WARNINGS

When Designing your GLC System:

- Be sure to design your GLC control system so that in the event of a main power
supply failure or a GLC accident, the user system’s overall safety integrity will be
maintained. If this is not done, incorrect output signals or a GLC malfunction may cause
an accident.
(1) Interlock circuits, etc. designed to interrupt or oppose normal machine movement

(i.e. Emergency Stop, General Protection, forward and reverse rotation, etc.), as well
as those designed to prevent machine damage (i.e. for upper, lower and traverse
movement limit positioning, etc.) should all be designed to be located outside of the
GLC.

(2) Whenever the GLC generates a “Watchdog Timer Error”, GLC operation will halt.

Also, when Errors occur in Input/Output control areas that the GLC cannot detect, it
is possible for unexpected movement to occur in those areas. As a result, for the
purpose of preventing unsafe machine movement, a “Failsafe Circuit” should be
created which is completely external to the GLC.

(3) If an problem arises with an external unit’s relay or transistor, causing an output

(coil) to remain either ON or OFF, a major accident can occur. To prevent this, be
sure to set up external watchdog circuits that will monitor vital output signals.

- Design a circuit that will supply power to the GLC’s I/O unit before starting up the

GLC. If the GLC’s internal program enters RUN mode prior to the I/O unit’s load
control power turning ON, an incorrect output (signal) or malfunction could cause an
accident to occur.

- Design a user program that will ensure the safety of the user’s system, in the event of a

GLC display or control error, or in the event of either a data transmission error or
power failure between the GLC and a connected unit. These types of problems can
lead to an incorrect output (signal) or malfunction, which could thereby cause an
accident to occur.

- Do NOT use GLC touch panel switches to perform life-related or important accident

prevention operations. These operations should be performed by separate hardware
switches to prevent operator injury and machine damage.

Wiring Warnings:

- To prevent electric shock or equipment damage, prior to installing or wiring the GLC,

confirm that the GLC’s power cord is unplugged from the power supply.

- After completing any GLC wiring work, be sure the terminal block’s protective plastic

cover is reattached. If this cover is not reattached, an electric shock could easily
occur.

- High voltage runs through the GLC. Except for changing the backlight, do NOT

attempt to open the GLC, since there is a possibility of an electric shock.

- Do not use power levels with the GLC that are outside of the GLC’s specified power

range. Doing so may cause a fire, electric shock or damage the GLC.

- Do not operate or store the GLC in areas where flammable gasses are present, since

operating the GLC may cause an explosion.

DANGERS

Summary of Contents for GLC300-TC41-24V

Page 1: ...e GLC If the GLC s internal program enters RUN mode prior to the I O unit s load control power turning ON an incorrect output signal or malfunction could cause an accident to occur Design a user program that will ensure the safety of the user s system in the event of a GLC display or control error or in the event of either a data transmission error or power failure between the GLC and a connected ...

Page 2: ...e damaged if it falls off the back of the GLC or a system related malfunction or accident may occur due to I O data signal problems Be sure any data cable attached to the GLC s connector is securely attached If the cable and connector pins do not all make complete contact incorrect input or output signals can result General Wiring Cautions To prevent shocks or malfunctions GLC s FG earth wire shou...

Page 3: ...rements Installation and operation instructions are provided with each GLC These installa tion instructions contain the following statements 1 Power input and output I O wiring must all be in accordance with Class I Division 2 wiring methods Article 501 4 b of the National Electrical Code NFPA 70 or as specified in Section 18 152 of the Canadian Electrical Code for units installed within Canada an...

Page 4: ...ontact your local GLC dis tributor immediately Package Contents User s Manual Sold Separately GLC300 User s Manual GLC Option Items Logic Program Development soft ware Sold Separately Pro Control Editor GLC Unit GLC300 TC41 24V Operation Instructions 1 this sheet Installation fasteners 4 pcs Operation Instructions Digital GLC300 MM01 ENG Digital GLC300 GLC300 GLC300 GLC300 GLC300 User s User s Use...

Page 5: ...PLC C Power Lamp Lights up when the power is turned On Normally Green LED D Power Input Terminal Block The input and ground terminals for AC power cable E Auxiliary Input Output AUX Operates the Touch Switch System Alarm Buzzer Run outputs and Remote Reset inputs F Serial Interface RS 232C RS 422 Serial interface Connect to the Host G Printer Interface Connect the printer here H Tool Connector Con...

Page 6: ...XM2A 2501 madebyOMRONCorp RecommendedCover Dsub25pinCover XM2S 2511 madebyOMRONCorp JackScrew XM2Z 0071 madebyOMRONCorp Use rough metric type M2 6 x 0 45p threads used to hold the cable s set fastening screws in place RecommendedCable CO MA VV SB5Px28AWG madebyHITACHICableLtd 1 13 14 25 Pin 14 can be used for the power supply for the user s optional equipment connected to the GLC Pin 14isnotprotec...

Page 7: ...wareAlarm SCREENMEMORYCHECKSUMERROR Software Alarm SYSTEM ERROR i e incorrect data that makes continuation of screen operation impossible or when Watchdag Timer s Alarm output occurs11 RecommendedConnector Dsub15pinPlug XM2A 1501 madebyOMRONCorp RecommendedCover Dsub15pinCover XM2S 1511 madebyOMRONCorp JackScrew XM2Z 0071 madebyOMRONCorp Use rough metric type M2 6 x 0 45p threads used to hold the ...

Page 8: ...asteners with a screwdriver To create a waterproof seal a force of 0 5 0 6N m is required Panel GLC unit Tightening the screws with too much force can damage the GLC Before installing the GLC be sure that the moisture resistant gasket is attached securely to the unit 6 Installation Rear of GLC Gasket 1 6mmto10mm Panelthickness 302 under 4 R2 228 Unit mm 0 1 0 1 ...

Page 9: ...ill result in excess noise and vibration Wherever possible use thick wires max 2 mm2 for power terminals and twist the wire ends before attaching the ring terminals Be sure to use the following size Ring Terminals 7 Wiring Under 6 0mm Over φ 3 2 mm WARNING 1 Ring Terminal to use V2 MS3 made by JST Rear side FG FG Ring Terminals 1 Power Input Terminal Block Connect the power cable following the ste...

Page 10: ...in circuit lines high voltage high current or input output signal lines Connect a surge absorber to deal with power surges To reduce noise make the power cable as short as possible 8 Precautions for Supplying Power 11 Replacing the Backlight 10 Precautions for Input Output Signal Lines Input and Output signal lines must be separated from the power control cables for op erational circuits if this i...