Fuse and Line Filter sizing for the Kinetix 5500 drive

530800 | Date Created: 03/03/2013 | Last Updated: 01/11/2018

 

Access Level: Everyone

 Print

Question

How do I size my fusing and line filter for the Kinetix 5500 drive?

Answer

Refer to documents in this tech note:

The 

Kinetix 5500 User Manual

(http://literature.rockwellautomation.com/idc/groups/literature/documents/um/2198-um001_-en-p.pdf)
Publication 2198-UM001 appendix C for tutorial of sizing main and control power for various application
configurations.
The 

Kinetix 5500 Design Guide

(http://literature.rockwellautomation.com/idc/groups/literature/documents/rm/gmc-rm009_-en-p.pdf)
Publication GMC-RM009
The 

Kinetix Servo Drive Technical Documentation

 (http://gmc-td003_-en-p.pdf/), Publication gmc-td003

Use the Motion Analyzer Software to evaluate your machine load inertia, transmission and cycle profile
characteristics.
Refer to other ancillary device documentation such as VPL motor, line filter installation and other as required.

To size your Kinetix 5500 fusing, circuit breaker and line filter, you will be required to know the exact configuration
of converter/inverter power modules based on the application requirement.

The Kinetix 5500 supports multiple configurations:

1. 

STAND-ALONE

In this example, AC line power is transferred solely to the 2198-H040-ERS module and converter for use for motor
inverter output.

Summary of Contents for Allen-Bradley Kinetix 5500

Page 1: ...Kinetix 5500 Design Guide http literature rockwellautomation com idc groups literature documents rm gmc rm009_ en p pdf Publication GMC RM009 The Kinetix Servo Drive Technical Documentation http gmc...

Page 2: ...98 um001_ en p pdf Chapter 2 Planning the Kinetix 5500 Drive System Installation and the Kinetix Servo Drive Technical Documentation http gmc td003_ en p pdf Recommended Components for the Stand Alone...

Page 3: ...ferent AC line characteristics such as inrush in order to have a symmetrical AC power up AC Sharing configuration does not support use of the 2198 capacitor module for similar reasons as item 2 above...

Page 4: ...bus capacitive absorption and more ability to handle regenerative energy on the entire DC bus This configuration MUST be used with the available AC bus bars DC bus bars and DC control power bus bars S...

Page 5: ...p pdf Kinetix Servo Drive Technical Documentation http gmc td003_ en p pdf Use Qty 1 2198 H040 ADP IN for the first 2198 H015 ERS which will allow you to bring in both AC L1 L3 and ground DC control...

Page 6: ...40 ERS use KTK R 25 fuses Other recommended fusing can be found in the Kinetix Servo Drive Technical Documentation http gmc td003_ en p pdf With DC shared the leader converter power MUST be able to su...

Page 7: ...oth DC Shared power and DC control power bus bars The 2198 H040 ERS is a frame 3 Kinetix 5500 as referenced in the Kinetix 5500 User Manual http literature rckwellautomation com idc groups literature...

Page 8: ...For configuration use Qty 2 2198 H015 ERS Qty 1 2198 H008 ERS and Qty 1 2198 H003 ERS A 2198 CAPMOD 1300 is also specified for adding DC bus capacitance and ability to assist in DC bus capacitance abs...

Page 9: ...ith DC bus and DC control power sharing Three phase power to the leader module MUST be used for Shared DC configuration Single Phase operation is not supported in Shared DC configuration The largest l...

Page 10: ...RETO AT ANY TIME IN ITS SOLE DISCRETION WITHOUT NOTICE FURTHER ALL INFORMATION CONVEYED HEREBY IS PROVIDED TO USERS AS IS IN NO EVENT SHALL ROCKWELL BE LIABLE FOR ANY DAMAGES OF ANY KIND INCLUDING DIR...