IRD 810 / 820

740e/05/94

INTRODUCTION

The IRD 810 or 820 is employed to monitor the flame of an
oil and/or gas burner. This flame monitoring device should
be connected to a Satronic oil or gas burner control box.
Monitoring is based on the infra-red flicker principle, in other
words, the flickering infra-red light of the flame is detected.
The steady radiation from, for example, the glowing refractory
layer on the inside of the boiler, has no effect on the detector.
The detectors are also available in 110 V versions or in an
industrial version which has a particularly robust and water-
proof detector probe.

TYPES AVAILABLE

IRD 810

No potential difference at working contact
4-pole connection

IRD 820

With simulation of ionisation current
For 3-pole connection to Satronic gas burner
control boxes

CONSTRUCTIONAL FEATURES

The monitoring device consists of the detector probe and
the electronics. The infra-red sensor and the pre-amplifier
are hermetically sealed in glass and along with the electronics
form an integral part of the flame detector.
The indicator control unit contains a mains transformer and
a relay which transmits the flame signal to the appropriate
control box via a working contact which carries no other
potential difference. Signal strength is indicated by a row of
5 LED’s. Beside the LED’s is a potentiometer for infinitely
variable adjustment of the sensitivity.
A fixed cable runs between the flame detector and the
indicator control unit. This cable must not be disconnected.
Power is supplied through either a 3 or 4-core cable (live,
neutral and flame signal).

Infrared Flicker Detector

TECHNICAL DATA

Supply voltage

220 / 240 V (-15... +10%)
50 Hz (40 - 60 Hz)

Power consumption

2 VA

Max. current output terminal

2 A, 250 V

Permissible ambient temp.

-20

°

 to +60

°

 C

Insulation standard

IP 41

Mounting attitude

any

Weight

250 g

Flame viewing attitude

side-on and end-on

Spectral response

800 - 1100 nm

Max. sensitivity

950 nm

Frequency range

15 - 150 Hz

Max. sensitivity

30 Hz

Response time

0,1 sec.

Cancelling time

0,5 sec.

Cable length, detector -
indicator ctrl. unit
Normal version

0,5 m

Industrial version

1,0 m

Flame monitoring device for
oil and/or gas flames

With a row of 5 LED indicators and
adjustable sensitivity

Summary of Contents for IRD 810

Page 1: ...n integral part of the flame detector The indicator control unit contains a mains transformer and a relay which transmits the flame signal to the appropriate control box via a working contact which carries no other potential difference Signal strength is indicated by a row of 5 LED s Beside the LED s is a potentiometer for infinitely variable adjustment of the sensitivity A fixed cable runs betwee...

Page 2: ... for normal operation pull out the detector probe and cover it up to cut off light The LED indicators must go out The control box should switch to lockout or attempt to restart the sequence 4 Attempttorestartwiththeflamedetectorcovered There must be no indication from the LED s The burner control box must switch to lockout at the end of the safety interval 5 Attempt to start the burner with the de...

Page 3: ...G THE IRD 820 TO SATRONIC OIL BURNER CONTROL BOXES IONISATION PROBE CONNECTION Control box type IRD 820 cable core colours max cable length IRD corresponding to control box m terminal no brown black light blue multiple cables laid separately MMI 810 9 2 8 2 200 MMI 812 9 2 8 2 200 MMG 810 9 2 8 2 200 TMG 740 2 740 3 20 1 8 2 200 IRD 810 AND 820 DETECTOR 50Hz 3VA 220V IRD 810 SR1 IP41 Swiss made by...

Page 4: ... detector IRD 820 110 volts 16221 Flame detector holder FZ Holder M 68 59068 Flame detector holder FZ Holder M 74 59074 Flame detector holder FZ Holder M 75 59075 Holder Industrial UVZ FZ 18807 The above ordering information refers to the standard version Spezial versions are also included in our product range Specificationssubjecttochangewithoutnotice M 74 DETECTOR MOUNT NORMAL VERSION 2 8 ø 6 3 ...

Reviews: