manualshive.com logo in svg
background image

SpecificationS 

Operating Temperature: 

–20° to 60° C

Storage Temperature: 

–20° to 60° C

Humidity: 

0% to 93% Relative Humidity Non-condensing

Air Velocity: 

1.5 to 20.3 m/sec

Rectangular Footprint Dimensions: 

37 cm L x 12.7 cm W x 6.36 cm D

Square Footprint Dimensions: 

19.7 cm L x 22.9 cm W x 6.35 cm D

Weight: 

0.73 kg

Electrical
Power supply voltage: 

8.5-35 VDC

Input capacitance: 

0.1 µF max.

Reset Voltage: 

2.5 VDC min.

Reset Time (with RTS451/RTS151): 

.03 to 0.3 sec.

Reset Time (by power down): 

0.3 sec. max.

Power Up Time: 

35 sec. max.

Alarm response time: 

15 sec.

Sensitivity Test: 

See detector label

Current Requirements (Using No Accessories)
Peak standby current 

120µA

Average standby current 

60µA

Max. alarm current 

130 mA

SS-300-020 

I56-3536-003R

D2e Duct Smoke Detector

inStaLLation anD Maintenance inStRUctionS

table of contents 

page

[1] Limitations of Duct Smoke Detectors  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 1
[2] General Description  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 1
[3] Contents of the Duct Smoke Detector Kit  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 1
[4] Exploded View of Duct Smoke Detector Components   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 2
[5] Detector Installation  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 2
[6] Sampling Tube Installation   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 3
[7] Measurement Tests  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 3-4
[8] Field Wiring  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 4
[9] Detector Status Indicator  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 4
[10] Verification of Operator  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 5
[11] Dectector Cleaning Procedures  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 5
[12] Sensor Replacement  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 6
[13] Optional Accessories  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 6
Wiring Diagrams  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 4,6
Warranty 

  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 6

The  D2E  model  is  a  photoelectric  detector  approved  for  an  extended  air  speed 
range  of  1.5  m/s  to  20.3  m/s  and  an  operational  temperature  range  of  −20°C 
to 60°C.

BefoRe inStaLLing

Read the System Sensor Guide for Proper Use of Smoke Detectors in Duct Appli-
cations  (A05-1004),  which  provides  detailed  information  on  detector  spacing, 
placement,  zoning,  wiring,  and  special  applications.  Copies  of  this  manual  are 
available  online  at  www.systemsensor.com.  Refer  also  to  local  standards  and 
codes of practice. 
NOTICE: This manual shall be left with the owner/user of this equipment.
IMPORTANT:  This  detector  must  be  tested  and  maintained  regularly.  The  de-
tector should be cleaned at least once a year.

WARNING

DUCT  DETECTORS  MUST  NOT  BE  USED  AS  A  SUBSTITUTE  FOR  OPEN  AREA 
DETECTOR  PROTECTION  as  a  means  of  providing  life  safety.  Nor  are  they  a 
substitute for early warning in a building’s regular fire detection system.
This  device  will  not  operate  without  electrical  power.  Fire  situations  may 
cause  an  interruption  of  power.  The  system  safeguards  should  be  discussed 
with your local fire protection specialist.

This  device  will  not  sense  smoke  unless  the  ventilation  system  is  operating 
and the cover is installed.
For  this  detector  to  function  properly,  it  MUST  be  installed  according  to  the  in-
structions  in  this  manual.  Furthermore,  the  detector  MUST  be  operated  within 
ALL  electrical  and  environmental  specifications  listed  in  this  manual.  Failure 
to  comply  with  these  requirements  may  prevent  the  detector  from  activating 
when smoke is present in the air duct.

[2] geneRaL DeScRiption

Smoke  introduced  into  the  air  duct  system  will  be  distributed  throughout  the 
entire  building.  Smoke  detectors  designed  for  use  in  air  duct  systems  are  used 
to sense the presence of smoke in the duct. 
Model  D2E  Duct  Smoke  Detector  utilizes  photoelectric  technology  for  the  de-
tection  of  smoke.  This  detection  method,  when  combined  with  an  efficient 
housing  design,  samples  air  passing  through  the  duct  allowing  detection  of  a 
developing  hazardous  condition.  When  sufficient  smoke  is  sensed,  an  alarm 
signal  is  initiated  and  appropriate  action  can  be  taken  to  shut  off  fans, 
blowers,  change  over  air  handling  systems,  etc.  These  actions  can  facilitate 
the  management  of  toxic  smoke  and  fire  gases  throughout  the  areas  served 
by the duct system.

[2.1] DetectoR featURe Set

- Uses 2351E, SD-851E, ECO1003 and 2020P Detector Heads
- Sampling tubes installed from front or rear
- Compatible with existing accessories

[3] contentS of the DUct SMoke DetectoR kit

1. 

Sensor/power board assembly and covers

2. 

Three #10 sheet metal screws for mounting

3. 

One test magnet

4. 

Drilling template

5. 

One sampling tube end cap

6. 

One plastic exhaust tube

NOTE:  A  sampling  tube  must  be  ordered  to  complete  the  installation.  It  must 
be the correct length for the width of the duct where it will be installed. See Ta-
ble 1 on page 3 to determine the inlet tube required for different duct widths. 

I56-3536-003R

ACCESSORY CURRENT LOADS AT 24 VDC

DEVICE

STANDBY

ALARM

RA400Z/RA100Z

0mA

12mA Max .

[1] LiMitationS of DUct SMoke DetectoRS

Pittway Tecnologica Srl,

Via Caboto 19/3, 34147 Trieste, Italy

www.systemsensoreurope.com

Содержание Innovair Flex D2E

Страница 1: ...g in a building s regular fire detection system This device will not operate without electrical power Fire situations may cause an interruption of power The system safeguards should be discussed with your local fire protection specialist This device will not sense smoke unless the ventilation system is operating and the cover is installed For this detector to function properly it MUST be installed...

Страница 2: ...e 2 REMOVE SCREW AND PIVOT DETECTOR AS SHOWN BELOW REPLACE SCREW TO SECURE DETECTOR IN PLACE H0550 00 5 3 Drill the Mounting Holes Remove the paper backing from the mounting template supplied Affix the tem plate to the duct at the desired mounting location Make sure the template lies flat and smooth on the duct 5 3 1 For rectangular side by side mounting configuration Center punch at 4 target cent...

Страница 3: ...two sam pling tubes The differential pressure should measure at least 25 mm of water and no more than 28 2 mm of water Because most commercially available manometers cannot accurately measure very low pressure differentials ap plications with less than 2 54 m sec of duct air speed may require one of the following 1 the use of a current sourcing pressure transmitter per Section 7 2 or 2 the use of ...

Страница 4: ...lor coded to prevent wiring mistakes Improper connections can prevent a system from responding properly in the event of a fire For signal wiring the wiring between interconnected detectors or from detec tors to auxiliary devices it is recommended that single conductor wire be no smaller than 18 gauge The duct smoke detector terminals accommodate wire sizes up to 12gauge Smoke detectors and alarm s...

Страница 5: ...low out the residual aerosol smoke from the chamber and reset the duct smoke detector Use duct tape to seal the aero sol smoke entry hole CAUTION Canned aerosol simulated smoke canned smoke agent formulas will vary by manufacturer Misuse or overuse to these products may have long term adverse effects on the smoke detector Consult the canned smoke agent man ufacturer s published instructions for an...

Страница 6: ...thorization number send defective units to Returns Department RA __________ Pittway Tecnologica Srl Via Caboto 19 3 34147Trieste Italy Please include a note describing the malfunction and suspected cause of failure The Company shall not be obligated to replace units which are found to be defective because of damage unreasonable use modifications or alterations occurring after the date of manufactu...

Отзывы: