P/N 315-094970-5

Installation and Power Limited Wiring Instructions

Model MLE-6
Enclosure for the MXL/MXLV Control Panel

INTRODUCTION

Model MLE-6 from Siemens Industry, Inc. is a
large-size enclosure for the MXL/MXLV System.
The enclosure consists of a backbox and front
door that is shipped assembled. Note that the
backbox has a flanged lip to permit semi-flush
mounting in addition to the usual surface
mounting.

Consider the following when mounting the
backbox:

• Mounting height for visual and manual

access to the MKB-2 Keyboard/annunciator

• Weight and size of enclosure
• Local mounting codes

Fasten the backbox securely to a clean, dry,
shock-free, and vibration-free surface. MLE-6
enclosure is for indoor use only in dry environ-
ments. Position the backbox clear of obstruc-
tions so that the front door opens freely and so
that the indicators and controls are easily
accessible.

NOTE: When the backbox is mounted semi-

flush, be sure that the position of the
backbox permits the front door to
swing fully open.

To install the MLE-6 backbox:

(Refer to Figure 1.)

1. Slip the front door off the hinges of the box

and put it to one side temporarily.

2. Remove the knockouts in the backbox

where field wiring is required.

3. Hold the empty backbox against the wall at a

height that provides easy access.

4. Mark drill points on the wall in the center of the

two slots on the upper rear of the backbox.

5. Drill the two holes and screw in the top bolts,

leaving a gap between the wall and the rear
of each bolt head.

6. Mount the backbox on the two bolts and then

install the bottom bolts in the two holes provided.

7. Tighten all bolts securely against the back

wall of the backbox.

8. Slip the front door back on the hinges of the

backbox (See Figure 2).

Figure 1

Mounting the Backbox

Siemens Industry, Inc.
Building Technologies Division
Florham Park, NJ

Siemens Building Technologies, Ltd.
Fire Safety & Security
2 Kenview Boulevard
Brampton, Ontario
L6T 5E4 Canada

Summary of Contents for MLE-6

Page 1: ... accessible NOTE When the backbox is mounted semi flush be sure that the position of the backbox permits the front door to swing fully open To install the MLE 6 backbox Refer to Figure 1 1 Slip the front door off the hinges of the box and put it to one side temporarily 2 Remove the knockouts in the backbox where field wiring is required 3 Hold the empty backbox against the wall at a height that pr...

Page 2: ...ng is not used within an MXL MXLV enclosure then the follow ing guidelines do not apply In that case be sure to follow standard wiring practices FRONT DOOR The front door is the main outer door for the MLE 6 enclosure The door is supplied without filler plates for the three large openings To select the appropriate filler plates for the three openings follow the information below When visual indica...

Page 3: ...Wiring Note Power limited circuits must use type FPLP FPLR or FPL cable per article 760 of the NEC Wiring to the following MXL MXLV module terminations See Table 2 is considered power limited and must enter the enclosure through knockouts dedicated to power limited wiring Wiring between these knockouts and the module terminations must be in the shortest route and most not overlap any other wiring ...

Page 4: ...urce WIRING IN THE REMOTE ENCLOSURE Non Power Limited Wiring The following wiring is considered non power limited from the MPS 6 W or MPS 12 W from the batteries to the PSR 1 To maintain the required 1 4 inch separation from other wiring these wires must be routed and held in place by a separate wire support This support is positioned on the left side wall of the enclosure To provide the separatio...