INTRODUCTION
Model SA-3I and SA-11P detectors from Siemens Industry, Inc. are self-contained air duct detec-
tors designed for installation in heating, ventilating, and air conditioning duct systems. These
Detector Models SA-3I and SA-11P can use ionization or photoelectric smoke detectors to sig-
nal the presence of combustion products in a duct system. (Refer to TECHNICAL DATA for informa-
tion on compatible detectors.)

In addition to the self-contained detection features of the SA-3I and SA-11P, these air duct
detectors also can power and supervise the following configurations.

(1) two air duct detectors (Model AD-3I or AD-11P) mounted on the exterior of the duct and

employing sampling tubes to monitor the air in the duct, or

(2) two spot detectors (Model PE-11) mounted on the interior wall of the air duct, or

(3) one each of the detectors listed in (1) and (2) above.

TECHNICAL DATA

Smoke Detector Compatibility:

SA-3I - Use Model DI-B3 or DI-B3H only
SA-11P - Use Model PE-11
AD-3I (Satellite) - Use Model DI-B3 or DI-B3H only
AD-11P (Satellite) - Use Model PE-11

Operation Voltage and Current:

120 VAC (50/60 Hz), .32A max

Alarm Relay:

DPDT contacts, rated at 125 VAC/24 VDC, 3A Resistive

Trouble Relay:

SPDT contacts, rated at 125 VAC/24 VDC, 2A Resistive

Smoke Detector Sensitivity:

Factory set for air duct application—See detector

nameplate label

Alarm Indicator:

LED on smoke  detector  displays steady or flashing red
light through air duct cover

Temperature Range:

32

O

F (0

O

C) to 100

O

 F (37.8

O

C) per UL 268/268A

Altitude  Range:

SA-3I, using DI-B3 - Altitude range is 0 to 4000 feet

above sea level

SA-3I, using DI-B3H - Altitude range is 3000 to  8000  feet

above sea level

SA-11P, using PE-11 - No altitude limitations; detectors

unaffected by altitude

Relative Humidity Range

0 to 93% (non-condensating) RH per UL 268/268A

Air Duct Velocity Range:

SA-3I:

500 to 4000 ft/min

SA-11P:

300 to 4000 ft/min

Sampling Tube Pressure

SA-3I:

0.017 to 1.07  inches of water

Differential Range:

SA-11P:

0.006 to 1.07  inches of water

CAUTION:

These air duct detectors are designed for detection of products of combus-
tion in a duct system. They are not to be used for open area protection.

P/N 315-096274-4

Siemens Industry, Inc.

Building Technologies  Division

Florham Park, NJ

Siemens Building Technologies, Ltd.

Fire Safety & Security Products

2 Kenview Boulevard

Brampton, Ontario

L6T 5E4 Canada

Summary of Contents for SA-3I

Page 1: ... 2 above TECHNICAL DATA Smoke Detector Compatibility SA 3I Use Model DI B3 or DI B3H only SA 11P Use Model PE 11 AD 3I Satellite Use Model DI B3 or DI B3H only AD 11P Satellite Use Model PE 11 Operation Voltage and Current 120 VAC 50 60 Hz 32A max Alarm Relay DPDT contacts rated at 125 VAC 24 VDC 3A Resistive Trouble Relay SPDT contacts rated at 125 VAC 24 VDC 2A Resistive Smoke Detector Sensitivi...

Page 2: ...m from the filters and positioned so as to operate reliably in case of smoke in any part of the air stream In instances where the filters are capable of removing smoke a detector should be installed both upstream and down stream from the filters The air duct detectors because they use sampling tubes which monitor the full width of an air duct overcome the limitations of spot type smoke and heat de...

Page 3: ... 16 17 COMPONENT COMPONENT COMPONENT COMPONENT 2 Sampling Tube Gasket 1 Housing 1 Inlet Sampling Tube 1 Outlet Sampling Tube 1 Template 2 Screw No 10 1 2 Lockwasher 1 Rubber Stopper 3 Bracket 3 Screw 3 16 1 Plug 1 Detector PE 11 1 Ionization Detector Cover 1 Detector DI B3 DI B3H 1 Sensitivity Test Jack Lid 1 Cover Gasket 1 PE 11 Detector Cover 1 DB ADPT Base Adapter 12 18 3 Screw 8 32 8 Screw No ...

Page 4: ...ockwashers 8 e Cut a 12 inch by 12 inch access hole in the duct adjacent to the housing to permit checking and cleaning of the sampling tubes The access hole must be covered and sealed when not in use Sampling Tube Selection To insure accurate air sampling inlet sampling tubes are available in four lengths To select the appropriate length determine the outside width of the duct Select the sampling...

Page 5: ...uld be taken by qualified personnel in accordance with the PDM 3 Instructions P N 315 085535 ELECTRICAL WIRING The Air Duct Detector Model SA 3I 11P is interconnected and wired following the wiring diagram in Figure 6 Each model requires a two wire circuit of 18 AWG min thermoplastic fixture wire enclosed in conduit or of 18 AWG min limited energy shielded cable without conduit if permitted by loc...

Page 6: ... for Models SA 3I and SA 11P CAUTION Do not use looped wire under terminal 5 of the DB 3S or DB 11 base Break wire run to provide supervision of both connections conduit ensure that it is properly connected to the internal metal ground strap using the proper conduit locking nuts Failure to provide proper grounding may result in fatal electrical shock 7 Connect EOL device 1 3K 1 2W resistor to term...

Page 7: ...to place Installation Removal of PE 11 Detector in Base Adapter To Install Align detector with base and insert detector Rotate detector counterclockwise while gently pressing on it until the detector drops fully into base Then rotate the detector clockwise until it stops and locks in place Insert optional locking screw Order Model LK 11 To Remove Rotate the detector counterclockwise until stop is ...

Page 8: ... listed limits MAINTENANCE The performance of the air duct detector unit may be adversely affected by dirt or foreign matter on the sampling tubes or detector If the air holes in the inlet sampling tube become restricted the unit cannot receive a proper air sample and performance is impaired It is recommended that the sampling tubes be checked and cleaned periodically The detector maintenance prog...