating the remote desktop connection To ensure that the remote desktop connection is not used it must be explicitly deactivated Industrial security 2 4 Product specific measures SIMOTION P320 4 E P320 4 S Commissioning and Hardware Installation Manual 11 2016 47 ...

Page 48: ...e Control Panel select System Remote settings Figure 2 16 Remote settings 2 Select the Remote tab in the System Properties dialog box Industrial security 2 4 Product specific measures SIMOTION P320 4 E P320 4 S 48 Commissioning and Hardware Installation Manual 11 2016 ...

Page 49: ...connections to this computer option at Remote Desktop 4 Confirm with OK Any remote desktop access is deactivated with this operation Industrial security 2 4 Product specific measures SIMOTION P320 4 E P320 4 S Commissioning and Hardware Installation Manual 11 2016 49 ...

Page 50: ...Industrial security 2 4 Product specific measures SIMOTION P320 4 E P320 4 S 50 Commissioning and Hardware Installation Manual 11 2016 ...

Page 51: ... SIMATIC Flat Panel IFP1500 IFP1900 and IFP2200 can be used for the operation of the SIMOTION P320 4 hardware platform in a distributed configuration SIMOTION P320 4 versions The SIMOTION P320 4 can control various I O systems and HMI components via PROFINET onboard or the optional IsoPROFIBUS board If required a USB DVD drive can be connected for example The following versions of the SIMOTION P32...

Page 52: ...4 product description 3 2 1 SIMOTION P320 4 overview The SIMOTION P320 4 provides high level industrial performance It features Compact design Maintenance free operation High degree of ruggedness Long term availability Figure 3 1 SIMOTION P320 4 view Description 3 2 SIMOTION P320 4 product description SIMOTION P320 4 E P320 4 S 52 Commissioning and Hardware Installation Manual 11 2016 ...

Page 53: ...nfigurable baud rates 9 6 Kbit s 12 Mbps Graphics Integrated Intel HD2000 or HD4000 DVI resolution of 640 480 pixels up to 1920 1200 pixels Display port resolution max 1920 1200 pixels Graphics memory is occupied in the main memory dynamic UMA Power supply 24 VDC 20 20 max 4 A Operating conditions Operation without fan Drives and storage media CFast card or SSD Solid State Disk Depending on the ha...

Page 54: ... or VGA DPP Display port DVI via DPP to DVI adapter USB 4 USB 3 0 simultaneous operation of high current backward compatible with USB 2 0 1 1 Ethernet 1 RJ45 10 100 1000 Mbps PROFINET I O 3 RJ45 100 Mbps Keyboard mouse Can be connected via USB interface Software Operating systems P320 4 E Windows Embedded Standard 7 32 bit P320 4 S Windows 7 Ultimate 32 bit Description 3 2 SIMOTION P320 4 product ...

Page 55: ...J 7 63 352 86 3 GULYHV 2 PRGXOHV QDORJ ULYH QWHUIDFH 6 0 7 7 H J 7 63 352 86 GULYHV H J 6 1 0 6 6 VR352 86 ERDUG RSWLRQDO 352 1 7 RQERDUG FRQWUROOHU OWHUQDWLYHO 0 3 6 352 1 7 2 H J 7 63 352 1 7 GULYHV H J 6 1 0 6 6 9 9 6HULDO LQWHUIDFH 20 5HWDLQ GDWD XIIHUHG 65 0 6 1 2 FRQQHFWLQJ FDEOH WKHUQHW 352 86 3 352 86 3 352 1 7 352 1 7 352 1 7 6 027 21 3 HMI Human Machine Interface PG Programming device ES...

Page 56: ...1000 Mbps COM1 Serial interface 3 PROFINET PROFINET ports with three RJ45 sockets 3 2 5 SIMOTION P Runtime software structure SIMOTION P Runtime contains the SIMOTION P Kernel which performs the motion control and interface control A SIMOTION project is planned configured assigned parameters commissioned and programmed via the SIMOTION SCOUT engineering system ES The user data can be stored on the...

Page 57: ...ore cannot be installed HMI software HMI Runtime software can be operated on the same PC e g the Siemens WinCC flexible software Other software packages can be linked by means of the OPC interface The HMI software is used as the general term in the following Internal communication A locally installed HMI can use the local communication to access the following Variables in SIMOTION RT Drives on PRO...

Page 58: ...with IP65 67 degree of protection for machine related cabinet free applications including motor starters Note Note that not all modules of the above mentioned I Os or I O systems have been released for SIMOTION There may also be system dependent functional differences with regard to the use on SIMOTION and on SIMATIC For example special process control functions e g HART modules etc are not suppor...

Page 59: ...SIMOTION SCOUT engineering system The HMI or ES software can be connected using the following versions Local Page 60 via PROFINET Page 72 via Ethernet Page 73 via IsoPROFIBUS optional Page 75 Local communication of the HMI ES If HMI or ES is installed locally on the SIMOTION P320 4 PC internal can establish a connection to the local SIMOTION P Runtime Only a local connection is permitted See secti...

Page 60: ...of delivery Figure 3 4 Set PG PC Interface TCP IP MAC Bridge Miniport dialog box Note Local communication via Ethernet TCP IP For the communication via Ethernet TCP IP to function locally a link must be available to the Ethernet interface or a LAN cable must be connected or the MAC bridge set up Note Setting up the MAC bridge miniport See also Section Setting up a network bridge MAC bridge minipor...

Page 61: ... a network bridge MAC bridge miniport Note If you are working with SIMOTION P320 4 version V4 5 the Network Bridge is already preset The network bridge is not preset for version V4 4 and must be set up as described in the following The following is a step by step description of how the network bridge MAC Bridge Miniport is set up Description 3 3 HMI and SIMOTION SCOUT SIMOTION P320 4 E P320 4 S Co...

Page 62: ...ange adapter settings Open the Network and Internet Network Connections dialog box The network connections of your PC are shown here Figure 3 7 Initial situation Network connections Device Manager Open the Device Manager via the Control Panel Description 3 3 HMI and SIMOTION SCOUT SIMOTION P320 4 E P320 4 S 62 Commissioning and Hardware Installation Manual 11 2016 ...

Page 63: ...work connections are shown here Figure 3 8 Opening the Device Manager 2 Install the Microsoft Loopback Adapter via the Device Manager 3 To do this select the menu Action Add legacy hardware The Add Hardware Wizard then opens Description 3 3 HMI and SIMOTION SCOUT SIMOTION P320 4 E P320 4 S Commissioning and Hardware Installation Manual 11 2016 63 ...

Page 64: ...Figure 3 9 Device Manager Action menu Description 3 3 HMI and SIMOTION SCOUT SIMOTION P320 4 E P320 4 S 64 Commissioning and Hardware Installation Manual 11 2016 ...

Page 65: ...e the Add Hardware Wizard to install the network bridge Figure 3 10 Add Hardware Starting the wizard Description 3 3 HMI and SIMOTION SCOUT SIMOTION P320 4 E P320 4 S Commissioning and Hardware Installation Manual 11 2016 65 ...

Page 66: ... in the wizard with Next Figure 3 11 Add Hardware Manual selection from a list 3 Select Network adapters in the dialog box now open and continue in the wizard with Next Figure 3 12 Select Add Hardware Network adapters Description 3 3 HMI and SIMOTION SCOUT SIMOTION P320 4 E P320 4 S 66 Commissioning and Hardware Installation Manual 11 2016 ...

Page 67: ...oft at Manufacturer and the Microsoft Loopback Adapter at Network Adapter 6 Continue in the wizard with Next Figure 3 13 Add Hardware Selecting the desired Network Adapter Description 3 3 HMI and SIMOTION SCOUT SIMOTION P320 4 E P320 4 S Commissioning and Hardware Installation Manual 11 2016 67 ...

Page 68: ...twork Adapter can be installed 8 After finishing the installation the following dialog box is displayed Exit the wizard with Finish Figure 3 15 Add Hardware Installation of the Microsoft Loopback Adapter is finished Description 3 3 HMI and SIMOTION SCOUT SIMOTION P320 4 E P320 4 S 68 Commissioning and Hardware Installation Manual 11 2016 ...

Page 69: ...anager The Microsoft Loopback Adapter is displayed at Network adapters in the Device Manager Figure 3 16 Device Manager Microsoft loopback adapter Network connections The newly installed Microsoft Loopback Adapter is also displayed at Network Connections Description 3 3 HMI and SIMOTION SCOUT SIMOTION P320 4 E P320 4 S Commissioning and Hardware Installation Manual 11 2016 69 ...

Page 70: ...tivate the network bridge proceed as follows 1 Select both adapters at Network Connections 2 Select Bridge Connections via the context menu Figure 3 18 Network Connections Setting the Bridge Connection Description 3 3 HMI and SIMOTION SCOUT SIMOTION P320 4 E P320 4 S 70 Commissioning and Hardware Installation Manual 11 2016 ...

Page 71: ... the network bridge has been set up Setting Set PG PC interface Now open the PG PC interface to complete the setting for the Network Bridge 1 Open the Set PG PC Interface dialog box via the Control Panel entry point 2 Deactivate the MAC Bridge Miniport DCP checkbox in the LLDP DCP tab If you do not deactivate the MAC Bridge Miniport DCP the SIMOTION P320 4 may not be found via Accessible nodes Des...

Page 72: ...standard EN 61158 for industrial automation With PROFINET devices can be linked up from the field level through to the management level With PROFINET an external HMI or ES can also be integrated into the network and data can be exchanged directly with the SIMOTION P320 4 device Description 3 3 HMI and SIMOTION SCOUT SIMOTION P320 4 E P320 4 S 72 Commissioning and Hardware Installation Manual 11 20...

Page 73: ...y Configuration Manual 3 3 4 HMI or ES via Ethernet Networking via Ethernet A complex interconnection with several HMIs or ESs is only possible using an Ethernet communication This allows both an external HMI or ES to access several SIMOTION devices or one SIMOTION device to access another one for example to display the production data 2 GULYHV 2 GULYHV 2 GULYHV 2 GULYHV 352 1 7 2 352 86 3 352 1 7...

Page 74: ...nterface This makes it possible to access data or diagnostic information in the SIMOTION P320 4 from any location via intranet or the Internet HTTP browser OPC XML Setting in WebCFG xml default 80 HTTPS browser OPC XML Setting in WebCfg xml default 443 FTP 21 Telnet References You can find further information in the documentation for SIMOTION IT SIMOTION IT Diagnostics and Configuration SIMOTION I...

Page 75: ...352 86 3 2 ULYHV 352 86 3 2 ULYHV 352 86 3 6 027 21 3 6 027 21 3 Figure 3 23 Model Networking via PROFIBUS DP References You can find further information on the HMI in the documentation SIMOTION Runtime Basic Functions section HMI Human Machine Interface coupling Description 3 3 HMI and SIMOTION SCOUT SIMOTION P320 4 E P320 4 S Commissioning and Hardware Installation Manual 11 2016 75 ...

Page 76: ...Description 3 3 HMI and SIMOTION SCOUT SIMOTION P320 4 E P320 4 S 76 Commissioning and Hardware Installation Manual 11 2016 ...

Page 77: ...ing and checking the delivery Device identification data Information about the permitted mounting positions Environmental conditions Electromagnetic compatibility Link to further information about relevant standards for electromagnetic compatibility EMC SIMOTION P320 4 E P320 4 S Commissioning and Hardware Installation Manual 11 2016 77 ...

Page 78: ...Use planning SIMOTION P320 4 E P320 4 S 78 Commissioning and Hardware Installation Manual 11 2016 ...

Page 79: ...de Two operating modes are available for the installation of a SIMOTION P320 4 SIMOTION P320 4 Headless operation Page 79 Distributed configuration of the SIMOTION P320 4 with a remote panel Page 82 5 2 Headless operation 5 2 1 SIMOTION P320 4 Headless operation The SIMOTION P320 4 is operated without a screen e g SIMATIC panel SIMOTION P320 4 is installed in a cabinet The maintenance and configur...

Page 80: ...tion service support 5 2 2 Deactivating the remote desktop connection Deactivating the remote desktop connection If you do not use the headless mode and do not require a remote desktop connection we recommend that you explicitly disable the remote desktop connection NOTICE Deactivating the remote desktop connection To ensure that the remote desktop connection is not used it must be explicitly deac...

Page 81: ...1 Using the Control Panel select System Remote settings Figure 5 2 Remote settings 2 Select the Remote tab in the System Properties dialog box Mounting 5 2 Headless operation SIMOTION P320 4 E P320 4 S Commissioning and Hardware Installation Manual 11 2016 81 ...

Page 82: ...cal areas of the plant e g cabinet The distributed configuration of a panel with the SIMOTION P320 4 can be performed via the DisplayPort or DVI connection Please note the cable lengths that are supported for the panel 5 4 Important information about installation When installing the unit in an enclosed housing make sure that sufficient space is available for air circulation Ensure that the clearan...

Page 83: ...e side Always use SIMATIC IPC CFast cards for industrial applications The CFast card is mandatory for operation of the SIMOTION P320 4 The CFast card is supplied with the SIMOTION P320 4 NOTICE Damage to the device The CFast and CompactFlash connections are not compatible The device will be damaged Use the slot described in this section only for a CFast card Note Note the version of the CFast card...

Page 84: ... Only use the CFast card specified with the article number above for the external interface Requirement The device is switched off SIMATIC IPC CFast card approved for industrial applications Mounting 5 5 Withdrawing inserting the CFast card SIMOTION P320 4 E P320 4 S 84 Commissioning and Hardware Installation Manual 11 2016 ...

Page 85: ...ithdraw the CFast card from the memory card slot 3 After removing the CFast card close and lock the cover Inserting the CFast card NOTICE Inserting the CFast card If you insert a CFast card into a built in SIMOTION P320 4 in a system observe the safety regulations for working with electrical systems Insert the CFast card carefully into the slot and without applying excess force Mounting 5 5 Withdr...

Page 86: ...d checkbox is activated in the SIMOTION P Control Manager in the Administration tab at Automatic Restart By Plug In External Memory Card Figure 5 4 Prompt about the missing CFast card automatic restart Enabled Note The prompt does not close automatically after inserting the CFast card If the prompt shown above is not automatically closed after inserting the CFast card and there is no automatic res...

Page 87: ...tting The automatic restart settings are made in the SIMOTION P Control Manager The default setting in the Administration tab at Start SIMOTION P is Enabled Further information can be found in Section SIMOTION P Control Manager Administration tab Automatic Restart By Plug In External Memory Card Page 132 5 6 Installing the SIMOTION P320 4 in the control cabinet 5 6 1 Notes on installation Requirem...

Page 88: ...4 on a standard rail Note Use of Siemens 35 mm standard mounting rail is recommended Mounting the standard mounting rail clip Before you can install the device on a standard mounting rail you will need to attach the standard mounting rail clip included in the scope of delivery The fasteners and screws required are supplied with the device for mounting depending on the order number Requirement 1 st...

Page 89: ...t an angle on the upper rail guide 2 Press the SIMOTION P320 4 slightly downward 3 Swivel the SIMOTION P320 4 completely onto the rail until both clamps lock completely into place Ensure that the locking into place of the SIMOTION P320 4 is audible Mounting 5 6 Installing the SIMOTION P320 4 in the control cabinet SIMOTION P320 4 E P320 4 S Commissioning and Hardware Installation Manual 11 2016 89...

Page 90: ...rews M 4 4 mm diameter 15 mm length NOTICE Observe the total weight of the SIMOTION P320 4 Ensure that the wall can hold four times the total weight of the device including mounting rail and additional expansion modules Removing the device from the mounting rails Push the device down until the bottom clamp releases the device Swing the device away from the rails Additional references Further infor...

Page 91: ...20 0YP0 x You can order the vertical mounting front kit via the Siemens Industry Mall https mall industry siemens com Additional references Further information on standard rail mounting and vertical mounting can be found in the SIMOTION P320 4 E P320 4 S Manual 5 7 SIMOTION P AutoLogin The password for the AutoLogin must be changed when the user has changed the Windows password The Windows user pa...

Page 92: ... order that an AutoLogin still functions after changing the Windows password the password for the AutoLogin must be changed Mounting 5 7 SIMOTION P AutoLogin SIMOTION P320 4 E P320 4 S 92 Commissioning and Hardware Installation Manual 11 2016 ...

Page 93: ...l Panel Items Administrative Tools Figure 5 7 Computer Management entry point 2 The Users folder is displayed at Local Users and Groups in the Computer Management window Click the Users folder The available user groups are displayed Figure 5 8 Computer Management Users Mounting 5 7 SIMOTION P AutoLogin SIMOTION P320 4 E P320 4 S Commissioning and Hardware Installation Manual 11 2016 93 ...

Page 94: ...ies 4 Deactivate the User cannot change password checkbox in the simotion Properties dialog box Figure 5 9 simotion Properties General dialog box 5 Confirm with OK Mounting 5 7 SIMOTION P AutoLogin SIMOTION P320 4 E P320 4 S 94 Commissioning and Hardware Installation Manual 11 2016 ...

Page 95: ...ogin proceed as follows 1 Open the search via Windows Start and enter netplwiz Figure 5 10 Programs netplwiz 2 The following User Accounts dialog box opens Mounting 5 7 SIMOTION P AutoLogin SIMOTION P320 4 E P320 4 S Commissioning and Hardware Installation Manual 11 2016 95 ...

Page 96: ...Figure 5 11 User Accounts Mounting 5 7 SIMOTION P AutoLogin SIMOTION P320 4 E P320 4 S 96 Commissioning and Hardware Installation Manual 11 2016 ...

Page 97: ...ecessary so that the Automatically Log On dialog box is subsequently displayed Figure 5 12 User accounts 4 Enter your changed Windows user password in the Automatically Log On dialog box and confirm it by entering it a second time Figure 5 13 Automatically Log On dialog box 5 Confirm the password with OK Mounting 5 7 SIMOTION P AutoLogin SIMOTION P320 4 E P320 4 S Commissioning and Hardware Instal...

Page 98: ...Mounting 5 7 SIMOTION P AutoLogin SIMOTION P320 4 E P320 4 S 98 Commissioning and Hardware Installation Manual 11 2016 ...

Page 99: ...ssed with a key or tool Only instructed or authorized personnel have access Observe the following points during installation The device may only be connected to 24 VDC power supplies that meet the requirements in accordance with SELV The cable cross section must be chosen large enough to ensure that no damage can result from cable overheating in the event of a short circuit in the SIMOTION P320 4 ...

Page 100: ...1 0 6 6 VR352 86 ERDUG RSWLRQDO 352 1 7 RQERDUG FRQWUROOHU OWHUQDWLYHO 0 3 6 352 1 7 2 H J 7 63 352 1 7 GULYHV H J 6 1 0 6 6 9 9 6HULDO LQWHUIDFH 20 5HWDLQ GDWD XIIHUHG 65 0 6 1 2 FRQQHFWLQJ FDEOH WKHUQHW 352 86 3 352 86 3 352 1 7 352 1 7 352 1 7 6 027 21 3 Figure 6 1 System overview SIMOTION P320 4 hardware The cabling for all elements and components of the complete system must only be carried ou...

Page 101: ...T and IRT using the permanently integrated PROFINET interface The device has a PROFINET interface with 3 ports The PROFINET IO with IRT allows IT services to be performed in parallel to the real time communication on an Ethernet cable where the PROFINET IO with IRT has a reserved area that provides a decoupling from the standard communication Note PROFINET onboard is not a plug in board Instead it...

Page 102: ...LWK 8 3 ERRN VL H 6 0 7 b 7b 6 ZLWK 0 31 352 1 7 RQERDUG FRQWUROOHU 6 1 0 6 6 ZLWK 8 3 ERRN VL H 6 1 0 6 6 ZLWK 8 3 ERRN VL H 6 1 0 6 6 ZLWK 8 3 ERRN VL H 6 0 7 b 7b 6 ZLWK 0 31 6 0 7 b 7b 0 6 0 7 b 7b 0 6 027 21 3 Figure 6 2 Example for a PROFINET application Connection 6 3 Connecting PROFINET SIMOTION P320 4 E P320 4 S 102 Commissioning and Hardware Installation Manual 11 2016 ...

Page 103: ...es you must install the strain relief bracket and attach the cable tie supplied in the accessory kit For further information see Mounting a strain relief Page 103 Additional references You can find further information on the website www siemens com simotion www siemens com simotion Drives and I O modules that are released for SIMOTION You will also find current brochures and catalogs 6 4 Mounting ...

Page 104: ... of the screws 2 Secure the strain relief at the marked points Only use the enclosed lens head screws for securing the strain relief 6 5 Connecting PROFIBUS 6 5 1 Requirement SIMOTION P320 4 is switched off and disconnected from the mains IsoPROFIBUS board Article No 6AU1390 0AA00 0AA1 Connection 6 5 Connecting PROFIBUS SIMOTION P320 4 E P320 4 S 104 Commissioning and Hardware Installation Manual ...

Page 105: ...he SYNC I O connecting cable is secured in the device using an adhesive tape Figure 6 4 Opened SIMOTION P320 4 with SYNC I O connecting cable as delivered ex works 2 Remove the adhesive tape and change the position of the SYNC I O connecting cable as follows the SYNC I O connecting cable is routed to the interface side of the device and secured there again Connection 6 5 Connecting PROFIBUS SIMOTI...

Page 106: ...s inserted in the next step Slide the IsoPROFIBUS board on the left into the guide rail of the previously removed slot plate and push it backward guided by the rail Figure 6 6 Inserting the IsoPROFIBUS board 5 The IsoPROFIBUS board is inserted into the rear PCI slot by applying slight pressure Connection 6 5 Connecting PROFIBUS SIMOTION P320 4 E P320 4 S 106 Commissioning and Hardware Installation...

Page 107: ... O connecting cable 7 Close the cover plate of the SIMOTION P320 4 and fasten the screws 6 5 3 Connecting the IsoPROFIBUS board The interface for the optional IsoPROFIBUS board is protected by a cover There are two holes in the cover for wiring Requirement The device is switched off Connection 6 5 Connecting PROFIBUS SIMOTION P320 4 E P320 4 S Commissioning and Hardware Installation Manual 11 2016...

Page 108: ...n of the arrow swivel the released cover in the direction of the arrow and remove it The interfaces for the optional IsoPROFIBUS board are then free 2 Connect the IsoPROFIBUS board to the slots shown Connection 6 5 Connecting PROFIBUS SIMOTION P320 4 E P320 4 S 108 Commissioning and Hardware Installation Manual 11 2016 ...

Page 109: ...the positions shown and close it Make sure that the latches engage to secure the cover in its position Connection 6 5 Connecting PROFIBUS SIMOTION P320 4 E P320 4 S Commissioning and Hardware Installation Manual 11 2016 109 ...

Page 110: ...6 1 0 6 6 ZLWK 8 3 ERRN VL H 6 1 0 6 6 ZLWK 8 3 ERRN VL H 6 0 7 b 7b 0 6 0 7 b 7b 0 3 3 6 027 21 3 Figure 6 8 Example for a PROFIBUS application 6 5 5 Connecting the bus connectors for the X101 and X102 interfaces IsoPROFIBUS The bus connector is used to connect the PROFIBUS cable to the IsoPROFIBUS interface X101 X102 thus establishing a connection to additional stations Connection 6 5 Connecting...

Page 111: ...h a bus connector is de energized Because the bus connector takes its voltage from the station this terminating resistor is ineffective Make sure that the stations at which the terminating resistor is connected are always energized 6 5 6 PROFIBUS cable Properties of the PROFIBUS cable The PROFIBUS cable is a two stranded twisted and shielded cable Table 6 1 Properties of the PROFIBUS cable Feature...

Page 112: ...siemens com simotion 6 6 Connecting Ethernet Procedure Plug the LAN cable into the Ethernet interface of the SIMOTION P320 4 You must hear the connection engage properly Cables Standard shielded twisted pair cables are used for the networking in this case The following connection cables are recommended SIMATIC NET ind Ethernet TP XP CORD RJ45 RJ45 TP CORD assembled with 2 RJ45 connectors send and ...

Page 113: ...ration In order to ensure safe operation of your equipment implement the following measures adapting them to suit your conditions An EMERGENCY OFF concept in accordance with the generally accepted rules of current engineering practice e g European standards EN 60204 EN 418 and similar Additional measures for limiting the end position of axes e g hardware limit switches Equipment and measures for p...

Page 114: ...owing list identifies considerations required for startup of a system following certain events If the system starts up again following a voltage drop or power failure all hazardous operating states must be prevented from occurring If necessary force an EMERGENCY OFF If the system starts up again after the EMERGENCY OFF apparatus is released the startup must not be unchecked or undefined 6 8 3 Conn...

Page 115: ...equipotential bonding strip on the SIMOTION P320 4 large surface large area contact with the central grounding point of the cabinet or system in which the devices are installed The protective conductor must not have less than a minimum core cross section of 2 5 mm2 Protective conductor connection potential equalization Connection 6 8 Connecting the power supply SIMOTION P320 4 E P320 4 S Commissio...

Page 116: ...Connection 6 8 Connecting the power supply SIMOTION P320 4 E P320 4 S 116 Commissioning and Hardware Installation Manual 11 2016 ...

Page 117: ...ion Windows with SIMOTION P is powered up automatically The SIMOTION P320 4 issues the following message after successful power up Figure 7 1 SIMOTION P320 4 after power up The SIMOTION P320 4 responds in this way to every subsequent power up SIMOTION P320 4 E P320 4 S Commissioning and Hardware Installation Manual 11 2016 117 ...

Page 118: ...spective software 7 3 Customer specific software To ensure high quality and reliable working of the device SIMOTION P320 4 is fully configured and ready for operation at the time of delivery For this purpose the system components used are subject to a certification procedure with Siemens as the system manufacturer The certification process establishes and documents the real time features of the co...

Page 119: ...s hardware on other SIMOTION platforms are visualized on the screen for SIMOTION P320 4 The display is performed by the SIMOTION P State application The following figures show SIMOTION P State in the started state with without inserted IsoPROFIBUS board Figure 8 1 SIMOTION P State PROFINET onboard SIMOTION P320 4 E P320 4 S Commissioning and Hardware Installation Manual 11 2016 119 ...

Page 120: ...hnology packages e g synchronous operation cam are ac tive Test and commissioning functions can be executed without a user program The user program is not active STOP Yellow SIMOTION P320 4 in STOP mode There is no user program running The technology packages are not active SF PN Red PROFINET bus fault A fault state is displayed on the PROFINET interface X3 SY MT Yellow Sync of the PROFINET inter ...

Page 121: ...P State Use the mode selector to set the SIMOTION P320 4 to different states The controller can be switched in RUN or STOP STOPU mode and perform an overall reset The change of the operating state with the mode selector has priority over a state selected via SIMOTION SCOUT Note Setting the operating state via the mode selector The STOP STOPU switch position cannot be set to RUN via the SIMOTION SC...

Page 122: ...20 4 is deactivated Figure 8 3 SIMOTION P State state display The status LEDs and the current operating state are also displayed in the Windows task bar RUN state Green STOP state Yellow NOT STARTED state Gray Note FAQs can be found in Section Troubleshooting FAQs Page 201 8 1 5 Function elements Functions of the buttons Below the current SIMOTION P320 4 status display you will find a selection of...

Page 123: ...s only possible if SIMOTION P320 4 has been powered up status not 0 to 5 not started Terminate SIMOTION P Stop SIMOTION P320 4 Note This is possible only if SIMOTION P320 4 has powered up Start SIMOTION P Start SIMOTION P320 4 Note This is possible only if SIMOTION P320 4 has not been started Resetting to the delivery condition SIMOTION P320 4 can be reset to the default settings at the time of de...

Page 124: ...tile SIMOTION data retain data Page 166 Webserver Access to the SIMOTION IT Web server is protected by a multi level security concept Upon delivery the security level is low to allow configuration of the device The security state of the Web server can be set here The following selection options are available Security Level normal Security Level low Temperature specifications Figure 8 4 Dialog Temp...

Page 125: ... Note Station Configurator settings Settings made with the Station Configurator are reset to the default values at the time of delivery as well Further information can be found in Section Defined states Restore the factory settings using SIMOTION P State Page 169 Info menu Info Description Hardware Version Display of the hardware information Software Version Display of the software versions Info a...

Page 126: ...Operator Control hardware 8 1 SIMOTION P state application SIMOTION P320 4 E P320 4 S 126 Commissioning and Hardware Installation Manual 11 2016 ...

Page 127: ...nd SIMOTION SCOUT Page 59 You are familiar with the Windows Control Panel Resetting the factory settings It is possible to reset SIMOTION P320 4 to the factory settings see section Resetting the SIMOTION P to the initial state Page 183 9 2 2 Ethernet TCP IP local SIMOTION P320 4 delivery state Local communication in the SIMOTION P320 4 between Windows programs such as HMI and the SIMOTION P Runtim...

Page 128: ...Panel Properties SIMOTION P Control Manager has the following features The following settings take effect immediately after a change Start SIMOTION P Automatic Restart By Plug In External Memory Card Ethernet IP address The values to be set are generally required only by the administrator These are License handling IP addresses 9 3 3 Calling SIMOTION P Control Manager from the control panel You ca...

Page 129: ...trol Manager application is in English 9 3 4 Administration tab The Administration tab contains Start SIMOTION P Page 131 Automatic Restart By Plug In External Memory Card Page 132 Runtime Network Connections Page 133 Parameter assignment addressing 9 3 SIMOTION P control manager SIMOTION P320 4 E P320 4 S Commissioning and Hardware Installation Manual 11 2016 129 ...

Page 130: ...gure 9 2 SIMOTION P Control Manager Administration tab Parameter assignment addressing 9 3 SIMOTION P control manager SIMOTION P320 4 E P320 4 S 130 Commissioning and Hardware Installation Manual 11 2016 ...

Page 131: ... by means of the SIMOTION P State application using the Start SIMOTION P button Disabled Prevents the automatic starting of SIMOTION P while the Windows system is booting up SIMOTION P cannot be started until this lock is canceled Figure 9 3 Start SIMOTION P Disabled Parameter assignment addressing 9 3 SIMOTION P control manager SIMOTION P320 4 E P320 4 S Commissioning and Hardware Installation Ma...

Page 132: ...t SIMOTION P State Figure 9 4 SIMOTION P State Disabled status 9 3 4 2 Automatic Restart By Plug In External Memory Card Note Not a Windows restart Note that this is not a Windows restart Parameter assignment addressing 9 3 SIMOTION P control manager SIMOTION P320 4 E P320 4 S 132 Commissioning and Hardware Installation Manual 11 2016 ...

Page 133: ...emory Card Disabled The automatic restart of the SIMOTION P Runtime is prevented after inserting the CFast card Note Behavior with withdrawn CFast card Further information on the behavior of the SIMOTION P320 4 with withdrawn CFast card can be found in Section Automatic restart of the SIMOTION P Runtime Page 86 9 3 4 3 Runtime Network Connections The Ethernet interface of the SIMOTION P320 4 is di...

Page 134: ...ngs after selecting the button the Onboard RT Ethernet Properties dialog box opens Figure 9 6 Onboard RT Ethernet Properties Click Check Configuration to validate the settings of the Runtime Ethernet configuration and check for agreement with the Windows Ethernet interface You can find further information about this in Section Ethernet communication overview Page 140 Click Assign Configuration to ...

Page 135: ...e licenses currently installed on this hardware If you wish to modify the licensing of this hardware click the Licensing button The License Manager dialog box is displayed here you enter a new License Key Parameter assignment addressing 9 3 SIMOTION P control manager SIMOTION P320 4 E P320 4 S Commissioning and Hardware Installation Manual 11 2016 135 ...

Page 136: ...n this case contact the hotline http support automation siemens com Note You must restart the SIMOTION P320 4 after licensing To do this in SIMOTION P State press either the Restart button or the Terminate SIMOTION P button and then Start SIMOTION P Note For more information on licensing see the SIMOTION SCOUT Configuration Manual Parameter assignment addressing 9 3 SIMOTION P control manager SIMO...

Page 137: ...echanisms 9 4 2 Checking the PC internal settings Configuration in the Windows Control Panel of the SIMOTION P320 4 To enable local communication the following settings must have been made You can access the settings via the Control Panel of Windows Figure 9 9 Control Panel Set PG PC Interface Parameter assignment addressing 9 4 Local communication via PC internal SIMOTION P320 4 E P320 4 S Commis...

Page 138: ...rsion for the SIMOTION P320 4 is TCP IP Further information can be found in Section Local HMI or ES on SIMOTION P320 4 Page 60 9 4 3 Station Configurator The Station Configurator is required to configure the communication paths for the HMI software The Station Configurator is provided directly as desktop icon of the SIMOTION P320 4 Parameter assignment addressing 9 4 Local communication via PC int...

Page 139: ...via the Station Configurator it is essential that you terminate SIMOTION P before calling the function with Terminate SIMOTION P in the SIMOTION P State application Parameter assignment addressing 9 4 Local communication via PC internal SIMOTION P320 4 E P320 4 S Commissioning and Hardware Installation Manual 11 2016 139 ...

Page 140: ...P320 4 has one onboard Ethernet interface NOTICE SIMOTION P Runtime During SIMOTION P Runtime the onboard Ethernet interface must be activated under Windows The onboard Ethernet interface must not be deactivated or activated during operation You can connect Industrial Ethernet to the Ethernet interface X1 Industrial Ethernet is a communication network with a transmission rate of 10 100 1000 Mbps P...

Page 141: ...address is taken from a DHCP server the assignment of the runtime IP address and runtime subnet mask must also be selected in accordance with the default setting of the DHCP server The following applies see Section Communication via an Ethernet interface Page 143 Windows IP address runtime IP address Windows IP address and runtime IP address must be in the same subnet Ethernet interface for SIMOTI...

Page 142: ...anel Network and Sharing Center Note Windows Firewall To allow the Windows IP to be accessed externally this must be set as an exception in the Windows firewall File and Printer Sharing Otherwise there is only limited access to Windows from outside Parameter assignment addressing 9 5 Ethernet communication SIMOTION P320 4 E P320 4 S 142 Commissioning and Hardware Installation Manual 11 2016 ...

Page 143: ...dresses for Windows are determined automatically 9 5 4 Communication via an Ethernet interface If both Windows and SIMOTION use the onboard Ethernet interface X1 the following configuration is present 6XEQHWV URXWHU SRVVLEOH 6 027 21b3 2QERDUG WKHUQHW 6 027 21 3 5XQWLPH 3 DGGUHVV 3 DGGUHVV LQGRZV HIDXOW DWHZD 6 027 21 3 Figure 9 13 Distribution of the IP addresses for Windows and SIMOTION P Runtim...

Page 144: ...g for the default gateway must be identical for the IP addresses 1 and 2 Procedure in HW Config to change the default IP addresses 1 Double click PNxIE of the PC station The following dialog box is opened 2 Click the Properties button of the Properties PNxIE dialog box Parameter assignment addressing 9 5 Ethernet communication SIMOTION P320 4 E P320 4 S 144 Commissioning and Hardware Installation ...

Page 145: ...the onboard Ethernet interfaces The onboard Ethernet interface must be activated for the SIMOTION P Runtime default setting activated You can check the activation via the Administration tab of the SIMOTION P Control Manager accessible via the Windows Control Panel with Start Control Panel The Activate Device checkbox is displayed after selecting the button for Onboard RT Ethernet Properties Parame...

Page 146: ...Figure 9 15 SIMOTION P Control Manager Administration Parameter assignment addressing 9 5 Ethernet communication SIMOTION P320 4 E P320 4 S 146 Commissioning and Hardware Installation Manual 11 2016 ...

Page 147: ...SIMOTION SCOUT 2 Click the button Open NetPro NETPRO is accessed and the configured network is graphically displayed The PG PC connection to the configured network is shown not bold and in a color other than yellow 3 Double click on the PG PC that you would like to configure The Properties PG PC dialog box is displayed with the Assignment tab in the foreground 4 In the field Assigned select the in...

Page 148: ...cs Communication PROFINET IO 9 7 PROFIBUS communication 9 7 1 Documentation Description of PROFIBUS communication A detailed description of PROFIBUS communication can be found in SIMOTION Communication System Manual or SIMOTION SCOUT Online Help under Basics Communication PROFIBUS DP Parameter assignment addressing 9 7 PROFIBUS communication SIMOTION P320 4 E P320 4 S 148 Commissioning and Hardwar...

Page 149: ...16 Inserting a SIMOTION device selecting the device version Behavior of the P320 4 PN device with the P320 4 PN DP module If a P320 4 PN device with created PN line is loaded to a P320 4 PN DP module the project runs exactly as on a P320 4 PN module Parameter assignment addressing 9 8 Project download SIMOTION P320 4 E P320 4 S Commissioning and Hardware Installation Manual 11 2016 149 ...

Page 150: ...clock Behavior of the P320 4 PN DP device with the P320 4 PN module Note A P320 4 PN DP device generally does not run on a P320 4 PN module The following message is displayed in the diagnostic buffer Source 0 could not be loaded inconsistency The loaded configuration is not suitable Parameter assignment addressing 9 8 Project download SIMOTION P320 4 E P320 4 S 150 Commissioning and Hardware Insta...

Page 151: ... battery for buffering CMOS data and buffered SRAM is at least 1 month You will find further information on the battery warning at Two stage battery monitoring Page 186 Lithium battery ordering data Designation Article number Further information Lithium battery A5E30314053 Spare part Parameter assignment addressing 9 9 Battery monitoring SIMOTION P320 4 E P320 4 S Commissioning and Hardware Instal...

Page 152: ...Parameter assignment addressing 9 9 Battery monitoring SIMOTION P320 4 E P320 4 S 152 Commissioning and Hardware Installation Manual 11 2016 ...

Page 153: ... following requirements must be met before initial commissioning The device is connected to the 24 VDC power supply Equipotential bonding is connected 10 3 Commissioning requirements Prior activities You have already performed the following actions Your system has been installed and wired The installation and parameterization has been completed When networking via PROFINET the PROFINET addresses o...

Page 154: ...ividual steps for first commissioning are listed below in the recommended order 1 The complete system is connected mechanically and electrically and has been verified SIMOTION P320 4 Drives Motors SIMATIC S7 I O components HMI user interfaces 2 The article numbers of the drives and SIMATIC S7 I O components should be available You need these order numbers when setting up a SIMOTION project to veri...

Page 155: ...emories on drives C and D The SIMOTION P Kernel and Windows system software are located on the internal storage medium on drive C Media The following figure shows the partitioning of the storage medium in the delivery state depending on the version of the SIMOTION P320 4 GULYH ULYH 66 DVW 8VHU GDWD 6 VWHP GDWD DVW DVW 6 027 21 3 6 6 027 21 3 Figure 10 1 Storage media of the SIMOTION P320 4 Commiss...

Page 156: ... and quick restoration of entire memory cards The SIMATIC IPC Image Partition Creator only supports the burning of DVD media This software is available via the online ordering system Siemens Industry Mall http www siemens com industrymall You can find more accurate information about the tool in the associated product documentation 10 6 3 Restore DVD SIMOTION P320 4 is supplied with pre installed h...

Page 157: ... Windows use the SIMOTION P State application To do this you must be logged on with administrator privileges Only the administrator is offered the button for the Terminate SIMOTION P function After explicitly terminating the SIMOTION P Kernel via the SIMOTION P State application the SIMOTION P Kernel can be restarted via this application Start SIMOTION P button A restart of Windows also results in...

Page 158: ...st possible scope of a backup to the backing up of variables Although the backup restore of data in many cases is initiated by the user it is sometimes also performed automatically or started by the user program In addition to restoring defined states and updating reloading a project in the target device data backups are also needed to prevent data loss resulting from a hardware defect or failure ...

Page 159: ... use system functions to perform a backup Version independent restoration of the retain data non volatile SIMOTION data Disadvantages No complete backup Defined states The Defined states Page 169 section describes the options for restoring a defined state initial state Application System defect Windows defect Restore a defined initial state for example during commissioning Commissioning software 1...

Page 160: ...0DLQ PHPRU 5 0 66 DVW FDUG 1 The user data must not be written by Windows during runtime SIMOTION P State RUN User data can be written from the Explorer or other applications in the Terminate SIMOTION P state Figure 10 2 SIMOTION P320 4 memory model 10 8 3 Project update 10 8 3 1 Overview The backup possibilities described in the following section can be used to update retransmit or back up a SIMO...

Page 161: ...HGLD 8VHU GDWD 6 027 21 3 65 0 5 0 QJLQHHULQJ 6 VWHP Figure 10 3 SIMOTION SCOUT download from the engineering system SCOUT project download online process 1 Load the project data via SIMOTION SCOUT menu Target system Load Load project into target system into the working memory of the SIMOTION P320 4 2 To transfer the data to the external storage medium use the menu Target system Copy RAM to ROM in...

Page 162: ... SIMOTION P320 4 e g with USB memory stick and Windows Explorer SIMOTION P must be in the terminated state for this Note Note the SIMOTION version The SIMOTION version on the target device must exactly match the version of the device on which the backup was created 10 8 3 4 SIMOTION SCOUT download of the project data with SIMOTION IT ZIP file SIMOTION SCOUT stores the project data in the form of a...

Page 163: ...6 027 21 3 LUPZDUH 2SHUDWLQJ V VWHP 66 DVW FDUG 6WRUDJH PHGLXP LQWHUQDO 5HWDLQ GDWD HUQHO GDWD XUUHQW GDWD DFNXSV 6WRUDJH PHGLXP H WHUQDO DVW FDUG 6 027 21 3 6WRUDJH PHGLD QJLQHHULQJ V VWHP 6 027 21 3 65 0 5 0 Figure 10 5 SIMOTION SCOUT download ZIP file Download of the project data process ZIP file 1 Save the data via SIMOTION SCOUT menu Edit Load to file system option Save compressed on the file...

Page 164: ...a storage medium of the SIMOTION P320 4 or a USB flash drive to the external CFast card and replace the existing directory This also enables series commissioning without a programming device or SIMOTION SCOUT 65 0 5 0 6WRUDJH PHGLXP LQWHUQDO 66 DVW FDUG DVW FDUG 6WRUDJH PHGLXP H WHUQDO 6 027 21b3 6WRUDJH PHGLD 6 027 21b3 LUPZDUH 2SHUDWLQJ V VWHP DFNXSV 8VHU GDWD 5HWDLQ GDWD HUQHO GDWD XUUHQW GDWD ...

Page 165: ...latile SIMOTION data retain data Page 166 Restoring non volatile SIMOTION data retain data Page 167 Backing up unit variables and global device variables Page 168 10 8 4 2 Back up restore SRAM The correct shutdown of Windows automatically initiates Terminate SIMOTION P SIMOTION P State This automatically saves the retain data from the SRAM to the external CFast card 6WRUDJH PHGLXP LQWHUQDO 66 DVW ...

Page 166: ...a SIMOTION SCOUT go online and in the context menu of a created source execute Save variables The data is saved in the unitdata xml file on the computer with SIMOTION SCOUT Alternatively the retain data is saved via the SIMOTION P State application via the SIMOTION P Set Diagnostic Switch menu The contents are saved to the PMEMORY XML backup file in the USER SIMOTION HMI SYSLOG DIAG directory To r...

Page 167: ...nt must be repeated 8VHU GDWD XUUHQW GDWD HUQHO GDWD 5HWDLQ GDWD 2SHUDWLQJ V VWHP 6 027 21b3 LUPZDUH 6 027 21b3 6WRUDJH PHGLD 6WRUDJH PHGLXP LQWHUQDO 66 DVW FDUG DVW FDUG 6WRUDJH PHGLXP H WHUQDO DFNXSV 6 027 21 3 65 0 5 0 Figure 10 9 Save retain data 10 8 4 4 Restoring non volatile SIMOTION data retain data The backup of the non volatile SIMOTION data variables declared as retain is restored in th...

Page 168: ...bal device variables Unit variables and global device variables are never retentive the data will be lost in the event of a power failure If the unit variables and global device variables which have not been declared as retain variables are to be recovered after a power failure the user program can use system functions to save this data to data sets files on the external CFast card 5HWDLQ GDWD HUQ...

Page 169: ... SIMOTION P State application Transfer backup from the file system Download backups that were stored on the file system using the backup mechanisms described previously For further information see Single backups Page 165 Detailed information about the backup options for detailed states can be found at Restore the factory setting using SIMOTION P State Page 169 Overall reset using SIMOTION P State ...

Page 170: ...tes the non volatile SIMOTION data and retain data 5HWDLQ GDWD HUQHO GDWD XUUHQW GDWD 8VHU GDWD DFNXSV 6 027 21b3 LUPZDUH 2SHUDWLQJ V VWHP 6 027 21b3 6WRUDJH PHGLD 6WRUDJH PHGLXP LQWHUQDO 66 DVW FDUG 6WRUDJH PHGLXP H WHUQDO DVW FDUG 65 0 5 0 6 027 21 3 Figure 10 13 General reset If a backup of the retain data PMEMORY XML exists this data will be accepted after the general reset Thus the user can p...

Page 171: ...eturned to a defined initial state The backed up program variables and retain variables and thus the encoder values homing data will be restored 5HWDLQ GDWD HUQHO GDWD XUUHQW GDWD 8VHU GDWD DFNXSV 6 027 21b3 LUPZDUH 2SHUDWLQJ V VWHP 6 027 21b3 6WRUDJH PHGLD 6WRUDJH PHGLXP LQWHUQDO 66 DVW FDUG 6WRUDJH PHGLXP H WHUQDO DVW FDUG 65 0 5 0 6 027 21 3 Figure 10 15 Delete SRAM Restart Del SRAM If the SIMO...

Page 172: ... overall reset overview Introduction When a general reset is performed the RAM on the SIMOTION P320 4 will be cleared along with any non volatile data in the SRAM with the exception of the communication configuration e g baud rates and network addresses For further information see Non volatile data and SRAM handling Page 189 Below is a list of the data that is either capable or not capable of with...

Page 173: ...ata deleted on general reset The following data is deleted on the SIMOTION P320 4 Configuration data Programs Parameter assignments Technology packages Data from absolute encoders absolute encoder adjustment cyclic range overflows Note Absolute encoder data is deleted during a general reset operation and must therefore be readjusted after the general reset Retain variables Retain variables are var...

Page 174: ...nd are transferred to the volatile data area of the SIMOTION P320 4 after the general reset Thus an existing configuration on the external CFast card is loaded to the SIMOTION device following the general reset Further information Data storage concept overview Page 157 10 9 2 Overall reset using the mode selector on screen For SIMOTION P320 4 the overall reset using a simulated mode selector is pe...

Page 175: ... the STOP operating state has been reached Figure 10 17 SIMOTION P State STOP operating state 2 When you release MRES the mode selector points to the STOP position again Figure 10 18 SIMOTION P State Mode selector from position MRES to STOP Commissioning software 10 9 SIMOTION P overall reset SIMOTION P320 4 E P320 4 S Commissioning and Hardware Installation Manual 11 2016 175 ...

Page 176: ...MOTION P State status MRES The mode selector then goes into the STOP position Figure 10 20 SIMOTION P State status MRES mode selector STOP 4 The SIMOTION P320 4 then restarts automatically Commissioning software 10 9 SIMOTION P overall reset SIMOTION P320 4 E P320 4 S 176 Commissioning and Hardware Installation Manual 11 2016 ...

Page 177: ...munication configuration and the user data on the CFast card are deleted You can thus continue to access the SIMOTION P320 4 with your PG PC Procedure To delete the user data 1 In SIMOTION SCOUT open the project you want to edit 2 Go online with SIMOTION P320 4 3 Select Target system Delete user data on card The data is deleted Commissioning software 10 10 Deleting user data on the CFast card SIMO...

Page 178: ... line side switch or through disconnection from the power supply NOTICE Do not protect external CFast cards with EWF Drive D the external CFast card must not be protected with EWF as otherwise the functionality of SIMOTION cannot be assured NOTICE Threat of data loss Always shut down SIMOTION correctly as otherwise there is a threat of data loss SIMOTION P320 4 If Windows is shut down properly the...

Page 179: ...ION P320 4 is still in the Running state the SIMOTION P320 4 is terminated automatically With large projects a black screen may be displayed in Windows with the message Waiting for SIMOTION P Please wait SIMOTION P is terminating The termination of the SIMOTION P Runtime can vary depending on the size of the project Figure 10 22 Black screen Commissioning software 10 11 Switching off SIMOTION P320...

Page 180: ...Commissioning software 10 11 Switching off SIMOTION P320 4 E P320 4 S 180 Commissioning and Hardware Installation Manual 11 2016 ...

Page 181: ...gnostics switch via the following option SIMOTION P State menu item SIMOTION P Set Diagnostic Switch The diagnostic data is recorded during operation and the SIMOTION P Set Diagnostic Switch switch automatically reset after writing the data Backing up diagnostic data Following a fault on a SIMOTION device diagnostic data e g diagnostic buffer content current content of website etc can provide impo...

Page 182: ...Single backups Page 165 11 2 Restoring factory settings 11 2 1 Overview of restoring the factory settings Note When the factory settings are reset restored licenses are retained 11 2 2 Resetting the SIMOTION P320 4 to the delivery status The SIMOTION P State application is used for this function Service and maintenance 11 2 Restoring factory settings SIMOTION P320 4 E P320 4 S 182 Commissioning an...

Page 183: ...g the Station Configurator will also be reset to the delivery status 11 2 3 Reset SIMOTION P320 4 to the initial state If an error occurred during parameter assignment download or when other settings were configured or if you are not sure whether you have specified all the information correctly it may be useful or necessary to reset the SIMOTION P320 4 to its state prior to parameter assignment Re...

Page 184: ... previous version is available on the included restore DVD The upgrade to the latest hotfix HF can be performed via a setup Procedure Possible types of upgrade Upgrade with external DVD drive First the upgrade software must be copied to an external DVD or USB memory stick Upgrade using a remote computer in the network connect the SIMOTION P320 4 to the drive of the remote computer via the network ...

Page 185: ...may only be replaced with an identical battery or with a type recommended by the manufacturer article number A5E30314053 WARNING Risk of explosion and release of harmful substances Therefore do not throw lithium batteries into an open fire do not solder or open the cell body do not short circuit or reverse the polarity do not heat to above 100 C dispose of them in accordance with regulations and p...

Page 186: ...stics buffer or at the very latest the first time the Battery error entry appears in the diagnostics buffer Disposal NOTICE Dispose of batteries properly Batteries must be disposed of in accordance with local regulations Preparation Note The configuration data and contents of the SRAM in the device are buffered for at least 30 seconds when the battery is replaced Preparation make a note of the BIO...

Page 187: ...cement loss of bit values in SRAM memory cells during battery replacement cannot be detected reliably SIMOTION P320 4 must then undergo an overall reset Tools You will need a T10 screwdriver to open the battery compartment Replacing the battery NOTICE Switch off the device before replacing the battery The battery can also be exchanged when the device is operating However we recommend switching off...

Page 188: ... Connect the battery plug to the new battery 5 Remove the old battery from the holder 6 Secure the new battery in the holder 7 Close the battery compartment Service and maintenance 11 4 Installing removing the back up battery of the SIMOTION P320 4 SIMOTION P320 4 E P320 4 S 188 Commissioning and Hardware Installation Manual 11 2016 ...

Page 189: ... up situations 11 5 1 Special startup situations overview The special power up situations are described in the following Non volatile data and SRAM handling Page 189 After new installation update of the SIMOTION P Kernel Page 191 After importing a backup copy Page 191 After a power failure POWER FAIL Page 192 Requirements You are familiar with the user storage concept of the non volatile data on t...

Page 190: ...on the storage medium of the SIMOTION P320 4 is used If the serial number of the SIMOTION P320 4 is not known The serial number of the SIMOTION P320 4 does not correspond to the one that was last saved on the SIMOTION P320 4 for example after the replacement of the SIMOTION P320 4 SRAM image storage medium or SRAM backup storage medium is OK if The SIMOTION software release of the SRAM image backu...

Page 191: ... software version with which the backed up user data of the SRAM was created Now SIMOTION P320 4 is immediately ready to run again Note If you do not want the backed up user data to be used again you will have to recommission the SIMOTION P320 4 Note Restart of SIMOTION P320 4 required After a new installation or update of the SIMOTION P Kernel a restart of the SIMOTION P320 4 is generally require...

Page 192: ...ailable again Now SIMOTION P320 4 is immediately ready to run again Note Backup of the user data in the SRAM of the SIMOTION P320 4 in case of power failure is only guaranteed if the SIMOTION P320 4 is operated within its defined specifications Case 2 SRAM not saved If the hardware of the SIMOTION P320 4 was operated outside of the defined specifications the user data might not have been backed up...

Page 193: ...te is selected the LED will flash until the operating state is actually attained 5 Hz FAULT state SIMOTION software does not run in the FAULT state all LEDs flash simultaneously STOPU Yellow SIMOTION P in the STOP user program This LED indicates that the technology packages are active No user program is being executed LED flashing 2 Hz When the STOPU operating state is selected the LED will flash ...

Page 194: ...INET IO with IRT has not been configured LED On The PROFINET interface has synchronized to the send cycle clock of PROFINET IO with IRT LED flashes 2 Hz A PROFINET firmware download is in progress 5 Hz FAULT state SIMOTION software does not run in the FAULT state all LEDs flash simultaneously BUS1F BUS2F X101 X102 Status of IsoPROFIBUS inter face LED Red If this LED is red it indicates a fault at ...

Page 195: ... Accessible nodes HW Config NetPro Start the Accessible nodes function in SIMOTION SCOUT Select a device and Flashing or Stop flashing is selected via the context menu Figure 12 1 Accessible nodes Alternatively you can also activate the DCP flashing function in HW Config or in NetPro under the following path Target system Ethernet Edit Ethernet node via the Browse button in the Search Network dial...

Page 196: ...ollowing actions may be required to rectify the fault Power OFF ON Recommissioning Table 12 4 LED combinations LED SF RUN STOPU STOP SF PN SY MT BUSF1 BUSF2 FAULT 5 red 5 red 5 red 5 red 5 red 5 red 5 red 5 red 5 Flashes with a frequency of 5 Hz 12 2 Temperature alarm For SIMOTION P320 4 two different temperatures are monitored in the device as regard to whether they reach their respective thresho...

Page 197: ...ble response to this battery state For this case the system variable persistentdatapowermonitoring warningbatteryvoltagelevel1 can be used to catch the complete loss of the retain data if the battery cannot be replaced fast enough Users should periodically save their retain data e g with the _savePersistentMemoryData function This ensures that the operating state established after the next start u...

Page 198: ...er supply If the voltage is not within the limits for the supply voltage of the SIMOTION P320 4 19 2 28 8 VDC then change the external power supply Windows If the SIMOTION P320 4 is shut down during operation the Windows installation may be damaged The consistency of Windows applications cannot be guaranteed during a power failure In these cases we strongly recommend use of an EWF or a UPS system ...

Page 199: ...ted I O device At least one of the assigned I O devices cannot be addressed Incorrect or no configuration PROFINET LAN X3 Port P1 P2 P3 The two LEDs on the respective PROFINET ports also provide information on the current connection status PROFINET interface LED 1 On Off Lights up green Link No physical connection available Troubleshooting Check for loose connector defective cable etc LED 2 On Off...

Page 200: ...ted if critical errors occur If the POST does not return an error the BIOS initializes and tests further functional units In this startup phase the graphics controller is initialized and any error messages are output to the screen The following lists the error messages from the system BIOS For information on error messages output by the operating system or programs refer to the corresponding manua...

Page 201: ...tton has been set to dark Set the monitor brightness button to obtain more light For detailed information refer to the monitor operating instruc tions The power cord or the mon itor cable is not connected Check whether the power cord has been properly connected to the monitor and to the system unit or to the grounded shockproof outlet Check whether the monitor cable has been properly connected to ...

Page 202: ... technical support team UPS does not function The operating system does not have a suitable driver for the UPS Install a suitable driver the correct driver can often be downloa ded from the homepage of the device s manufacturer See also Section Customer specific software Page 118 IP address assigned twice e g through series commis sioning Default IP address for Win dows See Default IP addresses fo...

Page 203: ...ult settings may differ from the following figures 2 After completing the startup test you can start the program setup with BIOS The following message is shown on the display Figure 13 1 SIEMENS Press Esc boot options Press Esc Troubleshooting FAQs 13 2 Hotplug Enabled BIOS settings SIMOTION P320 4 E P320 4 S Commissioning and Hardware Installation Manual 11 2016 203 ...

Page 204: ...up process Boot Manager Selection of the boot drive Boot From File Starting from a EFI file SCU Device configurator Setup Configuration Utility BIOS Update BIOS update from USB stick MEBx Start the Intel Management Engine BIOS Extension 5 Select the SCU device configurator Troubleshooting FAQs 13 2 Hotplug Enabled BIOS settings SIMOTION P320 4 E P320 4 S 204 Commissioning and Hardware Installation...

Page 205: ...nfiguration Press Enter to confirm the selection Figure 13 3 Advanced IDE configuration 7 In the IDE Configuration window select SATA Port 2 HotPlug Troubleshooting FAQs 13 2 Hotplug Enabled BIOS settings SIMOTION P320 4 E P320 4 S Commissioning and Hardware Installation Manual 11 2016 205 ...

Page 206: ...selection shown here to Enabled Figure 13 4 IDE Configuration SATA Port 2 HotPlug Troubleshooting FAQs 13 2 Hotplug Enabled BIOS settings SIMOTION P320 4 E P320 4 S 206 Commissioning and Hardware Installation Manual 11 2016 ...

Page 207: ...the subsequent prompt to save the settings and exit the BIOS setup with Yes Figure 13 5 Confirming SATA Port 2 HotPlug Enabled Troubleshooting FAQs 13 2 Hotplug Enabled BIOS settings SIMOTION P320 4 E P320 4 S Commissioning and Hardware Installation Manual 11 2016 207 ...

Page 208: ...Troubleshooting FAQs 13 2 Hotplug Enabled BIOS settings SIMOTION P320 4 E P320 4 S 208 Commissioning and Hardware Installation Manual 11 2016 ...

Page 209: ...ile E115352 File E85972 You can find further information on the respective device on the Internet at http database ul com cgi bin XYV template LISEXT 1FRAME index htm Enter the first seven characters of the article number at Keyword Then click Search Korea certification KC registration number KCC REM S49 SIMOTION Note that this device complies with limit class A with regard to the emission of radi...

Page 210: ...Standards and approvals A 1 General rules SIMOTION P320 4 E P320 4 S 210 Commissioning and Hardware Installation Manual 11 2016 ...

Page 211: ...ly touch components modules and devices if you are first grounded by applying one of the following measures Wearing an ESD wrist strap Wearing ESD shoes or ESD grounding straps in ESD areas with conductive flooring Only place electronic components modules or devices on conductive surfaces table with ESD surface conductive ESD foam ESD packaging ESD transport container B 2 Electrostatic charging of...

Page 212: ...t You should only touch ESD components if unavoidable for example during maintenance work When you touch modules make sure that you do not touch either the pins on the modules or the printed conductors If you follow these instructions electrostatic discharge cannot reach or damage sensitive components If you have to take measurements on a module make sure that you first discharge any static that m...

Page 213: ...r operation DTR Data Terminal Ready Data terminal is ready DVI I Digital Visual Interface Digital display interface with digital and VGA signals ESD Components sensitive to electrostatic charge EN European standard EWF Enhanced Write Filter Configurable write filter SIMOTION P320 4 E FAQ Frequently Asked Questions FAQs GND Ground Chassis ground HMI Human Machine Interface User interface HW Hardwar...

Page 214: ...ic RAM SVP Serial No of the device SW Software TFT Thin Film Transistor Type of LCD flat screen TxD Transmit Data Data transfer signal UL Underwriters Laboratories Inc US organization for tests and certifications according to own or binational standards with CSA Canada standards UMA Unified Memory Architecture Video memory USB Universal Serial Bus UPS Uninterruptible power supply VCC Positive supp...

Page 215: ...le PROFINET 103 Bus connector PROFINET 103 Bus fault PROFINET 199 C CE marking 209 CFast card Article number 84 Deleting user data 177 Inserting 85 Production version 83 Withdrawing 85 CFast card withdrawn During operation 87 Change Password 33 Cloud computing 26 Communication Ethernet interface 143 Company security 29 Connecting IsoPROFIBUS board 110 PROFINET on SIMOTION P320 4 102 Connecting Eth...

Page 216: ...t data with SIMOTION IT 163 Drive systems For connection via PROFINET 58 E Effects 25 Electromagnetic compatibility 209 EMC directives 209 EMERGENCY OFF concept 113 Enhanced Write Filter CFast card 178 SIMOTION P320 4 E 178 Equipotential bonding SIMOTION P320 4 115 Error correction SIMOTION P320 4 201 Error messages on the screen 200 ESD guideline 211 ET 200 58 Ethernet Cable 112 Default IP addres...

Page 217: ... battery 185 Local HMI ES SIMOTION P320 4 60 Logoff 179 M MAC bridge miniport 60 Setting up 61 Main memory P320 4 53 Media SIMOTION P320 4 155 Memory model SIMOTION P320 4 160 Messages on the screen 200 Microsoft loopback adapter Installing 65 Mobile devices 26 Mobile networks 26 Mode selector Overall reset 174 SIMOTION P State 121 SIMOTION P320 4 121 N Network bridge Setting up 61 Network connect...

Page 218: ...89 SIMOTION P Kernel 157 SRAM handling 189 Processor P320 4 53 PROFINET Bus fault 199 Cable types 103 Connecting to SIMOTION P320 4 102 Connection status 199 Connector 103 P320 4 54 SIMOTION P320 4 connection example 102 Strain relief 103 PROFINET connection example SIMOTION P320 4 102 Project data file structure back up restore 164 Protection zone 30 Protective conductor connection SIMOTION P320 ...

Page 219: ...me 56 HMI software 57 Power up without CFast card 86 SIMOTION SCOUT 57 Software 56 SIMOTION P State 123 Application 119 Diagnostics 193 General reset 170 Hardware version 125 Information about SIMOTION P State 125 LED display 120 Mode selector 121 Operating state 122 Overview 119 Reset to factory default 125 Restart 123 Restart Del SRAM 123 Restoring the default settings 169 Set Diagnostic Switch ...

Page 220: ...y status 182 Safety instructions 20 Set PG PC interface 137 SIMOTION P State 119 120 123 SIMOTION P Kernel 157 Software additional 118 Standard rail mounting 89 Station Configurator 138 Storage media 155 Strain relief 103 Sublicensing 200 Use planning 77 Versions 51 SIMOTION P320 4 E 51 Enhanced Write Filter 178 SIMOTION P320 4 S 51 Smart Grid 26 Software Additional 118 Software version 125 Softwa...

Page 221: ...ertical mounting Accessories 91 Screwing on the angle bracket 91 Virus scanner Requirements 34 Virus scanners SIMOTION P320 4 35 W Warranty 20 Web server SIMOTION P State 124 WinCC flexible 118 Windows Default IP address 143 Windows 7 Ultimate 32 bit Data backup 156 Windows Embedded Standard 7 32 bit Data backup 156 Windows locked Password 79 Windows password Changing 38 Permitting changes 36 Wind...

Page 222: ...Index SIMOTION P320 4 E P320 4 S 222 Commissioning and Hardware Installation Manual 11 2016 ...

Reviews: