SK-20NZ SMOKE ALARM INSTALLATION INSTRUCTIONS
Thank you for buying a Sentech photoelectric smoke alarm. Please read all 
instructions before installing the smoke alarm, so it will protect your home in the 
best possible way.
•  If you are installing the smoke alarm for some other person, leave these 

instructions or a copy of them with him/her.

•  The Sentech photoelectric smoke alarm is also suitable for use in camper 

vans, caravans, and boats.

1.  POSITIONING THE SMOKE ALARM
•  Place at least one smoke alarm per 60 m

2

 on each floor.

•  Place a smoke alarm in each corridor and bedroom.
•  The smoke alarm should be placed on the ceiling and ideally close to the 

middle of the room.

•  Place a smoke alarm at the top of each staircase.

AVOID THESE POSITIONS:
Near a wall or corner: 
Place the smoke alarm at a distance of at least 50cm from 
a wall or corner.
Moist places: Avoid installing smoke alarms near moist or occasionally moist 
places such as a shower or kitchen, where steam may cause a false alarm.
Ventilation ducts: Avoid installing a smoke alarm immediately next to a ventilation 
duct. The draft may prevent smoke from reaching the smoke alarm.  Smoke 
alarms can’t be installed in a location where the air velocity is more than 300ft/min 
(1.5 m/sec).
Dead-air spaces: Avoid installing a smoke alarm in the angle of a pitched roof. 
Install it at a distance of least 10cm from the ridge.
Fluorescent lamps: Avoid installing a smoke alarm immediately next to 
fluorescent lamps, such as halogen lights.
Radiation heating source: Avoid installing a smoke alarm radiant heating source. 
Radiant heating in the ceiling can create a hot air barrier layer along the ceiling 
surface which can seriously restrict the movement of smoke and heat towards a 
smoke alarm.

2:  OPERATION AND TESTING
Normal mode:
 The red light flashes once every 344 seconds (roughly 6 minutes) 
in normal mode.
Alarm mode: When the smoke alarm detects smoke, it goes into alarm mode in 
which the smoke alarm beeps continually and the red light flashes.
Test mode: Most of the alarm top/face is the test button. Press the test button 
until you hear the alarm sound and see the light flash. Release the button and the 
smoke alarm will go into silence mode (9 minutes).
Silence mode: During alarm mode, press the test button for 1 second to reset the 
smoke alarm.  The beep is silenced when the test button is released - the alarm 
then enters in to a 9 minute silence mode.  In silence mode, the red light flashes 
once every 10 seconds to indicate that the mode is active.
The silence mode will be cancelled if any of the following conditions exist:
• High smoke level. • Test button is activated again.
Error mode: The smoke alarm sends out a ‘beep’ three times every 43 seconds.
Remove the smoke alarm from the mounting plate and clean up the surface dust, 
then re-install. If the smoke alarm remains in error mode, contact the distributors 
as listed.
Low battery: When the battery is used up, the smoke alarm beeps at intervals of 
43 seconds.  You can silence the beep by pressing the test button for 3 seconds 
- during the 3 seconds the red light stays on and the beep sounds. After the 3 
seconds release the test button, and the ‘beep’ prompt is silenced for 8 hours. 

Pressing the test button for 3 seconds then releasing will also activate the smoke 
alarm in to a 9- minute silence mode.  At the end of the 8 hours, the audible 
indication will resume if the low battery condition still exists.
Local Alarm Memory: If the smoke alarm goes into alarm mode, it will enter the 
24 hours local alarm memory state after exiting alarm mode. 
In local alarm memory state, the green light flashes three times at 1.3 second 
intervals - this pattern will repeat every 43 seconds, and will stop after 24 hours, 
returning to normal mode.  You will still be able to identify a unit with an alarm 
memory by pressing the test button. When you press test button, the ‘beep’ 
sound will be once every 0.25 seconds - release the test button to revert from the 
local alarm memory state. The initial 24 hours visual indication is not displayed if 
the smoke alarm is in the low battery condition.
End of life indicator: After 10 years of operation, an audible warning signal 
occurs to indicate that the smoke alarm should be replaced. This indicator will 
be similar to the error mode warning that the smoke alarm sends out ‘beep’ three 
times every 43 seconds.

3. MAINTENANCE
Battery life: 
 The smoke alarm contains a 3V lithium battery (CR123A). The lifetime 
is 10 years. When the battery is used up, the smoke alarm beeps at intervals of 43 
seconds for at least 30 days. If the battery is used up, replace the smoke alarm as 
soon as possible.
WARNING: Lithium batteries can explode or cause burning if installed incorrectly. 
Do not attempt to replace the battery.
Clean the smoke alarm at least once a year. Separate the smoke alarm carefully 
from the installation plate by turning it counter-clockwise. 
Test the smoke alarm after cleaning it. Do not paint or modify the smoke alarm.
Waste handing: The smoke alarm should be disposed in accordance with normal 
waste handing for electronics.

4.  TECHNICAL INFORMATION

Operating principle: Photoelectric 

Warranty: 5 years 

Alarm current: < 200mA 

Sound volume: 

 85 dB  

at a distance of 3 meters

Dimensions: 42.5 x Ø50.8mm

Holding temperature of  
3M attachment tape -35°C~ 93°C

Maximum humidity: 93% 

Voltage: 3V (built-in lithium battery)

Quiescent current: < 3uA

Operating temperature: 0°C~ 45°C

Weight: 54 g

Conform to the standard: EN14604

5. MANUFACTURER’S GUARANTEE
The manufacturer provides a 5 year guarantee, starting from the purchase date 
of the product.  If the smoke alarm becomes defective during the guarantee 
period, the smoke alarm will be replaced with a new one providing the defective 
one is returned to the distributor. The guarantee covers manufacturing or material 
defects in the product, if the smoke alarm has been used according to the user 
instructions and the guarantee period has not expired.  The guarantee period for 
a smoke alarm that has been replaced with a new one is the same as that of the 
original smoke alarm. 

The guarantee is not valid if: 

1)   the product is used, maintained, or tested contrary to the user instructions,
2)   the defect has been caused by a negligent act by other than the manufacturer,
3)   if the product has been modified or treated with force, 
4)   if it the guarantee receipt is missing. 
The guarantee does not cover costs due to installation or battery replacement. 
The manufacturer’s responsibility does not in any case exceed the price of a new 
smoke alarm. The manufacturer is not responsible for any damage or loss that has 
been caused by a non-working smoke alarm or negligence by the manufacturer. 
This guarantee does not affect rights enacted by law.