SIMATIC 

ET 200S distributed I/O 

Power module PM-E DC24V 

(6ES7138-4CA01-0AA0) 

Manual 

 

  

04/2007 

A5E01119952-02 

Preface 

 

 

 

Properties 

 

 

Parameters 

 

 

Diagnostics 

 

 

Configuring 

 

 

Summary of Contents for 6ES7138-4CA01-0AA0

Page 1: ...________ ___________________ ___________________ ___________________ ___________________ SIMATIC ET 200S distributed I O Power module PM E DC24V 6ES7138 4CA01 0AA0 Manual 04 2007 A5E01119952 02 Preface Properties 1 Parameters 2 Diagnostics 3 Configuring 4 ...

Page 2: ...y personnel qualified for the specific task in accordance with the relevant documentation in particular its warning notices and safety instructions Qualified personnel are those who based on their training and experience are capable of identifying risks and avoiding potential hazards when working with these products systems Proper use of Siemens products Note the following WARNING Siemens products...

Page 3: ... to the fact that it is low in contaminants this ET 200S module is recyclable For environmentally compliant recycling and disposal of your electronic waste please contact a company certified for the disposal of electronic waste Additional support If you have any questions relating to the products described in this manual and do not find the answers in this document please contact your local Siemen...

Page 4: ...m automation csi_en_WW service Service Support on the Internet In addition to our documentation we offer a comprehensive knowledge base on the Internet http www siemens com automation csi_en_WW support There you will find Our Newsletter which constantly provides you with the latest information about your products The right documentation for you using our Service Support search engine The bulletin ...

Page 5: ...A5E01119952 02 5 Table of contents Preface 3 1 Properties 7 1 1 Power module PM E DC24V 6ES7138 4CA01 0AA0 7 2 Parameters 11 3 Diagnostics 13 3 1 Diagnostics using LED display 13 3 2 Error types 14 4 Configuring 15 4 1 Configuring the address space 15 Index 17 ...

Page 6: ...Table of contents Power module PM E DC24V 6ES7138 4CA01 0AA0 6 Manual 04 2007 A5E01119952 02 ...

Page 7: ... DC24V power module is suitable for fail safe modules Extended temperature range from 0 to 55 C with vertical installation CAUTION Only connect the specified rated load voltage of 24 VDC to the TM P terminal module of the power module The connected rated load voltage must correspond to the supply voltage of the electronic modules in the voltage group Maximum configuration per voltage group The num...

Page 8: ...inal assignment Note Terminals A4 and A8 are only available at specified terminal modules Terminal assignment for PM E DC24V 6ES7138 4CA01 0AA0 Terminal Assignment Terminal Assignment Notes 2 L 6 L L Rated load voltage 24 VDC M Chassis ground AUX1 Protective conductor terminal or potential bus freely usable up to 230 VAC 3 M 7 M A4 AUX1 A8 AUX1 ...

Page 9: ...0AA0 TM P15C23 A1 6ES7193 4CC30 0AA0 TM P15C23 A0 6ES7193 4CD30 0AA0 TM P15C22 01 6ES7193 4CE10 0AA0 Spring terminal TM P15S23 A1 6ES7193 4CC20 0AA0 TM P15S23 A0 6ES7193 4CD20 0AA0 TM P15S22 01 6ES7193 4CE00 0AA0 Screw type terminal TM P15N23 A1 6ES7193 4CC70 0AA0 TM P15N23 A0 6ES7193 4CD70 0AA0 TM P15N22 01 6ES7193 4CE60 0AA0 Fast Connect Block diagram Figure 1 1 Block diagram of the PM E DC24V p...

Page 10: ...ic circuit breakers Yes tripping characteristic B C Max current carrying capacity up to 60 C 10 A Short circuit protection No Electrical isolation Between rated load voltage and backplane bus Yes Between the power modules Yes Insulation test voltage 500 VDC Current consumption From the load voltage L no load Max 4 mA Power dissipation of the module Typically 100 mW Parameter length 3 bytes Status ...

Page 11: ...Default setting Applicability Diagnostics No load voltage Disable enable Disable Power module The parameters are explained below Diagnostics No load voltage Use this parameter to enable a diagnostic message because there is no load voltage If there is no load voltage only the diagnostic message of the affected power module is sent to the DP master The SF error LEDs of all modules in the relevant v...

Page 12: ...Parameters Power module PM E DC24V 6ES7138 4CA01 0AA0 12 Manual 04 2007 A5E01119952 02 ...

Page 13: ...oltage green Status and error displays by means of LEDs on power modules The table below shows the status and error displays on the power module Event LEDs Cause Remedy SF PWR On No parameter assignment or incorrect module plugged in A diagnostic message is pending Check the parameter assignment Evaluate the diagnostics Off There is no load voltage at the power module Check the load voltage ...

Page 14: ...pes The diagnostic message is reported on channel 0 and applies to the entire module The table below shows the types of errors affecting power modules Table 3 1 Power module error types Error type Meaning Remedy 17D 10001 Encoder or load voltage missing Supply voltage not present or too low Correct the process wiring Check the supply voltage ...

Page 15: ... the corresponding entry in the configuration software is configured or which entry has been selected This table shows the PII feedback interface and the PIO control interface for different entries Table 4 1 PII feedback interface and PIO control interface With STEP 7 HW Config or COM PROFIBUS or other configuration software PII feedback interface PIO control interface Usual entry for the power mo...

Page 16: ...nfiguring 4 1 Configuring the address space Power module PM E DC24V 6ES7138 4CA01 0AA0 16 Manual 04 2007 A5E01119952 02 Status byte for power modules Figure 4 1 Assignment of status byte for power modules ...

Page 17: ...ic knowledge requirements 3 Block diagram 9 D Disposal 3 I Internet Service Support 4 P Parameters For power modules 11 Power modules Parameters 11 Properties 7 R Recycling 3 S Scope Manual 3 Service Support 4 T Technical data 10 Technical Support 4 Terminal assignment 8 Training Center 3 ...

Page 18: ...Index Power module PM E DC24V 6ES7138 4CA01 0AA0 18 Manual 04 2007 A5E01119952 02 ...