background image

Opal Pro to Mod TCP 

Page 1 

 

 
 
 
 
 

Opal Pro MS6 SERIES

 

AB Ethernet IP Interface Users Manual 

 

 

 

 

 

 

 

 

 

Revision 1.00 

Содержание Ethernet IP Interface MS6 SERIES

Страница 1: ...Opal Pro to Mod TCP Page 1 Opal Pro MS6 SERIES AB Ethernet IP Interface Users Manual Revision 1 00 ...

Страница 2: ...Opal Pro to Mod TCP Page 2 ...

Страница 3: ...s and technical representations included in this manual are for typical installations and should not in any way be considered for specific applications or modifications Consult SAF OPAL Starters for supplemental instructions Brock Solutions Inc accepts no liability for any consequences resulting from inappropriate negligent or incorrect installation application or adjustment of this equipment The ...

Страница 4: ...Opal Pro to Mod TCP Page 4 ...

Страница 5: ...Opal Pro to Mod TCP Page 5 Table of Contents INTRODUCTION 6 HARDWARE 6 JUMPER SETTINGS 6 LED INDICATORS 7 OPAL PRO PARAMETER SETTINGS 8 I O CONFIGURATION 10 ...

Страница 6: ...main Opal Pro control card CA530 Access is gained to the Ethernet card via the communication opening on the right side of the Opal Pro The Opal Pro is a AB Ethernet IP slave and is mapped as I O through an Ethernet bridge Hardware Connection is made via a 10Mbaud Ethernet port which utilizes a RJ45 connector Connection should be made using CAT 5 cable Jumper Settings Jumper Setting Description J3 ...

Страница 7: ... open check software firmware version of Opal Pro Solid Green No errors normal operation Amber Red Green Configuration Mode card is not configured contact Brock Solutions for support The lower LED indicator indicates the Ethernet Network status LED State Ethernet Network Status OFF Network interface offline No network power Flashing Red I O connection in timed out state or other Recoverable fault ...

Страница 8: ...ernal 10 05 Phase Angle Source Comm Module If this is set to Comm Module the Opal pro will follow the Phase Angle reference from the communication link If there is no reference being sent on the communication link this should be set to Internal 14 07 Node 1 254 This is the Node of the slave Opal Pro 14 08 IP Addr 1 0 255 First number in the IP address of the Opal Pro 14 09 IP Addr 2 0 255 Second n...

Страница 9: ...lt 15 05 Comm Fault Time 0 1 to 5 0 secs This is the time setting that the Opal Pro uses to detect a communication fault Bit 15 of the command word must change state twice with in the time set in this parameter If parameters in group 14 are modified the changes do not take effect until the control power for the Opal Pro is turned off and then back on again ...

Страница 10: ...it 5 Reserved Bit 6 Reserved Bit 7 Reserved Bit 8 Reserved Bit 9 Reserved Bit 10 Reserved Bit 11 Reserved Bit 12 Reserved Bit 13 Reserved Bit 14 Reserved Word 1 Output Word 0 Command Bit 15 Watch Dog bit this bit must change at least twice in the time set by parameter 15 05 Word 2 Output Word 1 Current Reference 0 1000 833 500 of Motor Current set in parameter 13 01 Word 3 Output Word 2 Phase Angl...

Страница 11: ...ault Bit 14 Reserved Word 1 Input Word 0 Status Bit 15 Watch Dog Bit Word 2 Input Word 1 Current Feedback 833 500 of motor name plate current as set in 13 01 Word 3 Input Word 2 Phase Angle Actual Amount of time phased on in microseconds Parameter AB Ethernet IP Name Description 1 01 Input Word 3 Current Current feedback in Amps 1 02 Input Word 4 L1 to L2 Voltage Line 1 to Line 2 Voltage in Volts ...

Страница 12: ...5 Ramp Time Time is seconds 10 03 Input Word 16 Step Current In of nameplate current 10 04 Input Word 17 Current Reference 7 Internal 8 Analog Input 9 Comm Module 10 05 Input Word 18 Phase Angle 10 Internal 11 Analog Input 12 Comm Module 10 06 Input Word 19 Jog Accel Current Limit In of nameplate current 10 07 Input Word 20 Jog Current Limit In of nameplate current 10 08 Input Word 21 Jog Ramp Tim...

Страница 13: ... 1 254 14 08 Input Word 38 IP Address 1 0 255 14 09 Input Word 39 IP Address 2 0 255 14 10 Input Word 40 IP Address 3 0 255 14 11 Input Word 41 IP Address 4 0 255 14 12 Input Word 42 SubNet 1 0 255 14 13 Input Word 43 SubNet 2 0 255 14 14 Input Word 44 SubNet 3 0 255 14 15 Input Word 45 SubNet 4 0 255 15 01 Input Word 46 Shear Pin Flt 34 Enabled 35 Disabled 15 02 Input Word 47 MOL Fault 36 Disable...

Страница 14: ...Opal Pro to Mod TCP Page 14 NOTE The Opal Pro must have firmware version 1 70 or higher ...

Отзывы: