background image

www.rotronic.com

English

12.1067.9101E

RMS-GW-915

 

Short Instruction Manual

GENERAL DESCRIPTION

Congratulations on your new RMS gateway. The gateway transmits the 
data of the wireless data loggers continuously to the RMS software by 
Ethernet. These short instructions describe the main functions of the 
device.

Please read this short manual and the instruction manual on 

www.rotronic.com/rms

 carefully.

1.1   COMMISSIONING

The device must be supplied with 24 V (terminals: V+ / V-) or via PoE to be able to transmit data. 
The gateway can be mounted easily with the wall bracket. The device is connected to the RMS 
software by pairing.

Important: Port 80, DHCP

To integrate the device, port 80 must be enabled in your network and a DHCP server must assign 
the IP address to the device.

INTEGRATION OF THE GATEWAY (PAIRING) IN 6 STEPS

1. 

If you do not want to connect the device to the Rotronic Cloud, the server must be configured  

  in the device.

a. 

Connect the device to the local network and start the RMS configuration software.

b.  Search for the device under 

Device > Search > Network Device

. The software finds all RMS  

  devices in the local network.
c.  Enter the host (server address) and the 

URL of the software services under Settings.

d. 

Finish configuration with 

Write. 

2.  Log into the RMS software / cloud.  
 Select 

Tools > Setup > Devices > New >  

  LAN device 
 
 

3.  Enter the serial number of the device. 
 
 
 
 

4. 

Wait until the device is flashing orange.

 

  Press the button on the device briefly, 

 

  as shown in the picture on the RMS  

  software. The LED flashes green, 

 

  when connection is succesful. 
 
 
 
 
 

5.  Enter the device name, channel and  
 group. 
 
 
 
 
 
 
 
 

6. 

Finish configuration.

 

 

LED INDICATORS

Status

LED Function

Meaning

Connected

Flashes green

Status OK

Flashes red

2 times: no connection to the server

Not connected

Flashes orange

Device in pairing mode, push the button for integ-
ration into the software

4 ACCESSORIES

AC1321  

 

Mounting kit with Allen key and mounting cone

TECHNICAL DATA

Power supply:  

 

  24 VDC ±10 % / <100 mA

Power supply requirements:  

  24 VDC ±10 % / >4 W / limited power source

Range of measurement / application:   -40…70 °C
IP protection: 

 

  IP65

Software:  

 

  RMS Monitoring Software

Weight:  

 

  200  g

6 DIMENSIONS

DELIVERY PACKAGE

•  Gateway
•  Wall bracket
•  Short instruction manual

This equipment has been tested and found to comply with the limits for a Class A digital de-
vice, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable 
protection against harmful interference when the equipment is operated in a commercial 
environment. This equipment generates, uses, and can radiate radio  frequency energy 
and, if not installed and  used  in  accordance  with  the  instruction  manual, may cause 
harmful interference to  radio  communications.  Operation of this equipment in a residen-
tial area is likely to cause harmful interference in which case the user will be required to 
correct the interference at his own expense

Any changes or modifications to this device not explicitly approved by manufacturer could 

void your authority to operate this equipment.

105 mm

113 mm

38 mm