INSTALLATION INSTRUCTIONS

95-6999-08

V404, V504, V524, V804, and VS824 
Automatic Valve Operators

APPLICATION 

These valve operators provide automatic main valve 

operation in the VB00, VRB00, and VR8440 families of 

combination gas controls. The operators are 

interchangeable and can be used either for replacement 

or to add automatic operation to a C580/CS580 series 

manual valve. They cannot be used on VR850 series 

two-stage valves. 

The V404, V804, and VSB24 are magnetic operators. 

They contain an electromagnet that is energized to open 

the main valve when the thermostat contacts close on a 

call for heat. The V404/V804/VS824 replacement 

operator package includes: 

• Operator 

• Operator Gasket 

• Two Round Regulator Gaskets 

• 388589BA Mounting Screws for Standard Capacity 

Valves 

The V504 and V524 are mechanical operators. They use 

a bulb ·and bellows assembly filled with a temperature-

sensitive liquid to open and close the main valve. The 

liquid expands and contracts with temperature changes, 

expanding and contracting the bellows and operating 

the valve. V504 provides modulating control; V524 

provides on-off control. The V504/V524 replacement 

operator package includes: 

• Operator 

• Operator Gasket 

• 394018 Red Knob and Setscrew 

• 394138 Red Knob and Setscrew 

• 394075 Black Knob and Setscrew 

• 388589BF Mounting Screws for Standard Capacity 

Valves 

The bulb and bellows assembly must be ordered 

separately; see Table 2

Longer screws are required to mount the operators on 

nigh capacity valves. Obtain four screws locally as 

follows: 

V404, V804, VS824-No. 8-32 UNG, 1-13/16 in. V504, 

V524-No. 8-32 UNG, 2-3/8 in. 

Ambient temperature ratings are as follows:

V404A, V804A, VSB24A-plus 32 F to 175 F [0 C to 

80 C]

V404B, V804B, VS824B-minus 40 F to plus 175 F 

[minus 40 C to plus 80 C]. 

V504, V524-plus 32 F to 125 F [0 C to 52 C].

The V504 and V524 operators include a pressure reg-

ulator; see Table 1 for settings. A separate pres-

sure regulator is used with the V404, V804, VS824 

operators.

Table 1. Automatic Valve Operator Application. 

Operator 

Model 

Number

Pressure Regulator Setting

Control

Add-on or Replacement 

Operator on:

Min. Rate

Full Rate

Adjustment

in. wc

kPa

in. wc

kPa

V504A 1.2

0.3

3.5

0.87

Limited

Mechanical 

temperature-sensitive 

bulb

C580,C581, V500, V501, 

V510, V511 

V504B 

4.0

1.0

11.0

2.7

For LP gas

Summary of Contents for V404

Page 1: ...ng the valve V504 provides modulating control V524 provides on off control The V504 V524 replacement operator package includes Operator Operator Gasket 394018 Red Knob and Setscrew 394138 Red Knob and Setscrew 394075 Black Knob and Setscrew 388589BF Mounting Screws for Standard Capacity Valves The bulb and bellows assembly must be ordered separately see Table 2 Longer screws are required to mount ...

Page 2: ...ivoltage system the entire system is powered by the millivoltage generated by the Powerpile generator It is important to clean and scrape all wires before connecting Solder and tape all necessary splices using rosin flux to prevent corrosion Tighten terminal screws firmly Total control circuit wiring must not exceed 30 ft 9 m of 2 wire 18 gauge cable or 50 ft 15 m of 2 wire 16 gauge cable V524A 3 ...

Page 3: ...regulator gasket 3 Remove old operator from valve body Discard old operator and gasket REMOVING ADAPTER CASTING FROM MANUAL VALVE 1 Remove pressure regulator or blank cover plate Save regulator or cover plate for reassembly to operator Save gasket for blank cover plate discard pressure regulator gasket 2 Remove adapter casting from valve body See Figs 1 and 2 Discard casting and gasket INSTALLING ...

Page 4: ...s hole See Fig 4 5 If control has pressure regulator choose the cor rect new pressure regulator gasket see Fig 3 Press gasket into circle on operator casting align ing tab with recess in casting See Fig 4 Position regulator over gasket and fasten with two screws used originally For V5307 put the longer screw provided with the regulator in the outside corner hole Tighten screws evenly and securely ...

Page 5: ...splices using rosin flux to prevent corrosion Tighten terminal screws firmly Total control circuit wiring must not exceed 30 ft 9 m of 2 wire 18 gauge cable or 50 ft 15 m of 2 wire 16 gauge cable 1 Install millivoltage thermostat limit controller if required and Powerpile generator according to manufacturer s installation instructions 2 After Powerpile generator is installed route gener ator lead ...

Page 6: ... 32 UNC 2 3 8 in long screws obtain locally for high capacity valves 10 If the bulb and bellows assembly is new follow the instructions provided with the assembly to install the bulb and the remote dial assembly if used Fig 9 Form capillary smoothly and without crimping to fit in hole in operator Fig 10 Mounting the V504 and V524 operator on a standard capacity valve Cabinet mounted dial shown Fig...

Page 7: ... place 6 If using 394138 Dial insert 1 4 in rod obtain locally into end of dial Align hole in end with hole in dial sleeve Fasten with cotter pin 7 Turn dial to desired setting making sure the cali bration knob is turning with the dial If not repeat steps 2 5 Fig 12 Calibrating V504 V524 with dial on operator V504 V524 WITH DIAL MOUNTED ON CABINET 1 Light pilot as described under Pilot Lighting Pr...

Page 8: ...naturally Do not light pilot or operate electric switches lights or appliances until you are sure work area is free of gas Failure to follow these instructions may result in an explosion 2 Turn the Lite Rite knob to PILOT depress it com pletely and light the pilot burner while holding it down Hold the knob down about one minute If the pilot goes out when the knob is released repeat steps 1 and 2 3...