background image

ENGLISH - 4/8

MI004530-E

t

AN

ALOG

INPUTS

DIGIT

AL

POWER SUPPLY

RELAIS

DIGITAL

OUTPUTS

IDC10

RS485

RJ45

ANT.

RS232

USB

1500 V

A

3000 V

A

4

2

3

10 11 12

24

19

6

5

...

...

13

18

STANDARDS

EN61000-6-4

Electromagnetic emission, industrial environment.

EN61000-6-2

Electromagnetic immunity, industrial environment.

.

EN301 511

Harmonized standard for mobile stations

.

EN301 489-1

ElectroMagnetic Compatibility for radio equipment

.

EN301 489-7

Specific (EMC) conditions for mobile radio equipment

EN60950

Safety of information Technology Equipment.

INSULATION

ENVIRONMENTAL
CONDITIONS

Temperature
Humidity
Storage temperature
Protection rating

-10    + 50°C / (-10    + 40°C with internal UPS use).

30% –

t

ing.

90% no  condens

-20    + 65°C / (-20    + 45°C < 6

with internal UPS use).

months

IP20.

MOUNTING

35mm IEC EN60715 DIN Rail.

INTERNAL UPS

Backup

. Duration: up to 1 hour.

rechargeable batteries

CONNECTIONS

Removable three pole screw terminal pitch 5mm, for cable up to 2.5 mm ,

2

rear IDC10, front RJ45, Micro USB and Antenna SMA.

POWERSUPPLY

Voltage
Power absorbed

11 – 40 V

or 19 – 28 V

.

~

~

50

60 Hz

< 6.5W.

DIGITAL INPUTS

Number of channels 4. PNP or NPN configurable.
Input voltage OFF<4V ON>8V (Max. 24V ). Input current 20mA.

C

Max. frequency 30Hz. Absorbed Current 3mA at 12V

10mA at 24V .

C

C

TOTALIZERS

32 bit totalizers 4x on non-volatile memory.

COUNTERS

32 bit resettable counters 4x on non-volatile memory.

DIGITAL OUTPUTS

Number of channels

SPDT Relays with free contacts.

2.

Max. Voltage 250V . Max. Current 2A.

A

ANALOG INPUTS

Number of channels 2. mA

or V

configurable.

C

C

Voltage input 0 – 30V. accuracy 0.1% of the Full Scale.
Current input 0    20mA

accuracy 0.1% of the Full Scale.

Inputs protection 40V / 25mA. Resolution 16 bit.

COMMUNICATION
PORTS

Rear RS485 COM1 port. RS485 or RS232 M10-M11-M12 COM2 screw
terminals port. Ethernet 10/100 baseT RJ45 frontal port with autoswitch.
MicroUSB side port.

TECHNICAL SPECIFICATIONS

ENGLISH - 3/8

MI004530-E

t

LED

Status

LED’s meaning

DI1

(Red)

ON (NPN)

Digital Input 1: Energized (

closed contact

GND

)

ON (PNP)

Digital Input 1: Energized (

closed contact

+12V

)

OFF

Digital Input 1: De-energized (open contact)

DI2

(Red)

ON (NPN)

Digital Input   : Energized (

closed contact

2

GND

)

ON (PNP)

Digital Input   : Energized (

closed contact

2

+12V

)

OFF

Digital Input   : De-energized (open contact)

2

DI3

(Red)

ON (NPN)

Digital Input   : Energized (

closed contact

3

GND

)

ON (PNP)

Digital Input   : Energized (

closed contact

3

+12V

)

OFF

Digital Input   : De-energized (open contact)

3

DI4

(Red)

ON (NPN)

Digital Input   : Energized (

closed contact

4

GND

)

ON (PNP)

Digital Input   : Energized (

closed contact

4

+12V

)

OFF

Digital Input   : De-energized (open contact)

4

PWR/STS

(Green)

ON

n

Z-UMTS ON inactive log (status=ready)

Slow Blinking

2.8 sec ON 0.4 sec OFF

nnnnnnnnnnnnnnoo

Z-UMTS active log (status=normal)

Slow Blinking

1.6 sec ON 1.6 sec OFF

nnnnnnnnoooooooo

Battery powered inactive log (status=battery backup)

Medium Blinking

0.8 sec ON 0.8 sec OFF

nnnnoooonnnnoooo

Low battery warning

Fast Blinking

0.2 sec ON 0.2 sec OFF

nononononononono

Z-UMTS initializing or shutdown

Fast Blinking

0.6 sec

1 sec OFF

non

nonooooononooooo

Error, please refer to the diagnostic

OFF

o

Z-UMTS OFF

SD/STS

(Red)

ON

n

SD card mounted in the right way

Medium Blinking

0.8 sec ON 0.8 sec OFF

nnnnoooonnnnoooo

SD card activity

Fast Blinking

0.2 sec ON 0.2 sec OFF

nononononononono

SD card error

OFF

o

SD card not present

ETH LNK

(Green)

Blinking

RJ45 connection activated

ETH TRF

(Yellow)

Blinking

Traffic on Ethernet port

LED SIGNALING ON FRONT PANEL

ENGLISH - 2/8

MI004530-E

t

LED

Status

LED’s meaning

DO1

(Red)

ON

Digital output 1, relay energized

OFF

Digital output 1, relay de-energized

DO2

(Red)

ON

Digital output   , relay energized

2

OFF

Digital output   , relay de-energized

2

485 ACT

(Green)

Slow Blinking

2.8s ON

0.4s OFF

n

o

nnnnnnnnnnnnnnoo

RS485 activity or RS232 activity

OFF

o

RS485 or RS232 serial interface not used

Fast Blinking

0.2s ON

0.2s OFF

n

o

nononononononono

RS485 or RS232 communication Timeout

GSM

(Yellow)

ON

n

nnnnnnnnnnnnnnnnnnnn

HSDPA / HSUPA / HSPA+ / DC-HSPA Mode

Blinking

1.9s ON

0.1s OFF

n

o

nnnnnnnnnnnnnnnnnnno

WCDMA Mode

Blinking

1.7s ON

0.3s

n

ono

nnnnnnnnnnnnnnnnnono

GSM / GPRS / EDGE Mode

Fast Blinking

0.1s ON

0.1s OFF

n

o

nononononononononono

N

or Missing Signal

etwork Searching

OFF

o

Modem OFF

LED SIGNALING ON FRONT PANEL

Dimensions (L×H×W)

35 x 100 x 111 mm (with terminals).

Weight

250 g.

Case

Material PA6, black color.

100 mm

Z-UMTS

Connector

Rear bus

ETHERNET

micro

USB

Analog

IN 1, 2

6

5

4

RS485/RS232

COM2 (SW2)

15

14

13

Digital

IN 1, 2

Relay

OUT 1

18

17

16

Digital

IN 3, 4

Relay

OUT 2

10

11

12

19

20

21

22

23

24

Power

supply

3

2

1

MADE IN IT

AL

Y

ET005040B

HSP

A+ unit - RTU

multiprotocol datalogger

Power Supply

1

1

40 V

~

19

28 V    (50

60Hz)

~

Max 6.5 W

micro

SD Card

SIM

CARD

RS485 COM1 and

Power Supply

1

1

1 mm

1112

10

20 21

19

2324

22

35 mm

19 2021
22 23 24

13 1415

DI4

DI3

DI2

DI1

1 2 3

4 5 6

10 11 12

SENECA

ETH
TRF

ETH
LNK

PWR/

STS

SD/

STS

16 17 18

DO2

DO1

S

485
ACT

ETHERNET

ANTENNA

Z-UMTS

micro

USB

MODULE LAYOUT

ENGLISH - 1/8

ENGLISH LANGUAGE INSTRUCTIONS

MI004530-E

This document is property of SENECA rl. Duplication and reproduction are forbidden, if not authorized.

S

Contents of the present documentation refers to products and technologies described in it.
This informations may be modified or integrated for technical and / or commercial requirements.

SENECA s.r.l.

Headquarters: Via Austria, 26 – 35127 – PADOVA – ITALY

Phone +39.049.8705355 - 8705359  -  Fax +39.049.8706287

Manuals and configuration software are available at website:

www.seneca.it/products/z-umts

EN

EN

Datalogger HSPA + with built-in I/O, telecontrol functions,

embedded UPS and advanced programming language

Z-UMTS

INSTALLATION MANUAL

Reviews: