Eliminator Nano

Installation Manual

Central Heating Filter 

Version 1 – July 2014

IMPORTANT

Please retain these instructions 

for reference during servicing

Summary of Contents for Eliminator Nano

Page 1: ...Page 1 Eliminator Nano Installation Manual Central Heating Filter Version 1 July 2014 IMPORTANT Please retain these instructions for reference during servicing ...

Page 2: ...Page 2 Eliminator Nano Installation Manual V1 07 14 ...

Page 3: ... 4 General Description 5 Schematic Diagram 6 System Design 7 Mounting Considerations 8 Installation Procedure 9 11 Servicing 12 Dosing 13 Technical Specification 14 Guarantee 15 Please visit www sentinelprotects com uk guarantee registration for Guarantee Registration and Terms and Conditions ...

Page 4: ...heating engineer Always ensure that the system is fully drained and the pipework completely cooled before attempting installation Check very carefully for any leaks after fitting the filter and pressurising the system The T piece collar must be hand tightened only do not attempt to use a tool as this could damage the seal The filter bin is sealed permanently onto the main body of the unit do not a...

Page 5: ... such as magnetite and non magnetic particles with equal effectiveness In the interests of long term reliability the body of the filter is manufactured from a high performance glass reinforced engineering polymer which has been proven to withstand up to 13 bar static pressure The main filter body is permanently sealed Removal of collected deposits can be achieved by flushing at regular service int...

Page 6: ...IC DIAGRAM The main elements of the filter are shown below in Figure 1 A separate isolation valve is also supplied see later section Installation for further details Directional T piece Bleed valve Collection bin Anti tamper drain valve Dual seals Collar Fig 1 Filter components ...

Page 7: ...ion for further details of the working flow rate envelope The filter is designed only for temperatures of up to 80 C and pressure no greater than 3 bar Exposure to temperature and or pressure levels in excess of these values could lead to premature failure and would invalidate the warranty The filter should be mounted on the boiler return pipe only Prior to installation the system should cleaned w...

Page 8: ...d to drain the filter during servicing The filter can be fitted to either horizontal or vertical pipe work by rotating the T piece see Figure 2 for details Regardless of pipe work orientation the filter must be mounted vertically Also please ensure that the flow direction of the T piece is observed Check flow direction Rotate T piece to suit pipework Mount filter vertically Fig 2 Vertical or horizon...

Page 9: ...alve can be fitted on the opposing side of the filter as per Figure 3 As a result full isolation can be achieved within a minimal size envelope and with the fewest number of components Alternatively the filter can be fitted without the supplied valve but full isolation will not be possible should the filter ever subsequently need to be removed Page 9 Eliminator Nano Installation Manual V1 07 14 In...

Page 10: ...ssion fittings see Figure 4 for details of the T piece fitting method Ensure that the flow direction is correctly observed The nuts and olives can be found in a separate bag Step 4 Reposition the T piece gasket and secure the filter to the T piece ensuring that the retaining collar is hand tight Please do not in any circumstances use a tool to tighten the collar as this could result in damage to t...

Page 11: ...ully for any leaks and ensure that the drain valve is fully closed with handle in the horizontal position Ensure that the system is protected against corrosion and scale by dosing with Sentinel X100 Inhibitor or Sentinel X500 Inhibited Antifreeze whichever is appropriate for the property in question Correct levels of inhibitor can be checked with a Sentinel X100 Quick Test Kit ...

Page 12: ...n flushing a hot system Step 1 Place suitable shallow container underneath the filter Step 2 Remove the small nut retaining the drain valve handle See Figure 5 Step 3 Flip the handle over and re engage with the valve shaft Figure 6 Open valve to release the collected debris Step 4 Close the valve and replace handle together with small retaining nut Step 5 If necessary re pressurise the system topp...

Page 13: ...ep 3 Close the isolation valves and remove bleed pin slowly catching any escaping water Step 4 Cut down bleed pin adaptor to correct size for the valve Ensure the rubber bullet is next to the can actuator Step 5 Screw the dosing adaptor into the bleed valve Step 6 Open the isolation valves expect water to enter the tube the rubber bullet will seal the tube Step 7 Screw the Rapid Dose can onto the ...

Page 14: ...aterials Glass Reinforced Nylon 6 6 Brass Drain method Flush only Pipe Interface 22mm compression Isolation Valving 22mm ball valve compression fit GUARANTEE REGISTRATION Please complete and return the form opposite to Sentinel to register for your 2 year guarantee Alternatively you can register online at http www sentinelprotects com uk guarantee registration and select Eliminator Nano Full Terms...

Page 15: ...k here via Post Email Telephone Sentinel Performance Solutions Ltd and its sister companies may wish to send you information on products services and promotions in the future If you would like to receive communications please tick here via Post Email Telephone Installer Installer Name Company Address Postcode Telephone Email Place of purchase Date of purchase Date of installation RETURN COMPLETED ...

Page 16: ...expert advice any more information about the Sentinel Eliminator Nano or any other product in the range please contact customer services at Sentinel Performance Solutions Ltd 7650 Daresbury Park Warrington Cheshire WA4 4BS Tel 44 0 1928 704 330 www sentinelprotects com ...